ETC UNICON-JJXX-6

Programmable Isolating
Signal Converter
UNICON
The UNICON is a universal input, isolating signal converter
■
Universal configurable input stage
■
3-port isolation to 500 or 1000Vdc
■
Very high accuracy, low cost
■
Isolated transmitter supply
■
Alarm relays, RS232/485 comms using MODBUS protocol
■
Ultra-compact, only 22mm wide
PRICE
INFORMATION
AND ORDERING
3
Year
Guarantee
Options and ordering codes
UNICON
TRIP
–
JJXX
– 6
Options
With alarm relays
Without alarm relays
Comms
RS232
TRIP
D
RS485
Description
The unit can accept a signal from any common process
sensors types and give an isolated industrial standard DC
output either voltage or current
The functionality of the unit is designed to be fully user configurable
via the serial communications by using the RS232 or the RS485
programming lead, complete with the user-friendly PC Smart
software. This software sets up the sensor type and range for the
input signal, the high level output required and any intermediate
processing. The signal processing options featured include:
Thermocouple and RTD linearisation
User-defined input linearisation
Square-Root, power 3/2, power 5/2
Rate limiting
Input filtering
Trip amplifier Functionality
The optional trip relays (UNICONTRIP model) can be configured to
operate in all the normal fail-safe modes. In addition latching and
time-delay functions are also available. A 24Vdc isolated transmitter
supply is featured which can be used to power all standard two-wire
transmitters.
The operational status of the unit is indicated by the front panel LED,
a slow flash showing normal operation, a fast flash sensor failure or
open circuit input, or hard off indicating a power supply failure. The
unit may be powered by any DC supply from 16 to 32 volts.
Inputs
The input types and ranges specified are our standard ones. Please
contact our sales department for details on any application not
specified in the ranges opposite.
DC Current and Voltage
0-20mA, 4-20mA, 0-10mA, -50 to 50mA, into 10Ω
0-1V, 0-10V, 1-5V, -100 to 100V, into 1MΩ
Thermocouples
Types E, J, K, N, R, S, T and B all fully linearised
Ranges are user configurable to any values
Auto cold junction comp. Open cct T/C can drive either upscale,
downscale or to preset value
Resistance Thermometers
2 or 3 wire Pt100 or other standard type, linearised
Ranges are user configurable to any values
Outputs
DC Current (Source or Sink) and Voltage
0-20mA, 4-20mA, 0-10mA into 1kΩ maximum
0-1V, 0-10V, 1-5V into a minimum 1kΩ
The UNICON is designed to be user configurable, however the units can be
supplied factory configured to your specification – Please contact our sales
department with the following:
Input type:
Input range:
Output type:
Output range:
Linearisation:
Other options:
Trip configuration:
Comms option:
eg mA, Volt, T/C, RTD
eg 4-20, 0-10V, 0-500˚C
eg mA, Volt
eg 4-20mA, 0-10V
eg None, √, √3/2, √5/2
Averaging, inversion etc
eg H/L, failsafe, etc
RS232 or RS485
UNICON
Specifications
Parameter
Supply voltage
Supply current
Input impedance (volt)
Input impedance (mA)
Volt drop (mA input)
Input resolution
Overall accuracy
Input accuracy
Temperature coefficient
Load resistance error
Time constant (10-90%)
Operating ambient
Relative humidity
Isolation voltage
Surge voltage
Notes
Min
16V
Typ
24V
100mA
1MΩ
10Ω
0.2V
0.001%
±0.04%
±0.005%
±0.1ppm/Ω
65ms
Max
32V
200mA
Comments
11Ω
0.22V
At 20mA input
Dependent on input type
Input to analogue output
Input to RS232 comms output
±0.06%
50ppm/˚C
±1ppm/Ω
-15˚C
0%
500V
0 < RL < 1kΩ (mA output)
T/C 250ms. See note
60˚C
90%
1kV option by special request
2.5kV for 50µS
Transient of 10kV/µS
Absolute maximum ratings indicate sustained limits beyond which damage to the device may occur.
Device is protected against reverse polarity connection.
Accuracy figures based on an ambient temperature of 20˚C.
The time constant is dependent on which processing options have been selected.
▲
104.5mm
98mm
▲▲
▲
Dimensions and connections
123
Connection details
456
1. Power input -ve
2. Power input +ve
▲
75mm
▲
789
7. Input ground
8. RTD 3rd wire or T/C input +ve
9. RTD input +ve
10. Voltage input +ve
11. mA input +ve
12. 24V trans supply
mA sink output +ve
Output grouind
Voltage O/p +ve
mA source O/p +ve
13. Relay 1 common
14. Relay 1
15. Relay 2 common
16. Relay 2
10 11 12
▲
22.5mm
▲
3.
4.
5.
6.
Typical application
Digital comms
+24Vdc
Type K
Thermocouple
Isolated 4-20mA sink
High temp alarm
Sensor fail alarm
+24Vdc
PRICE
INFORMATION
AND ORDERING
PLC