PHOENIX EMD-SL-PS-120AC Star/delta timer relay Datasheet

ETD-SL-1T-S
Star/delta timer relay
INTERFACE
Data sheet
102573_en_06
1
© PHOENIX CONTACT - 09/2009
Description
Increasingly higher demands are being placed on safety and
system availability – across all sectors. Processes are
becoming more and more complex, not only in mechanical
engineering and the chemical industry, but also in plant and
automation technology. Demands on power engineering are
also increasing constantly.
The timer relays in the ETD series can be used to control time
sequences in production and process technology.
Features
–
–
–
–
–
–
One adjustable time
Time range of 500 ms to 3 minutes (four setting ranges)
Additional changeover time
Star/delta startup
Power supply via power module can be selected
Two floating PDTs
WARNING: Risk of electric shock
Never carry out work when voltage is present.
Make sure you always use the the latest documentation.
It can be downloaded at www.phoenixcontact.net/download.
ETD-SL-1T-S
2
Ordering data
Description
Type
Order No.
Pcs. / Pkt.
Star/delta timer relay
ETD-SL-1T-S
2867924
1
Accessories
Type
Order No.
Pcs. / Pkt.
Power modules, pluggable, for EMD-SL-..., supply voltage:
20 V DC ... 30 V DC
EMD-SL-PS- 24DC
2885359
1
Power modules, pluggable, for EMD-SL-..., supply voltage:
20.2...26.4 V AC
EMD-SL-PS- 24AC
2866103
1
Power modules, pluggable, for EMD-SL-..., supply voltage:
88...121 V AC
EMD-SL-PS-110AC
2866116
1
Power modules, pluggable, for EMD-SL-..., supply voltage:
108 V AC ... 132 V AC
EMD-SL-PS-120AC
2885731
1
Power modules, pluggable, for EMD-SL-..., supply voltage:
195...264 V AC
EMD-SL-PS-230AC
2866129
1
3
Technical data
Input data
Input voltage range
24 V DC (see Power modules)
24 V AC ... 230 V AC (see Power modules)
Nominal frequency
50 Hz ... 60 Hz
Temperature coefficient, typical
≤ 0.01 %/K
Recovery time
500 ms
Time setting range
500 ms ... 3 min (4 time end ranges)
Changeover time
40 ms / 60 ms / 80 ms / 100 ms
Function
S: Star/delta startup
Basic accuracy
± 1 % (of scale end value)
Setting accuracy
≤ 5 % (of scale end value)
Repeat accuracy
≤ 0.5 % ±5 ms
Nominal power consumption
2.5 VA (1 W)
Output data
Contact type
2 floating PDT contacts
Nominal insulation voltage
250 V AC (in acc. with IEC 60664-1)
Interrupting rating (ohmic load) max.
750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing)
1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing)
Output fuse
5 A (fast-blow)
General data
Service life mechanical
Approx. 2 x 107 cycles
Service life, electrical
Approx. 2 x 105 cycles at ohmic load, 1000 VA
Switching frequency
max. 60 (per minute at 100 VA ohmic load)
max. 6 (per minute at 1000 VA ohmic load)
Operating mode
100% operating factor
Degree of protection
IP40 (housing) / IP20 (connection terminal blocks)
Pollution degree
2 (according to EN 50178)
Surge voltage category
III, basic insulation (as per EN 50178)
Rated insulation voltage
300 V (According to EN 50178)
Inflammability class acc. to UL 94
V0
102573_en_06
PHOENIX CONTACT
2
ETD-SL-1T-S
General data (Continued)
Assembly
on TS 35 profile rail acc. to EN 60715
Mounting position
Any
Width
22.5 mm
Height
113 mm
Length
90 mm
Type of housing
Polyamide PA, self-extinguishing
Color
green
Weight
160 g
Connection data
Conductor cross section, solid
0.5 mm² ... 2.5 mm²
Conductor cross section, stranded
0.5 mm² ... 2.5 mm²
Stripping length
8 mm
Type of connection
Screw connection
Tightening torque
1 Nm
Ambient conditions
Ambient temperature (operation)
-25 °C ... 55 °C
-25 °C ... 40 °C (corresponds to UL 508)
Ambient temperature (storage/transport)
-25 °C ... 70 °C
Permissible humidity (operation)
15 % ... 85 %
Climatic class
3K3 (in acc. with EN 60721)
Conformance / approvals
Conformity
CE compliant
UL, USA / Canada
UL/C-UL listed UL 508
Conformance with EMC directive 2004/108/EC
Immunity to interference according to
EN 61000-6-2
Emitted interference according to
EN 61000-6-4
Conformance with LV directive 2006/95/EC
Industrial timer relays according to
4
EN 61812-1/A11
Block diagram
16
18
26
28
t
15
A1
A2
102573_en_06
POWER
MODULE
25
U = 24 V DC
24...230 V AC
PHOENIX CONTACT
3
ETD-SL-1T-S
5
Safety notes
WARNING: Risk of electric shock
Never carry out work when voltage is present.
6
Structure
1
2
3
4
5
6
7
1
C
0A
-2312 9
-PS 6
SL 8 6
D- o.:2
EM .-N
Ord
~
0V
23 2VVA
Hz 64
/60 0 2
505 23
19
A1
.4
.6
.8
T IM
30
s
10
E
1
7
Y
80
s
Timer
U/tY
15
.2
.0,5
"U/tY" LED: Supply voltage and adjustable time tY
"REL" LED: Output relay
Rotary switch "TIME Y>Δ": Changeover time
Rotary switch "TIME Y": Time end range
"TIME Y" potentiometer: Preset value
Universal snap-on foot for EN DIN rails
Power module
s
10
60
40
10
ETD-SL-1T-S
Y> ms
A
REL
TIM
E
2
25
16
6
80
26
18
28
A2
3
7
4
5
Power supply
The power module for power supply is supplied in a transport casing to prevent the connection legs from being bent.
To install the power module in the relay housing, remove the transport casing and position the power module in the recess
in the side of the housing (ensure that it is the right way round). The red locking latches snap in with an audible click when
the power module is securely positioned.
To remove the power module, press the two red locking latches together and pull out the power module.
8
Installation
WARNING: Risk of electric shock
Never carry out work when voltage is present.
The module can be snapped onto all 35 mm DIN rails according to EN 60715.
102573_en_06
PHOENIX CONTACT
4
ETD-SL-1T-S
9
Time setting
Example:
A1
.4
2
.6
.8
.2
1
.0,5
Timer
U/tY
1
15
TIM E Y
1
80s
30s
3
Set time: 0.5 * 1 minute = 0.5 minutes = 30 seconds
Setting of the turnaround time, e.g. 80 ms
10
10s
3
2
Specification of the time end range using a rotary switch,
e.g. 1 m (1 minute)
Fine setting of the time using a potentiometer, e.g. 0.5
60
80
10ms
40
REL
ETD-SL-1T-S
TIME Y>A
10
25
26
28
16
18
A2
Diagnostics
The LEDs indicate the following error states:
"U/tY" LED (Green)
–
–
LED flashes: Voltage present, set star time t1 running
LED ON: Voltage present, set star time t1 has elapsed
"REL" LED (Yellow)
–
–
LED ON: Output relay has picked up
LED OFF: Output relay has dropped out
102573_en_06
PHOENIX CONTACT
5
ETD-SL-1T-S
11
Connection example
A1
12
15
15
25
16 18
26 28
25
26
28
16
18
A2
Function
ATTENTION: Module can become damaged
Only set the functions when the module is switched off.
S: Star/Delta Startup
U
LED U/tY
LED REL, R 15-16-18
R 25-26-28
t1
102573_en_06
t2
t1
t2
When supply voltage U is applied, the output relay for the star
contactor picks up (yellow "REL" LED is ON) and set star time
t1 starts running (green "U/tY" LED flashes). Once the star
time has elapsed (green "U/tY" LED is ON) the output relay for
the star contactor drops out (yellow "REL" LED is OFF) and
set changeover time t2 starts running.
Once the changeover time has elapsed, the output relay for
the delta contactor picks up. In order to restart the function,
the supply voltage must be interrupted and applied again.
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49-(0) 5235-3-00
PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300
www.phoenixcontact.com
6