Cooper JKS-125 Jks â 600vac, 70-600a, fast-acting fus Datasheet

Limitron™ Class J
JKS — 600Vac, 70-600A, Fast-Acting Fuses
Dimensions - in
4.63"
3.63"
2.63"
0.38"
0.75"
1" 0.28"
7.13"
5.25"
3.38"
1.13"
1.63"
0.13"
0.53"
225 to 400A
65 to 100A
5.75"
4.38"
3.0"
0.41"
8.0"
6.0"
3.75"
1.13"
0.28"
0.38"
1.38"
Description: Advanced protection Class J current-limiting,
fast-acting fuses.
Catalog Symbol: JKS-(amp)
Ratings:
Volts — 600Vac
Amps — 70-600
IR — 200kA Vac RMS Sym.
2"
0.19"
Features:
• Provides 10X better current limitation to help prevent
equipment damage caused by short-circuit events.
• 200kA Interrupting rating complies with NEC® Section 110.9
for today's large capacity systems.
• Fast-acting fuse helps prevent equipment damage caused
by short-circuit events.
• Ideal for critical industrial or commercial applications that
have specific current limitation requirements.
Recommended Fuse Blocks
CE, UL Listed Class J (Guide # JDDZ, File # E4273)
Fuse Amps
70-100
110-200
225-400
450-600
Catalog Numbers (amps)
JKS-70
JKS-80
JKS-90
JKS-100
JKS-110
JKS-125
JKS-150
JKS-175
JKS-200
JKS-225
JKS-250
JKS-300
JKS-350
JKS-400
JKS-450
Carton Quantity:
Amp Rating
70–100
110–600
Carton Qty.
5
1
JKS-500
JKS-600
0.38"
2.13"
0.69"
1-Pole
JM60100-1CR
JM60200-1CR
JM60400-1CR
JM60600-1CR
2-Pole
JM60100-2CR
JM60200-2CR
JM60400-2CR
JM60600-2CR
3-Pole
JM60100-3CR
JM60200-3CR
JM60400-3CR
JM60600-3CR
For additional information on the JM Series of fuse blocks, see
product brochure # 3192.
Fuse Reducers For Class J Fuses
Equipment
Fuse Clips
100A
200A
400A
600A
Desired Fuse
(Case) Size
30A
60A
60A
100A
100A
200A
200A
400A
Catalog Numbers
(Pairs)
J-13
J-16
J-26†
J-21†
J-41†
J-42†
J-62†
J-64†
† Not for bolt-in applications.
0615
BU-SB13736
2.5"
450 to 600A
Agnecy Information:
CSA HRCI-J (Class 1422-02, File # 53787)
0.25"
0.53"
1.5"
110 to 200A
*2"
1.88"
Page 1 of 3
Data Sheet # 1027
Limitron™ Class J
JKS — 600Vac, 70-600A, Fast-Acting Fuses
600A
400A
200A
300
100A
Time-Current Curves - Average Melt
AMP RATING
100
TIME IN SECONDS
10
1
CURRENT IN AMPS
0615
BU-SB13736
Page 2 of 3
10,000
1000
40
0.01
100
0.1
Data Sheet # 1027
Limitron™ Class J
JKS — 600Vac, 70-600A, Fast-Acting Fuses
Current-Limitation Curves
B
AMP RATING
300,000
200,000
100,000
80,000
60,000
50,000
40,000
600
400
30,000
200
20,000
100
10,000
8000
6000
5000
4000
3000
A
200,000
80,000
100,000
30,000
40,000
50,000
60,000
20,000
8000
10,000
4000
5000
6000
3000
1000
2000
2000
1000
INSTANTANEOUS PEAK-LET-THROUGH CURRENT IN AMPS
400,000
RMS SYMMETRICAL CURRENT IN AMPS
A-B = ASYMMETRICAL AVAILABLE PEAK (2.3 X SYM RMS AMPS)
Current-Limiting Effects
Prosp.
Let-Through Current
S.C.C.
(Apparent RMS Symmetrical Vs. Fuse Rating)
—
100A
200A
400A
600A
5000
2000
3000
4000
5000
10,000
3000
4000
6000
9000
15,000
3000
4000
7000
10,000
20,000
3000
5000
8000
11,000
25,000
3000
6000
9000
12,000
30,000
3000
6000
9000
13,000
35,000
4000
6000
9000
13,000
40,000
4000
7000
10,000
14,000
50,000
4000
7000
10,000
15,000
60,000
5000
7000
11,000
16,000
70,000
5000
8000
11,000
17,000
80,000
5000
8000
12,000
17,000
90,000
6000
9000
13,000
18,000
100,000
6000
9000
13,000
18,000
150,000
6000
9000
14,000
22,000
200,000
7000
10,000
16,000
24,000
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended
to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction
of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product
has been selected, it should be tested by the user in all possible applications.
0615
BU-SB13736
Page 3 of 3
Data Sheet # 1027
Similar pages