LEM LV100-250 Voltage transducer lv 100-250 Datasheet

Voltage Transducer LV 100-250
VPN = 250 V
For the electronic measurement of voltages : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high voltage)
and the secondary circuit (electronic circuit).
Electrical data
VPN
VP
IPN
RM
Primary nominal r.m.s. voltage
Primary voltage, measuring range
Primary nominal r.m.s. current
Measuring resistance
with ± 15 V
ISN
KN
VC
IC
Vd
250
V
0 .. ± 375
V
40
mA
RM min
RM max
@ ± 250 V max
@ ± 375 V max
Secondary nominal r.m.s. current
Conversion ratio
Supply voltage (± 5 %)
Current consumption
R.m.s. voltage for AC isolation test, 50 Hz, 1 mn
0
0
170
90
Ω
Ω
50
mA
250 V / 50 mA
± 15
V
10 + IS
mA
6
kV
Accuracy - Dynamic performance data
XG
ε
Overall Accuracy @ VPN , TA = 25°C
Linearity
L
± 0.7
< 0.1
Typ
IO
IOT
Offset current @ IP = 0, TA = 25°C
Thermal drift of IO
tr
Response time @ 90 % of VP max
0°C .. + 70°C
± 0.2
%
%
Max
± 0.3
± 0.3
75
Note :
Ambient operating temperature
Ambient storage temperature
Turns ratio
Total primary power loss
Primary resistance @ TA = 25°C
Secondary coil resistance @ TA = 70°C
Mass
Standards 1)
1)
•Closed loop (compensated) voltage
transducer using the Hall effect
•Insulated plastic case recognized
according to UL 94-V0
•Primary resistor R 1 incorporated into
the housing.
Advantages
•Excellent accuracy
•Very good linearity
•Low thermal drift
•High immunity to external
interference.
Applications
mA
mA
•AC variable speed drives and servo
µs
•Static converters for DC motor drives
•Uninterruptible Power Supplies
motor drives
(UPS)
General data
TA
TS
N
P
R1
RS
m
Features
•Power supplies for welding
0 .. + 70
- 25 .. + 85
2500 : 2000
10
6.25
60
850
EN 50178
°C
°C
applications.
W
kΩ
Ω
g
A list of corresponding tests is available
980709/1
LEM Components
w w w .lem.com
Dimensions LV 100-250
(in mm. 1 mm = 0.0394 inch)
Front view
Left view
Secondary terminals
Terminal + : supply voltage + 15 V
Terminal M : measure
Terminal - : supply voltage - 15 V
Terminal
: ground or earth
Connection
Top view
Mechanical characteristics
•General tolerance
•Fastening
•Connection of primary
•Connection of secondary
•Connection to the ground
•Fastening torque
Remarks
± 0.3 mm
2 holes ∅ 6.5 mm
M5 threaded studs
Faston 6.3 x 0.8 mm
M5 threaded stud
2.2 Nm or 1.62 Lb. -Ft.
•IS is positive when VP is applied on terminal +HT.
•The primary circuit of the transducer must be linked to the
connections where the voltage has to be measured.
•This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...),
please contact us.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
Similar pages