EPCOS A61

Surge Arrester
2-Electrode-Arrester
A61-A350XF
Ordering code: T. B. D.
Preliminary data
DC spark-over voltage 1) 2)
350
± 20
V
%
< 750
< 680
V
V
< 900
< 750
V
V
Nominal impulse discharge current (wave 8/20 µs)
Single impulse discharge current
(wave 8/20 µs) 3)
10
20
kA
kA
Nominal alternating discharge current (50 Hz, 1 s)
Alternating discharge current (50 Hz, 9 cycles)
10
> 40
A
A
Service life
1000 operations
100
A
Insulation resistance at 100 Vdc
> 10
GΩ
Capacitance at 1 MHz
< 1.5
pF
Arc voltage at 1 A
Glow to arc transition current
Glow voltage
< 20
< 0.5
~ 60
V
A
V
Weight
~ 1.5
g
Storage temperature
-40 ... +90
°C
Climatic category (IEC 60068-1)
40/ 90/ 21
Impulse spark-over voltage
at 100 V/µs - for 99 % of measured values
- typical values of distribution
at 1 kV/µs
- for 99 % of measured values
- typical values of distribution
10/1000 µs
350 YY O
Marking, red
350
YY
O
- Nominal voltage
- Year of production
- Non radioactive
1)
At delivery AQL 0.65 level II, DIN ISO 2859
In ionized mode
3)
8
After load: Insulation resistance >10 Ω,
Impulse spark-over voltage < 1000 V
Terms in accordance with ITU-T Rec. K.12 and DIN 57845/VDE0845
2)
AB E / AB PM
Issue 03, 04.04.2002
Page 1 of 2
Surge Arrester
2-Electrode-Arrester
A61-A350XF
Ordering code: T. B. D.
Preliminary data
Not to scale
Dimensions in mm
Non controlled document
 EPCOS AG 2002. Reproduction, publication and dissemination of this data sheet, enclosures hereto and the information
contained therein without EPCOS' prior express consent is prohibited.
Purchase orders are subject to the General Conditions for the Supply of Products and Services of the Electrical and
Electronics Industry recommended by the ZVEI (German Electrical and Electronic Manufacturers' Association), unless
otherwise agreed.
AB E / AB PM
Issue 03, 04.04.2002
Page 2 of 2