ETC 2208L

2208e
2208e Controller PhaseII 8/31/98 11:10 AM Page 1
2208e
OP1
OP2
”
ED
C
AN
H
“EN DEL
W MO
NE
SP2
REM
Temperature Controller or Valve
Controller
MODEL
• Employs INSTANT
ACCURACY™ technology
• Heating and Cooling with
two modular outputs
•Motorized valve
positioning
• Heater current display
• Load diagnostics
• Up to three alarm relays
• Self-tuning with
overshoot inhibition
• Optimized fan, water
and oil cooling
• Two digital inputs for
second setpoint or
auto/manual select
• Simple Ramp Dwell
setpoint programming
• Digital communications
• Plug-in from front
• IP 65 panel sealing
• Compliant with European
EMC and low voltage
safety directives
The 2208e is a 1/8 DIN controller
that may be configured either
as a precision PID temperature
controller or a velocity mode
motorized valve positioning
controller. The two control
modes are co-resident and may
be selected through factory or
field configuration. The 2208e
features modular hardware, two
control outputs, two digital
inputs, self-tuning, a simple
ramp-dwell setpoint programming
feature and optional relay alarms
and communications port. The
control outputs may be
configured for heat/alarm,
heat/cool or for valve open/close
Precise Control
Advanced PID or valve
positioning algorithms give
stable straight-line control of
the process. A power feedback
feature automatically
compensates the output to
stabilize the temperature of
electrically heated loads during
supply voltage fluctuations.
Proprietary cooling algorithms
ensure optimum control of fan,
oil and water-cooled systems.
Velocity mode valve control
algorithms allow precise valve
UL and cUL pending
control without depending
on vulnerable valve position
slidewire feedback.
Universal Input
A universal input circuit with
an advanced A-D converter
samples the input at 9Hz and
continuously corrects it for drift,
giving high stability and rapid
response to process changes.
A filtered input covers all
thermocouple types, Pt100
3-wire RTD and linear inputs.
The patented Instant Accuracy™
feature allows precise input
measurement and control to be
achieved from the moment of
start up, independent of warm-up
drift, and even during periods of
ambient temperature upset.
Easy Operation
Bright, clear front-panel LED’s
display the process variable and
a configurable lower display for
setpoint or other important
parameters. Tactile pushbuttons
ensure positive operation. All
instrument parameters are easy
to access and may be presented
to the operator or hidden from
view under password protection.
A Siebe Group Company
2208e
Temperature
Controller
2208e Controller PhaseII 8/31/98 11:10 AM Page 2
Patented PDSIO® Load
Diagnostics
PDSIO® (Pulse Density Signaling
Input/Output) is a patented innovation
in the 2208e. When used in combination
with the Eurotherm TE10S Solid State
Contactor, the same wires from the 2208e
that transmit the logic output to the SSC
can be used to read back load faults, SSC
status and load RMS on-current. SSC
failure (open or short circuit) or load
failure (fuse blown, heater open circuit,
missing line voltage) alarms can be
detected, flash on the front panel and
trip alarm relays. Amperage information
can be read, displayed, and alarmed.
PDSIO® information is also available on
serial communications. PDSIO® is not
available on the Valve Positioner.
Alarms
Up to four process alarms may be combined
to a single alarm output. Alarms may be
full scale high or low, deviation, rate of
change or PDSIO® load failure. Alarms
may be latching or non-latching and will
flash on the front panel. Blocking alarms,
which only become enabled after first
entering a safe state, are also available.
Digital Communications
EIA-485 2-wire, EIA-422 4-wire or EIA-232
serial communications is optionally available
with industry standard Modbus® or
proprietary EI-Bisynch protocol.
Load diagnostic using Pulse Density Signaling Input/Output (PDSIO®)
Supply
2408e
OP1
OP2
PDSIO® 2-wire
Connection
SP2
TE10S solid
state contactor
REM
Heater
Sensor inputs and display ranges (Temperature scales conform to the ITS90 standard)
Celsius
Standard Sensor Inputs
J thermocouple
K thermocouple
T thermocouple
L thermocouple
N thermocouple
C thermocouple - W5%Re/W26%Re (Hoskins)
R thermocouple
S thermocouple
B thermocouple
Platinell II thermocouple
RTD/PT100DIN 43760
Custom Sensor Inputs (Replaces type C thermocouple)
E thermocouple
Ni/Ni18%Mo thermocouple
Pt10%Rh/P140%Rh thermocouple
Pt20%Rh/Pt40%Rh thermocouple
W/W26%Re (Englehard) thermocouple
W/W26%Re (Hoskins) thermocouple
W5%Re/W26%Re (Englehard) thermocouple
W5%Re/W26%Re (Bucose) thermocouple
D thermocouple - W3%Re/W25%Re
Linear Inputs
Fahrenheit
Min
-210
-200
-200
-200
-250
0
-50
-50
0
0
-200
Max
1200
1372
400
900
1300
2319
1768
1768
1820
1369
850
Min
-350
-325
-325
-325
-420
32
-60
-60
32
32
-325
Max
2192
2500
750
1650
2370
4200
3200
3200
3310
2500
1560
-270
0
200
0
0
0
10
0
0
-999
1000
1100
1800
2000
2000
2010
2300
2000
2400
9999
-450
32
392
32
32
32
50
32
32
1830
2012
3272
3632
3632
3650
4172
3632
4352
2208e Controller PhaseII 8/31/98 11:10 AM Page 3
2208e TECHNICAL SPECIFICATION
Inputs
General
Thermocouple
RTD/PT100
Process
Digital
Range
Sample rate
Calibration accuracy
Resolution
Linearizaton accuracy
Input filter
Zero offset
Types
Cold junction compensation
Type
Bulb current
Lead compensation
Linear
Type
Application
± 100mV and 0 to 10Vdc (auto ranging)
9Hz (110mS)
0.25% of reading, ±1 LSD or ±1°C/F
<1µV for ± 100mV range, <0.2mV for 10Vdc range
<0.1% of reading
1.0 to 999.9secs
User adjustable over the fully display range
Refer to Sensor inputs and display ranges table
Automatic compensation typically >30 to 1 rejection of ambient temperature change
External references 32, 113 and 122°F (0, 45 and 50°C).
Incorporates INSTANT ACCURACY™ cold junction sensing technology.
3-wire, Pt100 DIN43760
0.2mA
No error for 22 ohms in all 3 leads
±100mV, 0 to 20mA or 0 to 10Vdc (configurable between limits)
Contact closure
Manual select, 2nd setpoint, keylock and setpoint rate limit enable
Mode 5 Smart Digital Input™ (SDI), only on Digital LA input
Outputs
Relay
Logic
Triac
Analog
Rating: 2-pin relay
Rating: change-over, alarm relays
Application
Rating
Application
Rating
Application
Range
Application
Min: 12V, 100mA dc Max: 2A, 264Vac resistive
Min: 6V, 1mA dc Max: 2A, 264Vac resistive
Heating, cooling or alarms
18Vdc at 24mA (non-isolated)
Heating, cooling or alarms
The logic output is field configurable as a standard logic output, PDSIO® Mode 1 or PDSIO®
Mode 2.
PDSIO® Mode 1: Logic heating with load failure alarm (also called SSRx Load Doctor™)
PDSIO® Mode 2: Logic heating with load/SSC failure alarm and load current display (also called
SSRx Enhanced Load Doctor™)
1A, 30 to 264Vac resistive
Heating or cooling
Isolated 0 to 20mA (into 600Ω max) or 0 to 10Vdc (configurable between limits)
Heating or cooling
Transmission standard
Protocols
Setpoint input
EIA-485 2-wire, EIA-422 4 wire or EIA-232 at 1200, 2400, 4800, 9600, 19,200 baud
Modbus® or EI-Bisynch
Setpoint input from master PDSIO® controller, also called Smart Setpoint Transmission™ (SST)
Modes
Application
Auto/manual
Setpoint rate limit
Cooling algorithms
One-shot tune
Automatic droop compensation
Types
Modes
PID or PI with overshoot inhibition, PD, P only or On/Off
Heating and cooling
Bumpless transfer
0.01 to 99.99 degrees or display units per minute
Linear; Water (non-linear); Fan (minimum on time), Oil, proportional only
Automatic calculation of PID and overshoot inhibition parameters
Automatic calculation of manual reset value when using PD control
Full scale high or low. Deviation high, low, band or any new alarm.
Latching or non-latching. Normal or blocking action
Up to four process alarms can be combined onto a single output
Display
Dimensions and weight
Supply
Temperature and RH
Panel sealing
Electromagnetic compatibility
Dual, 4 digit x 7 segment high intensity LED
1.89W x 3.78H x 4.06D in (48W x 96H x 103Dmm) 14.1oz (400g)
85 to 264Vac -15%, +10%. 48 to 62Hz. 10watts max
Operating: 32 to 131°F (0 to 55°C), RH: 5 to 90% non-condensing. Storage: 14 to 158°F (-10 to 70°C)
IP 65
Meets generic emissions standard EN50081-2 for industrial environments
Meets general immunity requirements of EN50082-2(95) for industrial environments
EN61010, installation category 2 (voltage transients must not exceed 2.5kV)
Electrically conductive pollution must be excluded from the cabinet in which this controller is
mounted. This product is not suitable for use above 6,562ft (2000m) or in corrosive or explosive
atmospheres without further protection.
Communications
Digital
PDSIO®
Control functions
Control
Tuning
Alarms
General
Safety standards
Atmospheres
2208e Controller PhaseII 8/31/98 11:10 AM Page 4
2208e Outline Dimensions
4.06in (103mm)
1.89in (48mm)
3.78in (96mm)
2208e
OP1
OP2
SP2
REM
Panel cut-out
3.62in x 1.77in
(92mm x 45mm)
-0.0
+0.8
-0.0
+0.8
2208e Rear Terminal Connections
+
+
DC or Logic or
-
or
Output 1
1A
1B
1C
or
1D
1
2A
2C
O
U
T
P
U
T
2D
2
Output 2
2B
Alarm 2
relay
O
U
T
U
P
U
T
L
N
Line
85 to 264Vac
Neutral
E
C HD
O
M HE
M
S HF
LA
LB
Earth
Input 1
Input 2
LC
AA
AB
3A
AC
3B
VI
3C
V+
3D
V-
Alarm 1
relay
+
RTD/ PV
PT100 -
Thermocouple
Ordering Code
Basic Product
2208e
Output 1
Function
CC
Controller
XX
Not used
Output 2
XX
L1 Logic: non-isolated R1
R1
Relay: 2-pin
T1
Triac
D3
DC: isolated
T1
Not used
Relay: 2-pin
Alarm 1
XX
Not used
RF Relay:change over
Comms*
Alarm 2
XX
Not used
RF Relay:change over
Triac
L1 Logic: non-isolated
Default
Manual
XXX
No Manual
AO
American
2-wire EIA 485
ENG
English
EO
European
2YM
FRA
French
4-wire EIA 422
GDR
German
2AM
ITA
Italian
2XX
Not used
Modbus®
Modbus®
EIA 232
2FM
The above ordering code specifies only the hardware build. The
input type and output control functions must then be configured
on-site to suit a particular application. If preconfiguration is
required, ask for details on the full ordering code.
EUROTHERM CONTROLS INC
© Copyright Eurotherm Controls Inc 1998
A member of the Eurotherm plc
Group of Companies
11485 Sunset Hills Road
Reston, Virginia 20190-5286
Phone: 703-471-4870
Fax: 703-787-3436
BBS: 703-787-3444
Fax-On-Demand Service: 703-787-3441
www.eurotherm.com
INSTANT ACCURACY™, SSRx Load Doctor™ and SSRx Enhanced Load Doctor™ are
trademarks of Eurotherm. PDSIO® is a registered trademark of Eurotherm.
Modbus®
PDSIO® Input
2M4
fitted
For more information contact your local representative:
Modbus® is a registered trademark of Modicon.
All rights strictly reserved. No part of this document may be stored in a retrieval system,
or any form or by any means without prior written permission from Eurotherm Controls
Inc. Every effort has been taken to ensure the accuracy of this specification. However, in
order to maintain our technological lead we are continuously improving our products
which could, without notice, result in amendments or omissions to this specification. We
cannot accept responsibility for damage, injury, loss or expenses resulting therefrom.