Cooper JT60060 Class j (finger-safe) fuseholder Datasheet

Bussmann®
Safety J Fuseholders
Class J (Finger-Safe) Fuseholders
JT60030
JTN60030 (w/Indication)
JT60060
JTN60060 (w/Indication)
For use with Bussmann Class “J” fuses - (Bussmann LPJ, JKS)
Catalog Numbers: JT60030 and JT60060 - Non-Indicating;
JTN60030 and JTN60060 - Indicating (Neon)
Construction: Thermoplastic, UL Flammability; 94VO
Voltage Ratings: 600Vac or less,
600Vdc or less
Amperage Rating: JT(N) 60030 - 30A,
JT(N)60060 - 60A
Withstand Rating: 200,000A RMS Sym.
(Self Certified at 300,000A using Bussmann
LPJ_SP fuses)
Agency Information:
Listed to UL 512: 30 - 60A (Guide IZLT, File 14853)
CSA Certified: 30 - 60A (Class 6225-01, File 47235)
Dim. =
10-4-02
in.
(mm.)
SB02295
CE Mark: Molded into product
Indication: Min. voltage: 90Vac, 115 dc; Neon Lamp
“ON” when fuse opens, voltage source and current path
are present.
Touch Safe: IP20 per IEC 529
Terminations: Dual Port (30A) Torque 20 lb. in.,
Single Port (60A) Torque 45 lb. in., Terminal Construction,
Tin plated Copper Alloy
Wire Size: JT(N)60030 - Rated for #18-#8; 75°C, CU only,
JT(N)60060 - Rated for #14-#4; 75°C, CU only
(Note: For JT(N)60030 use both stranded or solid, in a variety of
dual wire combinations of same wire size and type.)
Packaging: 12 in a carton
JT60030
JTN60030
Form No. Safety J
Page 1 of 2
Data Sheet: 1152
Safety J Fuseholders
Bussmann®
Class J (Finger-Safe) Fuseholders
JT(N)600 Series fuseblocks can be ganged together to provide two and three pole block configurations.
JT60030 - JTN60030
BUSS
BUSS
JT60030
0 – 30A
600VAC
JT60030
0 – 30A
600VAC
DO NOT REMOVE
UNDER LOAD
DO NOT REMOVE
UNDER LOAD
USE CLASS J
FUSES
USE CLASS J
FUSES
2.42
(61.3)
JT60060 - JTN60060
BUSS
BUSS
BUSS
JT60030
0 – 30A
600VAC
JT60030
0 – 30A
600VAC
JT60030
0 – 30A
600VAC
DO NOT REMOVE
UNDER LOAD
DO NOT REMOVE
UNDER LOAD
DO NOT REMOVE
UNDER LOAD
USE CLASS J
FUSES
USE CLASS J
FUSES
USE CLASS J
FUSES
BUSS
BUSS
BUSS
BUSS
BUSS
JT60060
35 – 60A
600VAC
JT60060
35 – 60A
600VAC
JT60060
35 – 60A
600VAC
JT60060
35 – 60A
600VAC
JT60060
35 – 60A
600VAC
DO NOT REMOVE
UNDER LOAD
DO NOT REMOVE
UNDER LOAD
DO NOT REMOVE
UNDER LOAD
DO NOT REMOVE
UNDER LOAD
DO NOT REMOVE
UNDER LOAD
USE CLASS J
FUSES
3.60
(91.4)
USE CLASS J
FUSES
USE CLASS J
FUSES
USE CLASS J
FUSES
USE CLASS J
FUSES
2.96
(75.2)
4.40
(111.7)
1.31
(33.3)
1.25
(31.8)
3.10
(78.7)
.10
(2.6)
3.06
(77.7)
Dim. =
1.52
(38.1)
JT60060
JTN60060
in.
(mm.)
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this Data Sheet are by definition uncontrolled. This bulletin is intended
to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a
product has been selected, it should be tested by the user in all possible applications.
10-4-02
SB02295
Form No. Safety J
Page 2 of 2
Data Sheet: 1152