GAMEWELL-FCI FLEX4

Flex 4 & Flex 8
Description
The Gamewell Flex 4 and Flex 8 Fire Alarm Control Panels
are designed for small to medium commercial, residential, institutional and industrial occupancies. Simple and easy configuration of the microprocessor-based controls is accomplished via DIP switches.
Superior product flexibility allows compliance with the specific
job requirements at each installation. Two standard
configurations are available. The Flex 4 includes 4 Class B
(Style B) Initiating Device Circuits (IDCs), which are easily
programmed and wired to perform as 2 Class A (Style D)
circuits. For signaling an alarm condition, the Flex 4 provides
2 Notification Appliance Circuits (NACs) that may be wired for
Class A/B (Style Z/Y) performance and are rated for loads up
to 1.7 Amperes each.
With twice the circuit capacity, the Flex 8 provides 8 Class B
IDCs, which are easily configurable as 4 Class A circuits and
4 Class A/B NACs. Each NAC is also rated for a maximum of
1.7 Amps, with total notification appliance power for the Flex
8 at 5 Amps maximum. A Flex 4 may be expanded in the field
to provide the circuit capacity of a Flex 8 by installing a Circuit
Expander Module (CEM.) The CEM provides an additional 4
Class B (2 Class A) IDCs and 2 Class A or B NACs.
All initiating circuits of the Flex 4 and Flex 8 are factory set to
operate for Class B (Style B) wiring performance. Through
field programming, all circuits can easily be converted to Class
A (Style D) circuits.
An integral 6 Amp power supply is included in both products
to provide system power, 4-wire resettable smoke power (24
VDC @ 100 mA) and up to 5 Amps of notification appliance
power.
Programming
The Flex 4 and Flex 8 use simple DIP switches for
programming IDCs and NACs, as well as enabling and
disabling of system functions such as signal silence, fire drill
and auxiliary disconnect. Notification circuits may be
configured for audible or visual devices and silenceable or
non-silenceable operation. The Flex 4 and Flex 8 allow for
alarm verification on all Initiating Device Circuits (IDCs).
Predefined IDCs may be optionally configured for Waterflow
(zone 3 [Flex 4] or zones 3 & 7 [Flex 8]) or Latching/NonLatching Supervisory (zone 4 [Flex 4] or zones 4 & 8 [Flex 8]).
Conventional
Fire Alarm
Control Panels
Approvals
UL Listed
CSFM, MEA Approved
Features
• Initiating Device Circuits (IDCs) may be individually
configured for:
> General Alarm
> Waterflow
> Supervisory
> Alarm Verification
• Supervisory operation may be Latching or Non-Latching
• Notification Appliance Circuits (NACs) may be
programmed as:
> Silenceable
> Non-Silenceable
> Auto-Silenceable
> Coded (March Time, Temporal Code, California
Code)
• 5.0 Amps of total NAC power
• Common Alarm, Supervisory and Trouble contacts
• Resettable four-wire smoke detector power @ 100 mA
• Integral Walk Test operation
• EIA-485 interface for up to 3 model RA8 Remote
Annunciators
• Polarity Reversal and City Tie connection (optional)
• Digital Alarm Communicator Transmitter DACT (optional)
• Relay-by-zone capability with RY4 (Flex 4) or RY8
(Flex 8) modules
CS-2081 Rev. 1201-3
Page 1
DACT Digital Alarm Communicator
Transmitter/Dialer
Relay Module RY8
Remote Trouble Indicator
RA8
Remote Annunciator
Configuration and Programming Tool
CFG
The Flex 4 and Flex 8 can meet the following UL installation system designations (with indicated options selected):
•
•
•
•
Local, Auxiliary (using PRM),
Remote Station Protected Premises (using DACT or PRM),
Central Station Protected Premises (using DACT).
Type of Service / Signaling A, M, WF, SS (SS is only Local or with DACT)/Non-coded
Specifications
Flex 4 & Flex 8 Fire Alarm Control Panels
Primary Input Power:
Secondary Power:
Battery Charging Capacity:
Initiating Device Circuits:
IDC Compatibility Identifier:
Total Output Power:
NAC Output Ratings:
Auxiliary Power Output:
4-Wire Smoke Power:
Current Consumption:
Main Circuit Board Fuse:
Auxiliary Relays:
Alarm, Trouble, Supervisory:
EIA-485 Connection:
Trouble Indication Output:
End-of-Line resistor (30177):
102—132 VAC, 60 Hz, 4 Amp
Two 12-volt batteries (in series)
Up to 24 Amp hours max.
26 VDC, .003 A standby, 1.5Vp-p ripple, .050 A max. (alarm), power-limited
“GWC01”
6 Amp maximum
24 VDC unfiltered, 1.7 Amp max. / circuit (5 Amp max.), power-limited
24 VDC unfiltered, .3 A max., power-limited
28 VDC unfiltered, .100 A max., 1.5Vp-p ripple, resettable, power-limited
.110 A standby, .220A alarm
10 Amp
1 Amp resistive, 28VDC, Form-C
Connects up to 3 RA8 Remote Annunciators
Controls single RTI Remote Trouble Indicator
3.9 K-Ohm, 1/2 Watt, 5% with spade lugs—UL Listed
Flex 4 & Flex 8 Optional Modules
RA8—Remote Annunciator, 8-Zone:
Current Consumption:
.035 A standby, .090 A alarm
RTI—Remote Trouble Buzzer:
Current Consumption:
.035 A standby, .035 A alarm
DACT—Digital Alarm Communicator Transmitter:
Current Consumption:
.045 A standby, .120 A alarm
RY4—Relay Module, 4 Form-C:
Current Consumption:
.005 A standby, .160 A alarm 1 Amp resistive, 28 VDC
RY8—Relay Module, 8-Form-C:
Current Consumption:
.005 A standby, .160 A alarm 1 Amp resistive, 28 VDC
PRM—Polarity Reversal / City Tie Module:
Current Consumption:
.035 A standby, .3 A alarm Supervised City Tie: 24 VDC unfiltered, .210 A
max., 14 Ohms trip coil, NOT power-limited
Polarity Reversal:
24 VDC open, 12 VDC @ .003 A, .008 A max. (shorted), power-limited
CEM—Circuit Expander Module (Flex 4 only):
Current Consumption:
.045 A standby, .120 A alarm
Initiating Device Circuits:
22 VDC, .003 A standby, 1.5Vp-p ripple, .050 A max. (alarm), power- limited
IDC Compatibility Identifier:
“GWC01”
NAC Output Ratings:
24 VDC unfiltered, 1.7 Amp max. / circuit , power-limited
Cabinet Dimensions:
Battery Space:
Relative Humidity:
Temperature Rating:
14” H x 14” W x 5” D
Two 12 AH batteries max.
93% non-condensing
0°C - 49°C (32°F– 120°F)
CS-2081 Rev. 1201-3
Ordering Information
Model
Flex 4
Flex 8
Accessories
CEM
DACT
Description
Four-zone, expandable, microprocessor-based Fire Alarm Control Panel with 4
Class B (Style B) or 2 Class A (Style D) Initiating Device Circuits (IDCs), 2 Class
A/B (Style Z/Y) Notification Appliance Circuits (NACs) and a 6 Amp power supply.
Expandable up to 8 Class B (Style B) IDCs or 4 Class A (Style D) and 4 Class A/
B (Style Z/Y) NACs. Allows for installation of one DACT Digital Alarm Communicator Transmitter or one PRM Polarity Reversal / City Tie Module and one RY4 or
RY8 Auxiliary Relay Module. Red, surface- or flush-mount enclosure with CAT-60
key locked door.
Eight-zone, microprocessor-based Fire Alarm Control Panel with 8 Class B (Style
B) or 4 Class A (Style D) Initiating Device Circuits, 4 Class A/B (Style Z/Y)
Notification Appliance Circuits and a 6 Amp Power Supply. Allows for Installation
of one DACT Digital Alarm Communicator Transmitter or one PRM Polarity
Reversal / City Tie Module and one RY4 or RY8 Auxiliary Relay Module. Red,
surface- or flush-mount enclosure with CAT-60 key locked door.
30177
CFG
71954-M
72052
Circuit Expander Module to field modify a Flex 4 to a Flex 8
Digital Alarm Communicator Transmitter Module. Transmits in ADEMCO Contact
ID and SIA-DCS protocols. CFG configuration and diagnostics tool is required for
programming.
Polarity Reversal / City Tie Module. (Note: Only one of a DACT or PRM module
can be used with the Flex 4 or Flex 8).
Auxiliary Relay Module with 4 configurable, Form-C relays. Relays programmable
for: Relay-by-Zone, Common Alarm, Common Supervisory, etc.
Auxiliary Relay Module with 8 configurable, Form-C relays. Relays programmable
for: Relay-by-Zone, Common Alarm, Common Supervisory, etc.
Remote Trouble Indicator with trouble LED and piezo buzzer.
Remote Annunciator with common control features, indicators and 8 bi-colored
LEDs.
UL Listed, End-of-Line Resistor assembly with wire leads and spade lugs.
Hand-held Configuration and Diagnostics programming tool for DACT.
Set of Manuals for the Flex 4 and Flex 8 product line
Flex 4 and Flex 8 Main Board/Display replacement.
Batteries
B12V4
B12V7
B12V12
Battery, 12 VDC, 4 Ampere Hour (2 required per panel).
Battery, 12 VDC, 7 Ampere Hour (2 required per panel).
Battery, 12 VDC, 12 Ampere Hour (2 required per panel).
PRM
RY4
RY8
RTI
RA8
Specifications and wiring information are provided for information only and are believed to be accurate. Gamewell assumes no responsibility for their use. Data and design are subject to change without notice. Installation and wiring instructions shipped with the product
shall always be used for actual installation. For more information, contact Gamewell.
The Gamewell Company
Voice (508) 231-1400
60 Pleasant St.
Ashland, MA 01721
888-FIREBOX • (888) 347-3269
FAX (508) 231-0900
www.gamewell.com
Gamewell 2001
CS-2081 Rev. 1201-3
Page 4