ETC FS7-4 Flow switches - liquid Datasheet

FLOW SWITCHES
Flow Switches – Liquid (continued)
Series FS7-4
®
Industrial Liquid Flow Switches
• Universal design serves the widest variety of large pipe
applications, including heating and hydronic systems,
air conditioning, refrigeration and process work
F
A
B
• 11⁄4" (32mm) NPT
G
C
HJ
DIA. HOLE
FOR ELEC.
CONNECTION
• Brass with sealed tube construction
N
K
D
• Single pole, double throw snap switch
HEX.
E
PADDLE FOR
1-1/4" & 1-1/2"
(32 & 40mm) TEES
• Magnetic switching mechanism eliminates need for
bellows
• Sensitivity adjusting screw makes flow adjustment easy
Series FS7-4
• Paddles can be trimmed to suit application needs
PADDLE
FOR 2" TO 5"
(50-125mm) PIPE
Packed loose
in carton.
M
L
2
3
4
5
6
FLOW SWITCHES
• Optional features
– Extended paddle arm
– Two SPDT switches to make or break two separate
circuits
– Stainless steel
– BSPT threads
– Sprinkler service (UL & ULC listed)
• Minimum temperature (fluid or ambient) 32°F (0°C)
• Maximum temperature 300°F (149°C)
• Maximum operating pressure
300 psi (7 kg/cm2)
1000 psi (70 kg/cm2) – Stainless Steel models
Series FS7-4L
Electrical Ratings
Motor Switch Rating (Amperes)
Full Load
Locked Rotor
Voltage
120 VAC
7.4
44.4
240 VAC
3.7
22.2
Pilot Duty
125 VA at
120 or 240 VAC
50 or 60 cycles
Dimensions, in. (mm)
A
B
7
2 ⁄8 (73)
C
7
1 ⁄16 (37)
H
41⁄8 (105)
116
D
7
E
3
⁄8 (22)
9
1 ⁄4 (45)
13 ⁄16 (345)
F
13
5 ⁄16 (148)
G
3
3 ⁄8 (86)
K
L
M
NPT
N
⁄16 (24)
37⁄16 (87)
25⁄8 (67)
11⁄4 (32)
91⁄2 (241)
15
J
FLOW SWITCHES
Flow Rates
Model
Ordering Information
Size NPT
in. (mm)
1
1
⁄4 (32)
11⁄2 (40)
2
(50)
21⁄2 (60)
3
(80)
FS7-4
5 (125)
6 (150)
8 (200)*
10 (250)*
12 (300)*
14 (355)*
16 (405)*
20 (500)*
24 (600)*
FS7-4L
30 (760)*
36 (910)*
Factory or
Minimum
Maximum
Factory or
Minimum
Maximum
Factory or
Minimum
Maximum
Factory or
Minimum
Maximum
Factory or
Minimum
Maximum
Factory or
Minimum
Maximum
Factory or
Minimum
Maximum
Factory or
Minimum
Maximum
Factory or
Minimum
Maximum
Factory or
Minimum
Maximum
Factory or
Minimum
Maximum
Factory or
Minimum
Maximum
Factory or
Minimum
Maximum
Factory or
Minimum
Maximum
Factory or
Minimum
Maximum
Factory or
Minimum
Maximum
Factory or
Minimum
Maximum
4.8
7.7
(18.2)
(29.1)
3
5.9
(11.4)
(22.3)
6.3
10
(23.8)
(37.9)
3.6
7
(13.6)
(26.5)
9.9
15.8
(37.5)
(59.8)
5.9
11
(22.3)
(41.6)
15.3
23.7
(57.9)
(89.7)
9.5
17
(36)
(64.3)
24.4 (92.4)
35.5 (134.4)
15.4 (58.3)
29.2 (110.5)
33.3 (126)
61.4 (232.4)
21.1 (79.9)
37.7 (142.7)
44.4 (168.1)
84 (317.9)
31 (117.3)
51
(193)
56.3 (213.1)
114.8 (434.5)
48.7 (184.3)
71 (270.6)
104 (393.6)
210 (794.9)
89 (336.9)
131 (495.8)
184 (696.4)
369 (1397)
157 (594.2)
231 (874.3)
289
582
(1094)
(2203)
247 (934.9)
363 (1374)
387
753
(1465)
(2850)
323 (1223)
495 (1874)
513
998
(1942)
(3777)
428 (1620)
656 (2483)
520
780
(1968)
(2952)
260 (984)
693 (2623)
752 (2846)
1128 (4269)
376 (1423)
1002 (3793)
1177 (4455)
1766 (6684)
589 (2229)
1570(59842)
1723 (6522)
2584 (9870)
861 (3259)
2297 (8694)
Model
Part
Number Number Description
Weight
lbs. (kg)
FS7-4
FS7-4D
FS7-4DF
FS7-4DS
FS7-4F
FS7-4F CAN
FS7-4J
FS7-4L
FS7-4LJ
FS7-4S
FS7-4SJ
FS7-DSJ
5.5
5.7
5.7
5.7
5.5
5.5
5.5
5.5
5.5
5.0
5.0
5.0
119700
119750
119825
119760
119800
119801
120060
119900
119980
120160
120171
120174
Industrial flow switch
FS7-4 w/2 SPDT switches
FS7-4D for sprinkler service (UL listed)
FS7-4D w/Stainless steel
FS7-4 for sprinkler service (UL listed)
FS7-4F ULC listed
FS7-4 w/ BSPT threads
FS7-4 w/extended paddle arm
FS7-4L w/BSPT threads
FS7-4 w/Stainless steel
FS7-4S w/BSPT threads
FS7-4S w/2 SPDT switches & BSPT threads
(2.5)
(2.6)
(2.6)
(2.6)
(2.5)
(2.5)
(2.5)
(2.5)
(2.5)
(2.3)
(2.3)
(2.3)
NOTE: DO NOT USE LIQUID FLOW SWITCHES
ON SYSTEMS WITH FLOW GREATER
THAN 10 FEET (3M) PER SECOND.
FLOW SWITCHES
4 (100)
Settings
Mode of Operation
Flow
No Flow
gpm (lpm) gpm (lpm)
Values are ± 10%
* Equipped with a 6" (152mm) paddle
117