BRAIN DLA71TB23 3P

Monitoring Relays
Pump alternating
Type DLA71
Product Description
DLA71 is a level controller made to alternate 2 or 3 pumps
in a multiple pump system in a case of need(i.e.:overflow)
the second,or even the third pump can be activated together
with the first one.
In case more than one pump is required to start at the same
time,the pumps start 10s after the previous to avoid big
inrush current.
The LED indicates the state of the alarm and the output relay.
35.5mm wide housing suitable both for back and front panel
Property
• Pump alternating relay for 2 or 3 pumps
• Output: 2 x 5 A SPST relay or 3 x 5 A SPST
• For mounting on DIN-rail in accordance with
DIN/EN 50 022
• 35.5 mm DIN-rail housing
• LED indication for relay and power supply ON
• Galvanically separated power supply
• Built-in delay for the second or third pump in case of
simultaneous activation is required
• Built-in function for automatic rotation of the pumps
Type Selection
Mounting
Output
Function
Supply: 24/48 VAC
Supply: 115/230 VAC
DIN-rail
DIN-rail
2 x SPST
3 x SPST
For two pumps
For three pumps
DLA 71 D B48 2P
DLA 71 T B48 3P
DLA 71 D B23 2P
DLA 71 T B23 3P
Input Specifications
Output Specifications
Contact input
Terminals
Output
DLA71...2P (normal mode)
ON/OFF 1 pump
ON/OFF 2 pumps
C, S1
C, S2
DLA71...2P (differential mode)
first pump starts
first pump stops
second pump start
second pump stop
C, S1
C, S3
C, S2
C, S4
DLA71...2P
DLA71...3P
Rated insulation voltage
Contact ratings (AgSnO2)
Resistive loads
AC 1
DC 12
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
DLA71...3P (normal mode)
ON/OFF 1 pump
ON/OFF 2 pumps
ON/OFF 3 pumps
C, S1
C, S2
C, S3
Operating frequency
Dielectric strength
2 kVAC (rms)
Dielectric voltage
Rated impulse withstand volt. 4 kV (1.2/50 µs)
DLA71...3P (full mode)
ON 1 pump
ON 2 pumps
ON 3 pumps
OFF all pumps
C, S1
C, S2
C, S3
C, S4
Disabled
Enabled
Voltage
Current
> 10 kΩ
< 1 kΩ
< 25 V
< 2 mA
Empting mode
Filling mode
N.O. contacts
N.C. contacts
www.dold-relay.com
2 x SPST NO relay
3 x SPST NO relay
250 VAC
µ
5 A @ 250 VAC
5 A @ 24 VDC
1.5 A @ 250 VAC
1.5 A @ 24 VDC
≥ 30 x 106 operations
≥ 105 operations
(at 5 A, 250 V, cos ϕ = 1)
≤ 7200 operations/h
1
DLA71
Supply Specifications
General Specifications (cont.)
Power supply
Rated operational voltage
through terminals:
A1, A2 or A3, A2
B48:
Indication for
Power supply ON
One Pump ON
Two Pumps ON
Three Pumps ON(DLA71...3P)
B23:
Dielectric voltage
Supply to input
Supply to output
Input to output
Rated operational power
AC
Overvoltage cat. III
(IEC 60664, IEC 60038)
24/48 VAC ± 15%
45 to 65 Hz, insulated
115/230 VAC ± 15%
45 to 65 Hz, insulated
First pump activated after
power up
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Housing
Dimensions
Material
Weight
Screw terminals
Tightening torque
4 kV (1.2/50 µs)
4 kV (1.2/50 µs)
4 kV (1.2/50 µs)
3 VA
General Specifications
Reaction time
Closing input
Opening input
Minimum delay to activate
the rescue pumps
Continous working time to
activate the rotation pumps
< 100 ms
< 100 ms
Product standard
Approvals
CE Marking
10 s
6 h ± 10%
EMC
Immunity
Emissions
LED, green, steady
as above, flashing 1 Hz
as above, flashing 2 Hz
as above, flashing 3 Hz
Note: if more than one pump
is active, the indication refers
to the pump started last.
Random
(EN 60529)
IP 20
3
-20 to 60°C, R.H. < 95%
-30 to 80°C, R.H. < 95%
35.5 x 81 x 67.2 mm
PA66 or Noryl
Approx. 135 g
Max. 0.5 Nm
acc. to IEC 60947
EN 60255-6
UL, CSA
L.V. Directive 2006/95/EC
EMC Directive 2004/108/EC
According to EN 60255-26
According to EN 61000-6-2
According to EN 60255-26
According to EN 61000-6-3
Mode of Operation
DLA71 is made for pumping
systems where 2 or 3 pumps
are in parallel. It lets the
pumps work alternatively,
allowing more pumps to
work togheter in case of
need.
Example 1
(emptying a basin, 2-pump
system)
As soon as the liquid reaches switch S1 one pump
starts. As soon as S1
switches back the pump
stops. When switch S1 is
activated again the other
pump starts allowing uniform wear and tear of all the
pumps. If switch S2 is activated both pumps start (2
pumps running at the same
time). When S2 switches
back the pump running
since most time stops.
2
Example 2
(emptying a basin, 2-pump
system, differential mode)
In this case the pumps are
separately
started
and
stopped by the two pairs of
switches S1, S2 and S3, S4.
positioning
Appropriate
allows the pumps to work
together in case of need.
Note (2-pump system)
If the system is continuously
working with only one pump,
after working for 6 hours,
DLA71 stops the pump and
the second one automatically starts.
This rotation is repeated
every 6 hours of single and
continuative work of a
pump.
Example 3
(emptying a basin, 3-pump
system, normal mode)
The system works exactly as
described in example 1
except that if switch S3 is
reached three pumps work
at the same time. When they
switch back the pumps are
turned off in sequence starting from the one running
longer.
Example 4
(emptying a basin, 3-pump
system, full mode)
As soon as the liquid reaches switch S1 one pump
starts. When it drops below
switch S4 it stops. If switch
S1 is triggered again another
pump starts. If switch S2 is
activated a second pump
starts (rescue function). If
switch S3 is activated all the
pumps operate. The only
switch to stop all the pumps
active at a certain time is S4.
www.dold-relay.com
Note (3-pump system)
If the system is continuously
working with only one pump,
after working for 6 hours,
DLA71 stops the pump and
the second one automatically starts. If also the second
pump works continuously
alone for 6 hours, it is
stopped and the third pump
is then started.
If a couple of pumps is continuously working for 6
hours, the one running for
more time stops and the free
one starts.
This rotation is repeated
every 6 hours of continuative
work of a pump or a couple
of pumps.
Note (2 and 3-pump systems)
In case the task is to fill a
basin, all the switches are
reversed in the basin itself.
DLA71
Operation Diagrams
Power supply
Example 1 (empting mode)
L
A1
S4
S3
A3
m
m
18
28
S1
S2
S2
S1
C
A2
15
S3
N
S4
15 -18
S2
15 -28
S1
PUMP 2
Automatic
rotation function
PUMP 1
6h
6h
6h
6h
Working time
6h
6h
6h
6h
Working time
Example 2 (empting mode)
L
A1
S4
S3
S2
S1
C
A3
A2
m
m
18
28
Power supply
S1
S2
15
S3
N
S4
15 -18
15 -28
S2
S4
S1
PUMP 2
S3
Automatic
rotation function
PUMP 1
Example 3 (empting mode)
L
A1
S4
S3
S2
S1
C
A3
A2
N
m
m
m
18
28
38
15
Power supply
S1
S2
S3
S4
15 -18
15 -28
S3
15 -38
S2
S1
PUMP
PUMP 3
3
PUMP
PUMP 2
2
Automatic
rotation function
www.dold-relay.com
PUMP11
PUMP
6h
6h
6h
6h
Working time
3
DLA71
Operation Diagrams (cont.)
Example 4 (empting mode)
L
A1
S4
S3
A3
m
m
m
18
28
38
Power supply
S1
S2
S2
S1
C
A2
15
S3
N
S4
15 -18
15 -28
15 -38
S3
S2
PUMP
PUMP 3
3
S1
PUMP
PUMP 2
2
S4
PUMP 1
1
PUMP
Automatic
rotation function
6h
6h
6h
6h
6h
6h
Working time
Example 5 (filling mode)
Power supply
S1
L
A1
S4
S3
S2
S1
A3
m
m
18
28
S2
S3
C
A2
15
S4
15 -18
N
15 -28
S3
S1
S4
S2
Automatic
rotation function
6h
6h
Working time
Wiring Diagrams
DLA71...2P
DLA71...3P
48/230 VAC 24/115 VAC
48/230 VAC 24/115 VAC
L
A1
S4
S3
S2
S1
C
A3
A2
m
m
18
28
15
L
A1
S4
S3
S2
S1
C
A2
N
N
4
A3
www.dold-relay.com
m
m
m
18
28
38
15
Dimensions
35.5
67.2
45
2
81
18.7
www.dold-relay.com
5