GAMEWELL-FCI ILI-S-E3

ILI-MB-E3
Series
Description
Intelligent Loop
Interface-Main Board
ILI-MB-E3
The Intelligent Loop Interface-Main Board (ILI-MB-E3) is
the main interface for the E3 Series® product line. With its
state-of-the-art 32 bit RISC processor, this compact “panel
on a board” provides a powerful addition to GamewellFCI’s single pair conductor solutions. This intuitive design
provides two (2), signaling line circuits, two (2), notification
application circuits, local energy city box output, auxiliary
relay functions, and auxiliary power output. These features,
combined with built-in network and serial protocols, allow
this module to support a host of new and existing products,
resulting in a building block approach to fire alarm panel
design.
ILI-MB-E3
Features
ILI-MB-E3 and ILI-S-E3:
• Listed under UL Standard 864, 9th Edition
The ILI-MB-E3 is network ready and occupies one of 64
nodes, operating at 625K baud. When this sub-assembly is
integrated with proven Broadband components, the result
is a flexible yet powerful integrated audio solution. When
transmitting to remote locations, the optional RPT-E3 provides the ILI-MB-E3 with valuable signal boosting and transient protection, as well as connectivity using both wire and
fiber-optic cables.
The ILI-MB-E3 provides two (2), signaling line circuits and
terminals for the connections to up to 159 detectors and
159 modules per SLC in Velociti®. In clip mode, each SLC
supports 99 detectors and 98 modules. The RS-485 interface can support up to a total of sixteen (16), ASM-16 and/
or sixteen (16), ANU-48 remote LED driver modules.
The ILI-MB-E3 relay outputs include system alarm, supervisory, and system trouble contacts. The ILI-MB-E3 provides output for a local energy city master box or remote
location which is non power-limited. All other wiring is
power-limited.
• Network ready integral 625K baud ARCNET
• 115.2K baud RS-232
• Signaling line circuits with:
- Two (2), Class A, Style 6, 7* or Class B, Style 4
circuits
- 40 Character user-defined text per device
- Capacity of 159 sensors and 159 addressable
modules per circuit
• 4100 event history log
*Style 7 wiring requires the use of System Sensor M500X
Isolator Modules.
ILI-MB-E3 Only:
• Two (2), notification appliance circuits, Class “A”, Style Z
or Class B, Style Y rated at 2.0 amps. per circuit
• RS-485 supporting sixteen (16), ASM-16 switch modules and/or ANU-48 LED driver modules
• Alarm, trouble, and supervisory dry contacts Form “C”,
rated at 2 amp. @ 30 VDC (resistive)
• Supports six (6), local/remote LCD-E3 annunciators and
five (5), LCD-7100 annunciators
An ISO 9000-2000 Company
SIGNALING
E3 Series,® NetSOLO,® and Velociti® are registered trademarks of Honeywell International
Inc.
S1869
FM
MEA
APPROVED
Approved
City of
Chicago
Approved
3025415 231-06-E 7165-0694:268
7165-0694:269
Class 1
Class 2
High Rise
City of
Denver
Approved
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9020-0605 Rev. e1 page 1 of 2
©2007 by Honeywell International Inc. All rights reserved.
Specifications
Operating Voltage:
24 VDC FWR
(from PM-9 Power Supply)
Operating Current:
0.081 amp.
Alarm Current:
0.150 amp. max.
Operating Temperature: 32° to 120° F (0° to 49° C)
Relative Humidity:
0 to 93%, non-condensing
at 90° F (32° C)
SLC 40 Ohms maximum line impedance.0.5 µf maximum line capacitance.
ILI-S-E3
ILI-S-E3
The Intelligent Loop Interface - Expansion Board (ILI-S-E3)
provides the E3 Series control panel with two (2), additional
signaling line circuits. The layout is similar to the ILI-MB-E3
except a number of components are omitted. The ILI-S-E3
occupies one node on the Broadband network. The ILI-SE3 provides two (2), signaling line circuits and terminals for
the connections to up to 159 detectors and 159 modules
per SLC in Velociti mode. In clip mode, each SLC supports
99 detectors and 98 modules.
Ordering Information
Model
Description
ILI-MB-E3 Intelligent Loop Interface-Main Board
ILI-S-E3 Intelligent Loop Interface-Expansion Board
Installation
Typically, the ILI-MB-E3 or ILI-S-E3 can be mounted in the
following E3 Series cabinets:
• Cabinet B and D, backbox
• Cabinet C, INX-E3 sub-assembly plate
• Cabinet C, INCC-E3 sub-assembly plate
For instructions on installing the ILI-MB-E3 or ILI-S-E3,
refer to the E3 Series® Expandable Emergency Evacuation
Installation/Operating Manual, Part Number: 9000-0574,
the ILI-MB-E3 Installation Instructions, Part Number: 90000579, or the ILI-S-E3 Installation Instructions, Part Number:
9000-0569.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9000-0605 Rev. e1 page 2 of 2
www.gamewell-fci.com