LEM DK300-B420 Dc current transducer dk-b020/420 Datasheet

DC Current transducer DK-B020/420
A split core transducer for the electronic measurement DC current,
with galvanic isolation between the primary (High power) and the
secondary circuits (Electronic circuit) with current output.
Electrical data
IPN = 50 .. 400A
Features
• DC Measurement
Primary Nominal Current
Analogue Output Signal1)
IPN (A.t)
IOUT (mA)
50,75,100
0-20
DK 100 B020
• Current output
100,150,200
0-20
DK 200 B020
• Jumper selectable ranges
150,225,300
200,300,400
0-20
0-20
DK 300 B020
DK 400 B020
• Panel mounting
50,75,100
4-20
DK 100 B420
100,150,200
4-20
DK 200 B420
150,225,300
4-20
DK 300 B420
200,300,400
4-20
DK 400 B420
Vc
Types
• Split core box
Supply voltage
22-26
V AC/ DC
RL
Load resistance (max)
650
Ω
Vd
Isolation voltage
3000
V
f
Frequency
DC
Ic
Current consumption (max)
100
• Extended measuring range
Advantages
• Large aperture
• High isolation between primary and
secondary circuits
• Easy to mount
• No insertion losses
mA
Applications
Accuracy - Dynamic performance data
• Battery Banks
±1
- Monitors load current
X
Accuracy @ IPN, TA=25°C
%
εL
Linearity
± 0.75
%
tr
Response time @ 90% of IPN
< 100
mS
General data
- Monitors charging current
- Verifies operation
• Transportation
Measures traction power or auxiliary
loads
• Electric Heating Elements
TA
Ambient operating temperature (0-95% RH)
- 20 .. + 50
°C
TS
Ambient storage temperature
- 20 .. + 85
°C
Faster response than temperature
m
Mass
120
g
sensors.
Options
Bipolar output :
DK 100 B 420 B, DK 200 B 420 B, DK 300 B 420 B, DK 400 B 420 B
Options on request
• Bipolar output
• DIN mounting.
Note : 1) For 0-20 mA and 4-20 mA outputs models, no saturation outputs up to 23 mA.
040510/6
LEM Components
www .lem.com
Dimensions
DK-B020/420
(unit : mm, 1 mm = 0.0394 inch)
3.2
57.2
13
21.7
61
13
30
21.7
89.7
61
4.5
77.3
Mechanical characteristics
Standard output
output in %
• General tolerance
± 1 mm
• Primary aperture
21.7 mm sq.
• Panel mounting
2 holes ∅ 4.5 mm
Distance between holes
100
77.3 mm
- IP
Connections
+ IP
Bipolar output
output in mA
• 2 x UNC8 Cylindric Head
22-26 VAC/DC
20
12
4
- dead front captive screw terminals
- 12-22AWG solid or stranded
- IP
0
+ IP
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.