BEL 07CM-38S10L_10

ISOLATED DC/DC CONVERTERS
48 VDC Input 9.3VDC/36.5 A Output, 1/4 Brick
07CM-38S10L
RoHS 5 Compliant
•
Industry standard quarter-brick package
•
Up to 300 W at 95% efficiency
•
1500 V isolation
•
Safety Agency Approvals
Rev.C
Description
The 07CM-38S “Cimarron” Series are isolated DC/DC converters that
operate from a nominal 48 VDC source. These converters use a full bridge power train to provide isolation and
step down. These units will provide up to 300 W of output power from a nominal 54 VDC input. These units are
designed to be highly efficient and low cost. Features include remote on/off, over current protection and under
voltage lockout. These converters are provided in an industry standard quarter -brick package.
Part Selection
Output
Voltage
9.3 Vdc
Input Voltage
Max. Output
Current
36.5 A
48 Vdc
Max. Output
Power
300 W
Typical
Efficiency
95%
Model Number
07CM-38S10L
Notes: 1. Add “G” suffix at the end of the model number to indicate Tray Packaging.
2. All part numbers above indicate RoHS 5. Change the second letter "7" to "R" for RoHS 6 part numbers.
Input Specifications
Parameter
Input Voltage Range
Input Current (no load)
Min
36 V
Typ
-
Max
55 V
-
-
110 mA
Input Current (full load)
-
-
7.2 A
Reflected Ripple Current (rms)
Under-voltage Lockout
Turn-on
Turn off
Over-voltage Lockout
-
-
200 mA
-
35.8 V
33.8 V
57.1 V
-
Min
Typ
Max
0A
7.0 V
9.3 V
10.6 V
-
36.5 A
Notes
See figure 1 for measurement technique
Output Specifications
Parameter
Output Voltage
36Vin
48Vin
55Vin
Output Current
Output Power
-
-
300 W
Load Regulation
-
-
0.6 V
Ripple and Noise (pk-pk)
-
-
150 mV
100 uF
(50mohm)
-
3000 uF
-
150 mV
50 uS
250 mV
100 uS
Load Capacitance
Transient Response
Max deviation
Recovery to within ± 1%
Notes
Setpoint at no load.
0 to 20 MHz Bandwidth, use 1.0 uF ceramic
cap and 100 uF/50mOhm tantalum on
output
di/dt =0 .1 A/uS, Vin =48 V
Ta = 25 °C, 25% load change.
Bel Fuse Inc. 206 Van Vorst Street, Jersey City, NJ 07302 • Tel 201-432-0463 • Fax 201-432-9542 • www.belfuse.com
ISOLATED DC/DC CONVERTERS
48 VDC Input 9.3VDC/36.5 A Output, 1/4 Brick
General Specifications
Min
Parameter
Typ
Max
Switching Frequency
-
96 kHz
-
Weight
-
56 g (2.0oz)
-
Operating Temperature
-40 °C
-
85 °C
Non-Operating Temperature
-55 °C
-
125 °C
-
120 °C
-
Overtemp Shutdown
Dimensions
Inches (L × W × H)
Millimeters (L × W × H)
Protection Features
Short circuit
Over current
Undervoltage
Overvoltage
Remote On/Off
Active Low
(Optional Active High)
Turn on delay
Outupt voltage rise time
Safety Agency Approvals
(pending)
Notes
fixed
10 °C hysteresis measured on Q4
2.28 x 1.45 x 1.00
57.9 x 36.8 x 25.4
Latching
110% to 125% max Io
UVLO Vin < 35.0
OVSD Vin>57.0
0V
1.0 V
-
2.7 ms
4.3 ms
0.4 V
18 V
-
UL / cUL Recognized Certified to EN60950
Derating @ 54VDC Input
Derating @ 38VDC Input
35
40
30
35
200LFM
25
100LFM
30
Natural
convection
25
Output Current
Output Current
200LFM
100LFM
Natural
convection
20
15
10
20
5
0
15
0
5 10 15 20 25 30 35 40 45 50 55 60 65 70
Ambient Temperature C
0
5 10 15 20 25 30 35 40 45 50 55 60 65 70
Ambient Temperature C
Figure 1: Measurement circuit for reflected ripple current.
Bel Fuse Inc. 206 Van Vorst Street, Jersey City, NJ 07302 • Tel 201-432-0463 • Fax 201-432-9542 • www.belfuse.com
ISOLATED DC/DC CONVERTERS
48 VDC Input 9.3VDC/36.5 A Output, 1/4 Brick
Thermal Images
*>100.0˚C
Top Side of Unit
w/o Heatsink
Vin:
Iout:
Pout:
Tamb:
Airflow:
39 Vdc
33.2 A
240 W
22 C
200 LFM
Air Flow
100.0
75.0
50.0
*<40.0˚C
*>100.0˚C
Bottom Side of Unit
Vin:
Iout:
Pout:
Tamb:
Airflow:
39 Vdc
33.2 A
240 W
22 C
200 LFM
Air Flow
80.0
55.0
30.0
*<40.0˚C
Bel Fuse Inc. 206 Van Vorst Street, Jersey City, NJ 07302 • Tel 201-432-0463 • Fax 201-432-9542 • www.belfuse.com
ISOLATED DC/DC CONVERTERS
48 VDC Input 9.3VDC/36.5 A Output, 1/4 Brick
Thermal Images (continued)
*>100.0˚C
Air Flow
55.0
Top Side of Unit
w/ 0.5” heatsink
Vin:
Iout:
Pout:
Tamb:
Airflow:
39 Vdc
33.2 A
240 W
22 C
200 LFM
40.0
25.0
*<40.0˚C
Bel Fuse Inc. 206 Van Vorst Street, Jersey City, NJ 07302 • Tel 201-432-0463 • Fax 201-432-9542 • www.belfuse.com
ISOLATED DC/DC CONVERTERS
48 VDC Input 9.3VDC/36.5 A Output, 1/4 Brick
Mechanical Drawing
Pin Connections
Pin
1
2
3
4
5
Function
+ Vin
Remote On/Off
- Vin
- Vout
+ Vout
RoHS Compliance
These devices contain lead, as part of the solder and solder plating alloys, and thus
can be considered RoHS compliant if used in server or telecommunications
infrastructure equipment applications (RoHS 5).
©2010 Bel Fuse Inc. Specifications subject to change without notice. 050710
CORPORATE
FAR EAST
EUROPE
Bel Fuse Inc.
206 Van Vorst Street
Jersey City, NJ 07302
Tel 201-432-0463
Fax 201-432-9542
www.belfuse.com
Bel Fuse Ltd.
8F/ 8 Luk Hop Street
San Po Kong
Kowloon, Hong Kong
Tel 852-2328-5515
Fax 852-2352-3706
www.belfuse.com
Bel Fuse Europe Ltd.
Preston Technology Management Centre
Marsh Lane, Suite G7, Preston
Lancashire, PR1 8UD, U.K.
Tel 44-1772-556601
Fax 44-1772-888366
www.belfuse.com