SYSTEMSENSOR D4120W

Watertight
4-Wire Photoelectric
Duct Smoke Detector
The InnovairFlex™ Series are the only duct smoke
detectors flexible enough to fit configurations from
square to rectangular and everything in between.
Features
•NEMA Type 4 UL listed for non-hazardous indoor and outdoor applications
•UV Resistant, UL listed housing and cover material
•Photoelectric, integrated low-flow technology
•Air velocity rating from 100 ft/min to 4,000 ft/min (0.5 m/s to 20.32
m/sec)
•Versatile mounting options: square or rectangular configuration
•Plug-in sensor offers superb false alarm immunity and the latest
sensor technology
•Broad ranges for operating temperature (–4°F to 158°F) and
humidity (0% to 95% non-condensing)
•Patented sampling tube installs from front or back of the detector
with no tools required
•Increased wiring space with a newly added ¾-inch conduit
knockout
•One easy-access Test/Reset button and improved LED status
•Patented interconnect feature for multi-fan shutdown
•New high contrast terminal designations
•Built-in short circuit protection from operator wiring errors
•Field selectable settings for configuring the detector
•Two DPDT Form-C relay contacts
•24 VAC/DC or 120VAC
•Backward compatibility with existing Innovair products, including
remote accessories
Agency Listings
The InnovairFlex D4120W watertight 4-wire photoelectric duct
smoke detector is UL listed as a watertight enclosure providing
protection against falling dirt, rain, windblown dust, splashing
and hose directed water. D4120W duct smoke detector features
a pivoting housing that fits various applications: both square and
rectangular footprints mount to round or rectangular ductwork.
This unit senses smoke in the most challenging conditions, operating
in airflow speeds of 100 to 4,000 feet per minute, temperatures
of –4°F to 158°F, and a humidity range of 0 to 95 percent (noncondensing). A plug-in sensor head offers superior false alarm
immunity. These features, plus a NEMA 4 rating, allow operators to
mount the detector to rooftop HVAC equipment or use the detector
in other harsh environments.
The new design provides the same form, fit, and wiring terminations
as the standard InnovairFlex unit. Superior test and operational
features added to the standard model are also available in this
watertight unit. As the only watertight duct smoke detector on the
market, D4120W provides unsurpassed environmental protection
while simplifying installation, testing, and maintenance.
This InnovairFlex duct smoke detector can be customized to meet
local codes and specifications without additional wiring. The new
InnovairFlex product line is compatible with all previous Innovair
models, including remote test accessories.
WARNING: Duct smoke detectors are NOT a substitute for open
area smoke detectors; NOT a substitute for early warning detection;
NOT a replacement for a building’s regular fire detection system.
Refer to NFPA 72 and 90A for additional information.
NOTE: To maintain the watertight properties of this duct smoke detector, watertight
conduit and fittings must be used. Mount the product with the conduit holes facing
downwards, if possible
InnovairFlex Duct Smoke Detector Specifications
Architectural/Engineering Specifications
The air duct smoke detector shall be a System Sensor InnovairFlex™ D4120W Watertight NEMA4 Photoelectric Duct Smoke Detector. The detector housing
shall be UL listed per UL 268A specifically for use in air handling systems. The flexible housing of the duct smoke detector fits multiple footprints from square to
rectangular. The detector shall operate at air velocities of 100 feet per minute to 4000 feet per minute (0.5 to 20.32 meters/second). The unit shall be capable of
controlling up to 50 air handling systems when interconnected with other detectors. The detector shall be capable of providing a trouble signal in the event that
the front cover is removed. It shall be capable of local testing via magnetic switch, test button on the cover, or remote testing using the SSK451 Multi-Signaling
Accessory or the RTS451KEY Remote Test Station. Terminal connections shall be of the strip and clamp method suitable for 12–18 AWG wiring.
Physical Specifications
Size: (Rectangular Dimensions)
14.38 in (37 cm) Length; 5 in (12.7 cm) Width; 2.5 in (6.36 cm) Depth
(Square Dimensions)
7.75 in (19.7 cm) Length; 9 in (22.9 cm) Width; 2.5 in (6.35 cm) Depth
Weight:
2.5 lbs (1.14 kg)
Operating Temperature Range:
–4° to 158°F (–20° to 70°C)
Storage Temperature Range:
–22°F to 158°F (–30°C to 70°C)
Operating Humidity Range:
0% to 95% relative humidity non-condensing
Air Duct Velocity:
100 to 4000 ft/min (0.5 m/sec to 20.3 m/sec)
NEMA Enclosure Rating:
Type 4 – Watertight Indoor/Outdoor
Electrical Ratings
Power supply voltage:
20–29 VDC
24 VAC 50–60 Hz
120 VAC 50–60 Hz
Input capacitance:
Reset voltage:
Reset time: (with RTS451)
Reset time: (by power down)
Power up time:
Alarm response time:
Sensitivity Test:
270 μF max
3.0 VDC min
.03 to 0.3 sec
0.6 sec max
35 sec max
15 sec
See detector label
Current Requirements: (Using No Accessories)
Max. standby current:
21 mA @ 24 VDC
Max. alarm current:
65 mA @ 24 VDC
270 μF max
2.0 VAC min
.03 to 0.3 sec
0.6 sec max
35 sec max
15 sec
See detector label
N/A
10 VAC min
.03 to 0.3 sec
0.6 sec max
35 sec max
15 sec
See detector label
65 mA RMS @ 24 VAC 60 Hz
135 mA RMS @ 24 VAC 60 Hz
20 mA RMS @ 120 VAC 60 Hz
35 mA RMS @ 120 VAC 60 Hz
Contact Ratings
Alarm initiation contacts: (SPST)
2.0A @ 30 VDC (resistive)
10A @ 30 VDC; 10A @ 250 VAC; ½ HP @ 240VAC; ¼ HP @ 120VAC
Note: A
larm auxiliary contacts shall not be connected to initiating circuits of control panels. Use the alarm initiation contact for this purpose.
Supervisory contacts: (SPDT)
2.0A @ 30 VDC (resistive); 2.0A @ 125 VAC (resistive)
Alarm auxiliary contacts: (DPDT)
Accessory Current Loads at 24 VDC
Device
Standby
Trouble
Alarm
APA451
MHR/MHW
RA400Z
RTS451
RTS451KEY
12.5 mA
0 mA
0 mA
0 mA
12 mA
N/A
N/A
N/A
N/A
N/A
30 mA Max
29 mA Max
12 mA Max
12 mA Max
12 mA Max
SSK451
8 mA Max
16 mA Max
40 mA Max
Note: Any combination of accessories may be used such that the given accessory loads are: 110mA or less at the Aux output, and 50mA or
less at the Alarm output.
A05-0420-000
Installing the InnovairFlex Sampling Tube
The InnovairFlex sampling tube may be installed from the front or back of the detector. The tube locks securely into place and can be removed by releasing
the front or rear locking tab (front locking tab shown below right).
Wiring for Watertight 4-wire Duct Smoke Detector
POWER INPUTS (NOTE 1)
24VAC/DC
9
POWER INPUTS (NOTE 1)
120
VAC
120
VAC
24V
9
10
10
OR
OR
AUXILIARY CONTACTS
FOR FAN SHUTDOWN, ETC. (NOTE 2)
N.C.
16
AUX A
C.
6
N.O.
AUXILIARY CONTACTS
FOR FAN SHUTDOWN, ETC. (NOTE 2)
AUX A
N.C.
AUX B
C.
N.O.
N.C.
8
18
7
16
17
SUPERVISORY CONTACTS
(NOTE 3)
UL/FM LISTED
4-WIRE
CONTROL PANEL
C.
6
N.O.
17
N.C.
AUX B
C.
N.O.
8
18
7
SUPERVISORY CONTACTS
(NOTE 3)
SUP C.
SUP N.O.
SUP C.
SUP N.O.
3
14
3
14
EOL RESISTOR
SPECIFIED BY
PANEL
MANUFACTURER
+
ALARM
INITIATION
LOOP
ALARM
INITIATION
CONTACTS
(NOTE 4)
4
ALARM C.
5
ALARM N.O.
ALARM
INITIATION
CONTACTS
(NOTE 4)
FIRST DETECTOR IN THE LOOP
NOTE 1: 24V Power Inputs accept a non-polarized 24VDC or 24VAC 50-60Hz.
120VAC Power Inputs accept only 120VAC 50-60Hz. Connect power
source to appropriate terminals of each detector. See specifications
for additional power supply information.
NOTE 2: Auxiliary contacts shown in standby position. Contacts switch
during alarm as indicated by arrows. Auxiliary contacts are not to
be used for connection to the control panel. See specifications for
contact ratings.
4
ALARM C.
5
ALARM N.O.
LAST DETECTOR IN THE LOOP
NOTE 3: Supervisory contacts shown in standby position. Open contacts
indicate a trouble condition to the panel. See specifications for
contact ratings.
NOTE 4: Alarm Initiation contacts shown in standby position. Closed
contacts indicate an alarm condition to the panel. See specifications
for contact ratings.
*Please refer to the corresponding installation manual for accessory wiring diagrams.
Important Interconnect Notes
• When using the interconnect feature, all interconnected units must be powered using the same independent supply.
• Polarity must be maintained throughout the interconnect wiring. Connect the INT+ terminal on unit 1 to the INT+ terminal on unit 2 and so on. Similarly,
connect the INT/AUX– terminal on unit 1 to the INT/AUX- terminal on unit 2 and so on.
• Up to 50 D4120W units may be interconnected.
• Up to 10 DH100ACDC units may be interconnected. Please note that each of the 9 DH100ACDC units interconnected may be replaced by three D4120W
units. Therefore, when using the interconnect feature a single DH100ACDC can drive either 9 DH100ACDCs or 27 D4120W units.
* NOTE: Alarm can be reset only at the initiating device and not at the devices interconnected.
A05-0420-000
Accessories
System Sensor provides system flexibility with a variety of accessories, including two remote test stations and several different means of
visible and audible system annunciation. As with our duct smoke detectors, all duct smoke detector accessories are UL listed.
RTS451 UL S2522
RTS451KEY UL S2522
RA400Z UL S2522
APA151 UL S4011
MHW UL S4011
MHR UL S4011
SSK451 UL S2522
SSK451 with PS24LOW strobe
and PS12/24 LENSW lens
Ordering Information
Part No.
D4120W
Accessories
2D51
DST1
DST1.5
DST3
DST5
DST10
APA151
DH400 OE-1
ETX
M02-04-00
Description
Watertight 4-wire photoelectric low-flow duct smoke detector
4-wire conventional photoelectric sensor head
Metal sampling tube duct width up to 1ft (0.3m)
Metal sampling tube duct widths 1 ft to 2 ft (0.3 to 0.6 m)
Metal sampling tube duct widths 2 ft to 4 ft (0.6 to 1.2 m)
Metal sampling tube duct widths 4 ft to 8 ft (1.2 to 2.4 m)
Metal sampling tube duct widths 8 ft to 12 ft (2.4 to 3.7 m)
Remote annunciator with piezo alarm
Weatherproof enclosure
Metal exhaust tube duct width 1ft (0.3m)
Test magnet
MHR
MHW
P48-21-00
PS12/24SLENSC
PS12/24SLENSW
PS24LO
PS24LOW
RA400Z
RTS451
RTS451KEY
SSK451
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
Mini Horn, Red
Mini Horn, White
End cap for metal sampling tubes
Ceiling-mount “SMOKE” lens
Wall-mount “SMOKE” lens
Mini-Alert add-on strobe (red)
Mini-Alert add-on strobe (white)
Remote annunciator alarm LED
Remote test station
Remote test station with key lock
Multi-signaling accessory
©2008 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com for
current product information, including the latest version of this data sheet.
A05-0420-000 • 8/08 • #1837