LEM LV25-600 Voltage transducer lv 25-600 Datasheet

Voltage Transducer LV 25-600
VPN =
600 V
For the electronic measurement of voltages : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high voltage)
and the secondary circuit (electronic circuit).
Electrical data
VPN
VP
IPN
RM
Primary nominal r.m.s. voltage
Primary voltage, measuring range
Primary nominal r.m.s. current
Measuring resistance
with ± 12 V
with ± 15 V
ISN
KN
VC
IC
Vd
600
V
0 .. ± 900
V
10
mA
RM min
RM max
@ ± 600 V max
@ ± 900 V max
@ ± 600 V max
@ ± 900 V max
Secondary nominal r.m.s. current
Conversion ratio
Supply voltage (± 5 %)
Current consumption
R.m.s. voltage for AC isolation test 1), 50 Hz, 1 mn
30
30
100
100
200
100
320
180
Ω
Ω
Ω
Ω
25
mA
600 V / 25 mA
± 12 .. 15
V
10 (@ ± 15 V) + IS mA
4.1
kV
Accuracy - Dynamic performance data
XG
ε
Overall Accuracy @ VPN , TA = 25°C
Linearity
L
± 0.8
< 0.2
Typ
IO
IOT
Offset current @ IP = 0, TA = 25°C
Thermal drift of IO
tr
- 25°C .. + 25°C
+ 25°C .. + 70°C
Response time @ 90 % of VP max
Max
± 0.15
± 0.10 ± 0.60
± 0.10 ± 0.60
%
%
15
mA
mA
mA
µs
Features
•Closed loop (compensated) voltage
transducer using the Hall effect
•Transducer with insulated plastic
case recognized according to
UL 94-V0
•Primary resistor R 1 and transducer
mounted on printed circuit board
128 x 60 mm.
Advantages
•Excellent accuracy
•Very good linearity
•Low thermal drift
•High immunity to external
interference.
Applications
•AC variable speed drives and servo
motor drives
•Static converters for DC motor drives
•Uninterruptible Power Supplies
(UPS)
•Power supplies for welding
General data
TA
TS
N
P
R1
RS
m
Notes :
Ambient operating temperature
Ambient storage temperature
Turns ratio
Total primary power loss
Primary resistance @ TA = 25°C
Secondary coil resistance @ TA = 70°C
Mass
Standards 2)
1)
2)
applications.
- 25 .. + 70
- 40 .. + 85
2500 : 1000
6
60
110
60
EN 50178
°C
°C
W
kΩ
Ω
g
Between primary and secondary
A list of corresponding tests is available
981125/3
LEM Components
w w w .lem.com
Dimensions LV 25-600
(in mm. 1 mm = 0.0394 inch)
Front view
Top view
Standard 00
or N° SP..
Secondary terminals
Year
Week
Connection
Terminal + : supply voltage + 12 .. 15 V
Terminal M : measure
Terminal - : supply voltage - 12 .. 15 V
Mechanical characteristics
•General tolerance
•Fastening
•Connection of primary
•Connection of secondary
Remarks
± 0.3 mm
4 holes ∅ 4.2 mm
Faston 6.3 x 0.8 mm
Faston 6.3 x 0.8 mm
•IS is positive when VP is applied on terminal +HT.
•The primary circuit of the transducer must be linked to the
connections where the voltage has to be measured.
•This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...),
please contact us.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.