GENERAL C8109

Description:
A.
Tinned Copper conductor, FEP Insulation, twisted pair, overall foil shield and FEP Jacketed Plenum Cable.
Construction:
1.0
Primaries:
1.1
1.2
Conductor:
AWG
Stranding
Nom. Dia
Insulation:
Material
Nom. thickness
Nom. OD
22 AWG
7/30 Tinned Copper;
.030"
FEP
.006”
.042"
2.0
Pair construction:
2.1
No. of Pairs
2.2
Pair Color Code:
Two insulated conductors twisted together
1
Black & Red
3.0
4.0
Overall shield:
3.1
Separator:
3.2
Shield:
3.3
Drain Wire:
Jacket
Material:
Polyester tape
Aluminum/Polyester Tape; 100% coverage; (Aluminum Side out)
22 AWG Stranded Tinned Copper
FEP
Nom. wall:
.016”
Color:
TBD
5.0
Overall Diameter of Cable Nom.
.122”
6.0
Marking:
Characteristics:
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
Conductor DC Resistance @20C Max. (Ohm):
Capacitance between conductors Nom. (pF/ft):
Capacitance Cond. To other Cond.& Shield Nom. (pF/ft):
Inductance Nom. (µH/ft):
Shield Resistance Nom.(Ohms/1000’):
Velocity of propagation Nom.:
Characteristic Impedance Nom. (Ohms):
Operating Voltage Nom.:
Continuous Operating Temp:
Min. Bend Radius (inches):
Max. Pulling Tension Lbs:
C.
Approvals:
UL –CMP ; C(UL) CMP
R
E
V
DATE
B.
Surface Print:
GENERAL CABLE (F) C8109 2C 22 AWG SHIELDED CMP (UL) C(UL) ---- ROHS
AAAAA*
* Indicates Shop Order number
16
35
65
.15
12
69
48
300 V
-40C to + 200C
1.2
27.0
CHANGE DETAIL
General Cable
20 Forge Park, Franklin, Ma 02038
Phone: 508-541-7100 Fax: 508-541-8122
Title:
C8109
Description:
1 PR 22 AWG Shielded Plenum Cable
Created By:
A 07/02/09
Initial Release -DB
Final Approval:
VM – 7/2/09
PAGE 1 of 1
General Cable reserves the right to modify this information without prior notification and does not make a warranty or representation of any kind, whether implied or expressed with respect to the information contained
herein. General Cable assumes no risks, and will not be liable for direct or indirect, special; incidental or consequential damages, any defect or personal injury resulting from the use of this document.