ETAL EBU-TA1-003-AC230V-C-16A Electronic circuit breaker ebu Datasheet

Electronic circuit breaker EBU
Description
The electronic circuit protector type EBU (Electronic Breaker Unit)
provides selective overcurrent protection in AC 230 V UPS systems.
It consists of an MCB approved for short circuit interruptions up to
10 kA and of an add-on electronic circuitry, taking over measuring
and evaluation tasks. The product is available with the typical MCB
ratings 4 A, 6 A, 10 A and 16 A with B and C characteristics and is
directly operated at the output of the corresponding UPS.
UPS units often do not supply sufficient power in the event of a short
circuit to trip standard MCBs. The electronic AC circuit breaker can
individually be adjusted to the UPS unit and will therefore reliably trip
in the event of a short circuit. Optimal adjustment of the load’s current
rating allows detection and disconnection of an overload in the load
circuit. This helps exclude the fatal disconnection of the entire output
voltage of the UPS unit.
The Electronic Breaker Unit EBU allows a reduction in size of one
third for UPS units because power reserves do no longer have to
be kept available for tripping. The EBU increases system availability,
reduces overall costs and simplifies electrical planning.
Typical applications
Electronic overcurrent protection by means of electronic AC circuit
breakers is ideally suited to the selective protection of uninterruptible
power supplies (UPS) in industrial plants. EBU ensures the power
safety provided by AC UPS systems.
Benefits
Enhanced system availability through effective protection
Reduction of overall costs by a 1/3 more efficient rating
l Easy planning with a variable overcurrent protection
l
l
AC 230 V ±10%
Current ratings IN
4 A, 6 A, 10 A, 16 A
Frequency
50 Hz
Rated insulation voltage
AC 250 V
Rated voltage and
current rating range of
the auxiliary contact
DC 110 V / 0.3 A – 33 W
DC 30 V / 1.1 A – 33 W
AC 120 V / 0.5 A – 60 VA
AC 240 V / 0.25 A – 60 VA
Min. load of aux. contact 3 mA at 24 V
(valid for standard
industrial surroundings,
no aggressive gases)
Reference ambient
-35 °C...+60 °C
temperature
Method of operation
S-type
4
mechatronic / trip free
(positively trip-free)
Max.* cable length (outgoing wire) from generator to EBU
Type No.
EBU Electronic circuit breaker for AC UPS applications
Mounting method
T rail mounting
Design
A adjustability IN UPS + IN load
Number of poles
1 1-pole, 1-pole protected electronically
2 2-pole, 1-pole protected electronically
Version
0with physical isolation by means of MCB 4230-T
Signal input
0 without signal input
Signal output
3 auxiliary change-over contact
Operating voltage
AC 230 V
voltage rating AC 230 V
Characteristic curve
Bthermal 1.05 - 1.30 IN;
magnetic 3.2 - 4.8 IN
Cthermal 1.05 - 1.30 IN;
magnetic 6.4 – 9.6 IN
Current rating range
4 A (only Characteristic curve C)
6A
10 A
16 A
1638
Rated voltage UN
Mode of trip / degree
of trip-free behaviour
Order numbering code
EBU10 - T A 1 - 0 0 3 - AC 230 V - C - 10 A
Preferred types Characteristic curve C
Technical data
B6
B10
B16
C4
C6
C10
C16
31 m/
mm2
19 m/
mm2
12 m/
mm2
24 m/
mm2
17 m/
mm2
10 m/
mm2
6 m/
mm2
Typical electrical operational values
Voltage drop in V at 1 x IN
IN (A)
4
6
10
16
V
0,77
0,53
0,35
0,3
Insulation co-ordination
(except signalling)
Rated impulse voltage 4 kV;
overvoltage category III; pollution
degree 2; reinforced insulation in the
actuating area
Rated impulse voltage: 2.5 kV
Insulation co-ordination
of the signalling
Note: The Si contacts are not suitable for connection to SELV
control voltage.
Insulation resistance
> 100 MOhm (DC 500 V)
Degree of protection
II
Endurance
mechanical (contacts)
20,000 cycles
electronic
> 15 years within specification
potentiometer
min. 1000 steps
ordering example
www.e-t-a.de
1
Electronic circuit breaker EBU
Technical data
Operating behaviour
(endurance)
IEC 60947-2
Rated service short-­
circuit rupture capacity
(Ics)
to IEC 60947-2
Rated ultimate short-­
circuit rupture capacity
(Icu) IEC 60947-2
Signalling
Auxiliary contacts
LED status indication
Mounting values
Mounting method
Mounting position
Technical data
1500 cycles;
UN (AC); 1*IN; cos phi= 0.8
+ 8500 cycles mechanically
+ 12 cycles;
UN (AC); 6*IN; cos phi= 0.5
3 cycles (O-CO-CO); UN (AC); 7500 A;
cos phi = 0.5
Terminals
- s crew terminals
input side (cage clamps)
horizontal busbar connection
possible with comb busbars
- push-in terminal on output
side and on aux. contacts
Cable cross section
Line
N
Load
Si
Tightening torque
Mass
2 cycles (O-CO); UN (AC); 10,000 A;
cos phi = 0.5
1…25 mm²
1…10 mm²
0.5…4 mm²
0.5…1.5 mm²
2 Nm max.
approx. 230 g
1-pole
approx. 330 g
2-pole
Environmental tests (typical values)
Vibration (sinusoidal)
test to IEC 60068-2-6, ± 0.38 mm (10 – 57 Hz), 5 g
test Fc
(57 – 500 Hz)
10 frequency cycles per axis
Shock
30 g (11 ms)
test to IEC 60068-227, test Ea
Humidity
48 hours at 95% RH, temperature
test to IEC 60068-2-78, +40°C
test Cab
Degree of protection
operating area IP 40
terminal area IP00
Storage temperature
-40 °C ...+70 °C
1 change over contact
(terminals 11, 12, 14)
terminals 11-12 closed in
OFF or error condition
terminals 11-14 open in OFF
or error condition
normal condition:
green
after adjustment
orange blinking
IN UPS / load:
for 5 s
error condition
(electrical trip)
red
error condition (no
voltage applied):
off
symmetrical rail
any
Max. operating currents depending on ambient temperature
4
Rated
current IN (A)
Max. operating currents depending on ambient temperature T
(A)
-35°C
-30°C
-25°C
-20°C
-15°C
-10°C
-5°C
0°C
+5°C
+10°C
4
5.08
5.00
4.92
4.84
4.76
4.68
4.60
4.52
4.40
4.32
6
7.70
7.58
7.46
7.34
7.21
7.09
6.96
6.83
6.70
6.56
10
13.89
13.62
13.35
13.07
12.81
12.53
12.23
11.93
11.63
11.33
16
20.78
20.43
20.08
19.75
19.40
19.05
18.70
18.33
17.96
17.58
Rated
current IN (A)
Max. operating currents depending on ambient temperature T
(A)
+15°C
+20°C
+25°C
+30°C
+35°C
+40°C
+45°C
+50°C
+55°C
+60°C
4
4.24
4.20
4.08
4.00
3.88
3.76
3.64
3.56
3.44
3.32
6
6.42
6.27
6.14
6.00
5.84
5.68
5.52
5.36
5.19
5.01
10
11.01
10.67
10.34
10.00
9.63
9.24
8.85
8.45
8.01
7.55
16
17.20
16.80
16.40
16.00
15.55
15.11
14.66
14.20
13.71
13.21
All dimensions without tolerances are for reference only. E-T-A reserves the right change
specifications at any time in the interest of improved design, performance and cost effectiveness, the right to make changes in these specifications without notice is reserved. Product
markings may not be exactly as the ordering codes. Errors and omissions excepted.
2
www.e-t-a.de
1638
Electronic circuit breaker EBU
Dimensions
Installation drawing
mounting area
operating area
EBU10-T 1 pole
65,7
52,8
69 ± 2 (max. 72 mm)
rail EN 60715-35 x 7,5
45.3
Schematic diagram
IN UPS
Status indication
green / orange / red
Label
IN Load
EBU10-T 2 pole
electronic control unit
signalling current /
control
voltage
measurement
45 ± 0.5
95
ON / OFF Line
N
I>
I>
4
11 14 12 Load
70,4
N
N
EBU10-TA1-...
EBU10-TA2-...
65,7
Connection and operating elements
1
2
3
4
5
6
7
8
9
rail EN 60715-35 x 7,5
70 ± 2 (max. 74 mm)
45.3
Toggle MCB
Status indication MCB
Adjustment of operating range UPS
Adjustment of trip range load
LED status indication of EBU10-T
Screw terminal line
Screw terminal neutral conductor
Push-in terminal load
Push-in terminal signalling (change over contact)
7
95
5
4
Label
1638
(1)
(N)
(2.1/2.2)
(11/12/14)
6
2
45 ± 0.5
3
(IN UPS in [A])
(IN load in [A])
1
9
8
www.e-t-a.de
3
Electronic circuit breaker EBU
Time/current characteristics
Curve B
Curve C
1000
1000
100
100
trip time in seconds
10000
trip time in seconds
10000
10
10
1
1
0,1
0,1
0,01
0,8 1
2
4
6
8 10
20
0,01
0,8 1
40
... times rated current
2
4
6 8 10
20
... times rated current
40
Ambient temperature 30 °C
Ambient temperature 30 °C
4
Electronic trip curve:
Type B
thermal
magnetic
electronically variable
1.05 ... 1.30
× IN
3.2 ... 4.8
× IN
I (t > 100 s)= 1.05 x IN, load
I (t > 10 s) = 1.6 x IN, load
I (t > 1 s)
= 2.7 x IN, load
I (t < 20 ms) = 1,5 x IN, UPS
Type C
1.05 ... 1.30
× IN
6.4 ... 9.6
× IN
I (t > 300 s)= 1.05 x IN, load
I (t > 30 s) = 1.3 x IN, load
I (t > 3 s)
= 2.3 x IN, load
I (t > 0.3 s) = 5.2 x IN, load
I (t < 20 ms) = 1,5 x IN, UPS
Tolerance of electronic trip curve (at 23°C)
Type B
Type C
4
t > 100 s
t < 20 ms
1,05…1,17 IN Load
1,33…1,5 IN,UPS
t > 300 s
t < 20 ms
1,05…1,17 IN Load
1,31…1,5 IN,UPS
www.e-t-a.de
1638
Electronic circuit breaker EBU
Adjustment of electronic time-current characteristics (example)
Step 1:
selection of EBU
Selection of trip characteristic and current rating:
uninterruptible
power supply / UPS
current rating = 12 A
Characteristic curve C ⇒ inrush current SMPS
Current rating:
⇒ 10 A cable protection
for cable cross
section 1.5mm²
EBU10-TA1-003-AC230V-C-10A
UPS
current rating =12 A
Load SMPS DC 24 V: IN = 3 A
Step 2:
adjustment of EBU to
UPS rating
Step 3:
adjustment of EBU
to load
EBU ⇒ IN UPS:
adjustment to 12 A
⇒ rated current UPS = 12 A
EBU ⇒ IN UPS:
adjustment to 3 A
⇒ rated current load = 3 A
4
Setting options:
IN, UPS:
IN, load:
single phase rated current of the UPS unit at cont. load
rated current of the connected load
Recommendation:
IN, UPS:
IN, load:
smaller or equal to the determined value
higher or equal to the determined value
Setting parameters:
B6
B10
IN, UPS
IN, load
B16
IN, UPS
IN, load
C4
IN, UPS
IN, load
C6
IN, UPS
IN, load
C10
IN, UPS
IN, load
C16
IN, UPS
IN, load
IN, UPS
IN, load
7
OFF
11
OFF
17
OFF
4.3
OFF
7
OFF
11
OFF
17
OFF
7.5
2
12
3
19
4
5.5
1.3
8
2
12
3
21
4
8
2.5
13
3.5
21
5
6.5
1.6
9
2.5
14
3.5
25
5
8.5
3
14
4
23
6
7
2.0
11
3
16
4
28
6
9
3.5
15
5
25
7
8.5
2.3
12
3.5
21
5
34
7
9.5
4
16
6
28
8
10
2.6
14
4
25
6
38
8
10
4.5
17
7
29
10
11
3.0
16
4.5
28
7
43
10
11
5
19
8
31
12
13
3.3
18
5
34
8
57
12
12
5.5
21
9
34
14
14.5
3.6
21
5.5
38
9
64
14
13
6
22
10
35
16
17
4.0
25
6
43
10
68
16
In the OFF condition the electronic trip curve only takes effect in the short circuit range
1638
www.e-t-a.de
5
Electronic circuit breaker EBU
Accessories
Busbar
EBU10-Tx1 16mm² 80 A / 250 V AC (1-pole devices)
Screw
Screw terminal
terminal
6 –– 50
50 mm²
mm² connection
connection from
from the
the side,
side, 32
32 x
x4
4 mm
mm
6
Y 312 284 01
Y
Y 312
312 288
288 01
01
N
L
N
L
N
L
16
L
48,75
48,75
32,25
32,25
1020
N
4
4
35,2
27,1
27,1
4
7,5
52,8
20
20
15,9
33,3
Screw
Screw terminal
terminal
6
6 –– 50
50 mm²
mm² connection
connection from
from above,
above, 32
32 x
x4
4 mm
mm
Y 312
312 289
289 01
01
Y
Busbar
EBU10-Tx2 16 mm² 80 A / 250 V AC (2-pole devices)
16,5
16,5
Y 312 285 01
N
N
L
L
N
N
L
35,2
52,8
70,4
4
N
Mounting examples
16
L
27,1
27,1
52,5
52,5
1020
N
44
20
20
4
7,5
Mounting examples
examples (1-pole;
(1-pole; end
end caps
caps not
not shown)
shown)
Mounting
15,9
33,3
End cap for busbars, 2-/3-pole
Y 308 506 01
Label, packing unit 50 pcs
X 222 977 50
Mounting
Mounting examples
examples (2-pole;
(2-pole; end
end caps
caps not
not shown)
shown)
6
www.e-t-a.de
1638