SYSTEMSENSOR 1151

INSTALLATION AND MAINTENANCE INSTRUCTIONS
1151 Low Profile Ionization
Plug-in Smoke Detectors
Specifications
Size
Height:
Diameter:
Weight:
Operating Temperature Range:
Operating Humidity Range:
Latching Alarm:
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
1.7 inches (43 mm)
4.0 inches (102 mm)
3.6 oz (102 g)
–10°C to 60°C (14°F to 140°F)
NOTE: Do not install in locations where normal ambient temperature range extends
beyond 0°C to 49°C (32°F to 120°F)
10% to 93% Relative Humidity, Noncondensing
Reset by momentary power interruption
Before Installing
Please thoroughly read the System Sensor manual A051003, Applications Guide for System Smoke Detectors,
which provides detailed information on detector spacing,
placement, zoning, wiring, and special applications. Copies
of this manual are available from System Sensor.
Base Selection and Wiring Guide
Refer to the installation instructions for the plug-in detector
bases for wiring instructions. System Sensor has available a
variety of detector bases for this smoke detector, including
2-wire applications with and without relays and/or current
limiting resistors, 4-wire and 120 VAC applications.
NOTICE: This manual should be left with the owner/user
of this equipment.
All bases are provided with screw terminals for power,
ground, remote annunciator connections, and relay contact
connections, if applicable. The electrical ratings for each
detector-base combination are also included in the base
installation instructions.
IMPORTANT: The detector used with this base must be
tested and maintained regularly following NFPA 72 requirements. The detector used with this base should be cleaned
at least once a year.
Installation
NOTE: All wiring must conform to applicable local codes,
ordinances, and regulations.
NOTE: Verify that all detector bases are installed, that the
initiating-device circuits have been tested, and that
the wiring is correct.
General Description
Model 1151 ionization detector uses state-of-the-art sensing chambers. This detector is designed to provide open
area protection, and to be used with compatible UL-listed
control panels only. The capability of plugging this detector
into a variety of special bases makes it more versatile than
equivalent direct-wired models.
WARNING
Remove power from initiating device circuits before installing detectors.
Two LEDs on each detector light to provide a local 360° visible alarm indication. Remote LED annunciator capability
is available as an optional accessory. This detector also has
the latching alarm feature. The alarm can be reset only by
a momentary power interruption. For testing, this detector
has an internal magnetically activated reed switch.
1. Install Detectors:
a. Place the detector into the detector base.
b. Rotate the detector clockwise until the detector drops
into place.
c. Continue rotating the detector clockwise to lock it in
place.
2. Tamper-Resistance: The detector bases include a feature
that, when activated, prevents removal of the detector
without the use of a tool. See the installation instruction manual of the detector base for details in using this
feature.
Spacing
Spacing of 30 ft. on a smooth ceiling as per NFPA 72.
Where conditions or response requirements vary, other
spacing may apply.
D100-51-00
1
I56-546-08R
3. After all detectors have been installed, apply power to
the control unit.
4. Test the detector as described under TESTING.
5. Reset the detector at the system control panel.
6. Notify the proper authorities that the system is in operation.
2. Both LEDs should latch on within 30 seconds,
indicating an alarm and annunciating the panel.
B. Calibrated Sensitivity Test (MOD400R)
Use the MOD400R Test Module with a digital or analog voltmeter to test calibrated detector sensitivity as
described in the test module manual.
C. Aerosol Generator (Gemini 501)
Set the generator to represent 4%/ft. to 5%/ft. obscuration as described in the Gemini 501 manual. Use the
bowl shaped applicator to apply aerosol to the sensor. It
should alarm within 30 seconds.
CAUTION
Dust covers are an effective way to limit the entry of dust
into smoke detector sensing chambers. However, they may
not completely prevent airborne dust particles from entering the detector. Therefore, System Sensor recommends the
removal of detectors before beginning construction or other
dust producing activity. Be sure to remove dust covers from
any sensors that were left in place during construction as
part of returning the system to service.
Notify the proper authorities that the system is back on
line. Detectors that fail these tests should be cleaned as
described under MAINTENANCE and retested. If the detectors still fail these tests they should be returned for repair.
CAUTION
Maintenance
Before cleaning, notify the proper authorities that the system is undergoing maintenance and will be temporarily
out of service. Disable the system to prevent unwanted
alarms.
1. Remove the sensor to be cleaned from the system.
2. Remove the sensor cover. Use a small standard screwdriver to release each of four cover removal tabs
that hold the cover in place.
3. Vacuum the outside of the screen carefully without
removing it.
4. Remove the sensor screen. Pull the screen straight away
from the sensing chamber until it snaps out of place.
Replacement screens are available.
5. Use a vacuum cleaner or clean, compressed air to remove
dust and debris from the sensing chamber.
6. Reinstall or replace the sensing chamber screen by sliding the edge without the tabs over the sensing chamber.
Make sure that one of the Screen Contacts touches the
PC Board Contact.
Smoke detectors are not to be used with detector guards
unless the combination has been evaluated and found
suitable for that purpose.
Testing
Detectors must be tested after installation and following
periodic maintenance. However, before testing, notify the
proper authorities that the smoke detector system is undergoing maintenance and the system will be temporarily out
of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms.
In addition, check to ensure that the LEDs blink. If they do
not, power has been lost to the detector (check the wiring),
or it is defective (return for repair).
Test the sensors as follows:
A. Test Magnet (p/n M02-04-01 or M02-09-00)
1. Test the sensor by positioning the optional test magnet against the sensor plastic just to the left of LED1
(Figure 1).
Figure 1. Bottom and side views showing position of test magnet:
� � � ��� �
����
�� �
����
������
������
����
������
�������
�������
�
�� ���
��
��
�������
�������
S0170-00
����
D100-51-00
2
I56-546-08R
7. Reinstall the sensor cover. Use the test module socket
and LEDs to align the cover with the sensor. Snap the
cover into place.
8. When all sensors have been cleaned, restore power to
the system and test the sensor(s) as described in the
TESTING section of this manual.
Figure 2:
S0171-00
Special Note Regarding Smoke Detector Guards
Smoke detectors are not to be used with detector guards
unless the combination has been evaluated and found
suitable for that purpose.
D100-51-00
3
I56-546-08R
Please refer to insert for the Limitations of Fire Alarm Systems
Three-Year Limited Warranty
System Sensor warrants its enclosed smoke detector to be free from
defects in materials and workmanship under normal use and service for a
period of three years from date of manufacture. System Sensor makes no
other express warranty for this smoke detector. No agent, representative,
dealer, or employee of the Company has the authority to increase or alter
the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any
part of the smoke detector which is found to be defective in materials or
workmanship under normal use and service during the three year period
commencing with the date of manufacture. After phoning System Sensor’s
toll free number 800-SENSOR2 (736-7672) for a Return Authorization
number, send defective units postage prepaid to: System Sensor, Repair
D100-51-00
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174.
Please include a note describing the malfunction and suspected cause
of failure. The Company shall not be obligated to repair or replace units
which are found to be defective because of damage, unreasonable use,
modifications, or alterations occurring after the date of manufacture. In
no case shall the Company be liable for any consequential or incidental
damages for breach of this or any other Warranty, expressed or implied
whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of
incidental or consequential damages, so the above limitation or exclusion
may not apply to you. This Warranty gives you specific legal rights, and
you may also have other rights which vary from state to state.
4
I56-546-08R
©2004 System Sensor