MALLORY 676M

OPERATING INSTRUCTIONS
FORM 1554M (REV. A) 10/02
®
HYFIRE® 7C CONTROL UNIT
PART NO. 676M
RPM Switch:
NOTE: This feature is not available on the HYFIRE® 667S. The
built-in RPM switch can either turn an electrical load off or on
at a selected RPM. See below for more detail.
NC
C
NO
RPM Limiters:
The HYFIRE® 676M Control has three built-in RPM limiters. Each
one has a range of 1000 to 12,800 RPM in 50 RPM steps. On the
main display, there is a decimal point on the mode digit. When that
decimal point is lit up, the RPM limit is increased by 50 RPM.
This is the RPM switch (mode 7) relay contact that is
normally closed. In other words, as long as you haven’t RPM1 (Mode 1)This is the RPM limit that is always active if you
reached the point where the RPM switch is active, this
haven’t selected any other RPM limit.
contact remains connected to the “common” or “C” terRPM2 (Mode 2) This is an auxiliary RPM limiter that is actiminal. You would use this connection if, for example,
vated when you apply 12 volts to the “RPM2” terminal on
you wanted to turn something OFF (such as a nitrous
the top-side connector. This could be a burnout limiter.
system) when you reached the RPM switch point. See
When selected, it overrides RPM 1 (the main engine
Example 1.
protection RPM limiter). See Example 4.
This is the common terminal for the RPM switch (mode
RPM3 (Mode 3) This is the other auxiliary RPM limiter. It also
7) relay in the main unit. It is connected to the RPM
is activated by 12 volts on the “RPM3” terminal on the
switch, where it will switch the accessory connected to
top-side connector, and overrides both RPM2 and
the “NC” terminal OFF, and the accessory connected
RPM1. Use this limit as a staging (starting line) RPM
to the “NO” terminal ON when the RPM switch value is
limiter. See Example 5.
reached. The “C” terminal can be used to switch either
to power or ground.
High Speed Timing Retards:
RET1, RET2, RET3 (Modes 4, 5, 6) These are all high-speed
This is the RPM switch (mode 7) relay contact that is
timing retard functions that are activated by 12 volts on the appronormally open. In other words, as long as you haven’t
priate top-side connector terminal. Each higher stage overrides
reached the point where the RPM switch is active, this
the lower stages, which means that you set each stage for exactly
contact isn’t connected to the “C” contact. You would
the amount of retard you want, rather than adding up each stage to
use this contact to turn something ON (such as a shift
get the actual retard. See Example 6.
light or an air shifter) at a specific RPM. See Example 2
and Example 3.
NOTE: When you apply 12 volts to RPM2, RPM3, RET1, RET2,
or RET3 the display will switch to show that function. If you
have both an auxiliary RPM limit AND a retard selected, the
display will show the retard value.
See the accompanying illustrations for some examples of how to use
the RPM limiters, the RPM switch, and the timing retard functions.
1
Push this button to change the mode.
UP
MODE
®
VALUE
1 - RPML 1
2 - RPML 2
3 - RPML 3
50 RPM
STEPS
8 - HSA SLOPE
+50
RPM
A - HSA MAX
DOWN
Push either of these buttons to change
the value of the mode.
R
B - TRIGGER
5 - RETARD 2
C - CYLINDER
6 - RETARD 3
7 - RPM SWITCH
D - DEG / PSI
E - MAP SELECT
676M
MODE
9 - HSA CUT-IN
4 - RETARD 1
P/N
FIGURE 1
NOTE: If any button is held down for more
than 1/2 second, the displayed value will
change automatically.
BTR CONTROL CENTER
Additional Functions:
The HYFIRE® 676M has two more modes that can make the ignition
installation and setup work better. One of these is the high speed
advance function. This lets you put small amounts of timing in the
engine after the torque peak to pick up a bit of horsepower. There are
three things that need to be set up for this: the cut-in RPM (Mode 9),
the maximum advance (Mode A), and the slope (Mode 8). The cutin RPM is the RPM where you want the curve to start working. The
slope is how much the timing will advance every 1000 RPM after the
cut-in RPM. The maximum advance is the highest amount of advance you want the system to reach.
Once the compensation is set, then the high speed advance settings will be accurate. The factory setting should be correct for
most types of flying magnet type crank trigger systems, and should
not normally need to be adjusted unless you are using a different
trigger type.
Number of cylinders selection
The next mode that can be set is mode “C”. This allows you to
select 4 through 12 cylinder operation. This ensures that the RPML
and the timing are proper for the engine. Mode 6F is special—this
is for odd-fire V6 engines ONLY! The cylinder firing spacing should
For example, say that your engine has the torque peak at 6500 RPM, be 45/75 (at the distributor) or 90/150 at the crank.
and you want to add some timing after this. You might want to start
adding timing after 7000 RPM, so this becomes your cut-in speed. If MAP Sensor Functions:
you then want 2 degrees additional timing at 8000 RPM, then the The 676M has two modes for use with a MAP (manifold absolute
slope would be set for 2 degrees per 1000 RPM. However, let’s say pressure) sensor. Mode “d” lets you select the number of degrees of
that you don’t want more than 2 degrees of advance, so you would set retard per pound of boost, from .1 to 4 degrees. Mode “E” lets you
the maximum advance at 2 degrees. See Example 7 for more detail. select the type of MAP device. Typical MAP sensors used in turbo/
supercharged engines are either 2 or 3 bar range, and these
The other similar mode available is trigger compensation, which is correspond to “2” and “3” in mode “E”. Selection “1” is different. This
set when the mode indicator is “b”. This lets you compensate for the is not made for a 1 bar MAP sensor. Instead, selection 1 lets you use
various delays in ignition timing caused by both electronic and me- an external 0-5 volt signal to control a 0-20 degree retard. This signal
chanical changes. To set the trigger compensation, set mode 9 to could be from an external dash-mount control, such as the Mallory
5000 RPM, and mode 8 to zero. What this does is tell the system to 29784, or from an external proportional nitrous controller.
start the high-speed advance at 5000 RPM, but with a slope of zero,
there should be no advance. Once the system is set up this way, MAP sensor and extension harness are not supplied with 676M.
watch the timing as the engine revs past 5000 RPM. If the timing Part numbers are:
does not stay at a steady value (once the 5000 RPM point is reached)
716
2 bar MAP Sensor
then adjust the compensation value until it is as flat as possible. For
717
3 bar MAP Sensor
example, if the timing retards slightly as the RPM goes up, increase
29785 Extension Harness
the compensation value. If the timing advances slightly as the RPM
NOTE: The 3 bar MAP Sensor (PN 717) and Extension Harness
goes up, decrease the compensation value.
(PN 29785) are included when a complete Mallory 667BTR
NOTE: This function is only valid for RPM above the highIgnition System is purchased.
speed advance cut-in RPM. If you have the high-speed advance cut-in set above the normal operational range of the
motor, the compensation function does nothing.
2
Example 1
Using the RPM switch (Mode 7) to turn
OFF a nitrous system at a particular RPM
(Not available when used with the
HYFIRE® 667S)
NC
C
NO
RPM2
RPM3
RET1
RET2
RET2
From Nitrous
Activation Switch
To Ground
COIL
CONTACT
COIL
CONTACT
To +12 Volts
To Nitrous System
RELAY—Use a relay if you are
switching more than 3-5 amps.
Example 2
Using the RPM switch (Mode 7) to turn
ON a shift light (Not available when used
with the HYFIRE® 667S)
Example 3
Using the RPM switch to activate a retard
stage at a particular RPM (Not available
when used with the HYFIRE® 667S)
Example 4
Burnout RPM Limiter (Mode 2).
NC
C
NO
RPM2
RPM3
RET1
RET2
RET2
NC
C
NO
RPM2
RPM3
RET1
RET2
RET2
NC
C
NO
RPM2
RPM3
RET1
RET2
RET2
To Ground
To +12 Volts
To +12 Volts
To roll control switch that supplies
+12 volts when active
3
Example 5
NC
C
NO
RPM2
RPM3
RET1
RET2
RET2
Staging RPM Limiter
Example 6
Using the high-speed timing retard function
with a 3-stage nitrous system.
Example 7
To clutch pedal or transbrake switch
that supplies +12 volts when active
NC
C
NO
RPM2
RPM3
RET1
RET2
RET2
CUT-IN (Mode 9)
This is the RPM where the
timing starts to advance.
This example shows a cutin of 7.0 (7000 RPM).
To nitrous stage 1 (+12 volts when active)
To nitrous stage 2 (+12 volts when active)
To nitrous stage 3 (+12 volts when active)
SLOPE (Mode 8)
This is how much the timing
advances for every 1000 RPM.
This example shows a slope of
2.0 (2 degrees per 1000 RPM).
MAXIMUM ADVANCE (Mode A)
This example shows a maximum of 2
degrees advance.
ADVANCE
8
6
4
2
0
RPM 0
2000
4000
MALLORY IS A DIVISION OF THE MR. GASKET PERFORMANCE GROUP
550 MALLORY WAY, CARSON CITY, NEVADA 89701
(775) 882-6600
FAX (775) 887-4326
www.mrgasket.com
4
6000
8000
10k
FORM 1554M
(REV. A) 10/02
Made in U.S.A.
Printed in U.S.A.