LEM LF505-S

IPN
Current Transducer LF 505-S
=
500 A
For the electronic measurement of currents : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
16137
Electrical data
I PN
IP
RM
Primary nominal rms current
Primary current, measuring range
Measuring resistance
with ± 15 V
with ± 18 V
with ± 24 V
ISN
KN
VC
IC
500
0 .. ± 800
RM min
RM max
@ ± 500 A max
@ ± 800 A max
@ ± 500 A max
@ ± 800 A max
@ ± 500 A max
@ ± 800 A max
0
0
0
0
5
5
Secondary nominal rms current
Conversion ratio
Supply voltage (± 5 %)
Current consumption
60
11
92
30
149
65
A
A
Ω
Ω
Ω
Ω
Ω
Ω
100
mA
1 : 5000
± 15 .. 24
V
24 (@ ± 18 V) + IS mA
Accuracy - Dynamic performance data
XG
ε
Overall accuracy @ IPN , T A = 25°C
Linearity error
L
± 0.6
< 0.1
Typ
%
%
Max
± 0.4
± 0.4
IO
IOT
Offset current @ IP = 0, T A = 25°C
Thermal drift of IO
- 40°C .. + 70°C
± 0.1
tr
di/dt
f
Response time 1) @ 90 % of IPN
di/dt accurately followed
Frequency bandwidth (- 1 dB)
<1
> 100
DC .. 100
mA
mA
µs
A/µs
kHz
General data
TA
TS
RS
m
Note :
Ambient operating temperature
Ambient storage temperature
Secondary coil resistance @
Mass
Standards
1)
T A = 70°C
- 40 .. + 70
°C
- 40 .. + 85
°C
70
Ω
230
g
EN 50155 : 1995
EN 50178 : 1997
Features
• Closed loop (compensated) current
transducer using the Hall effect
• Insulated plastic case recognized
according to UL 94-V0.
Advantages
•
•
•
•
•
•
•
Excellent accuracy
Very good linearity
Low temperature drift
Optimized response time
Wide frequency bandwidth
No insertion losses
High immunity to external
interference
• Current overload capability.
Applications
• AC variable speed drives and servo
motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies
(SMPS)
• Power supplies for welding
applications.
•
•
•
•
Applications domain
• Traction
• Industrial.
With a di/dt of 100 A/µs.
page 1/3
060922/9
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Current Transducer LF 505-S
Isolation characteristics
Vd
Vw
R.m.s. voltage for AC isolation test, 50 Hz, 1 mn
Impulse withstand voltage 1.2/50 µs
3.8
12.5
kV
kV
dCp
dCl
CTI
Creepage distance
Clearance distance
Comparative Tracking Index (Group IIIa)
Min
15.2
14.5
175
mm
mm
Application examples
According to EN 50178 and CEI 61010-1 standards and following conditions :
• Over voltage category OV 3
• Pollution degree PD2
• Non-uniform field
EN 50178
CEI 61010-1
Rated isolation voltage
Nominal voltage
Single isolation
1250 V
1250 V rms
Reinforced isolation
690 V
690 V rms
dCp, dCI, VW
Safety
This transducer must be used in electric/electronic equipment with respect to
applicable standards and safety requirements in accordance with the following
manufacturer's operating instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a built-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
page 2/3
060922/9
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Dimensions LF 505-S
(in mm. 1 mm = 0.0394 inch)
Bottom view
Right view
Back view
Top view
Connection
Mechanical characteristics
• General tolerance
• Transducer fastening
Vertical or flat lying position
Recommended fastening torque
or vertical position
Recommended fastening torque
or flat lying position
Recommended fastening torque
• Primary through-hole
• Connection of secondary
060922/9
± 0.5 mm
4 or 6 holes ∅ 4.3 mm
4 or 6 steel screws M4
3.2 Nm or 2.37 Lb.-Ft.
4 holes ∅ 1.9 mm,
depth : 7.5 mm
4 screws PTKA 25,
length: 6 mm
0.7 Nm or 0.52 Lb.-Ft.
4 holes ∅ 1.9 mm, crossing
4 screws PTKA 25,
length:10 mm
0.75 Nm or 0.55 Lb.-Ft.
∅ 30.2 mm
MOLEX 5045-03/A
Remarks
• IS is positive when IP flows in the direction of the arrow.
• Temperature of the primary conductor should not exceed
100°C.
• Dynamic performances (di/dt and response time) are best
with a single bar completely filling the primary hole.
• This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...), please
contact us.