LEM HTR50-SB Current transducer Datasheet

Current Transducer HTR 50 to 500-SB
For the electronic measurement of currents: DC, AC, pulsed...,
with galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
IPN = 50 .. 500 A
Electrical data
Type
Primary nominal
current rms
IPN (A)
HTR 50-SB
50
HTR 100-SB
100
HTR 200-SB
200
HTR 300-SB
300
HTR 400-SB
400
HTR 500-SB
500
VOUT
Output voltage (Analog)
RL
Load resistance
VC
Supply voltage (± 5 %)
IC
Current consumption (max)
Primary current,
measuring range
IPM (A)
± 100
± 200
± 400
± 600
± 800
± 1000
± 4
V
> 10
kW
± 12 .. 15
V
20
mA
Accuracy - Dynamic performance data
X
ε
L
VOE
VOM
VOT
TCεG
tr
di/dt
BW
Accuracy 1) @ IPN , TA = 25°C, @ ± 12 .. 15 V (± 5 %)
Linearity error 1)
Electrical offset voltage @ IP = 0, TA = 25°C
Magnetic offset voltage @ IP = 0 and specified RM,
after an overload of 3 x IPN
Temperature variation of VO
- 10°C .. + 70°C
Thermal drift of the gain, TA = - 10 .. + 70°C
Response time to 90 % of IPN step
di/dt accurately followed
Frequency bandwidth (- 1 dB)
Note:
Advantages
●● Low power consumption
●● Split core easy for mounting
●● High isolation between the
primary and the secondary circuit
●● Through-hole, no insertion losses.
≤ ± 2
≤ ± 1
Typ
Max
± 45 ± 65
%
%
mV
± 10 ± 20
± 70 ± 240
± 140 ± 450
< 10
> 50
DC .. 10
mV
mV
mV
µs
A/µs
kHz
●● Power supplies for TELECOM
(monitoring & measuring)
●● Uninterruptible Power Supplies
(UPS)
●● Switched Mode Power Supplies
(SMPS)
●● Electrical chemistry
●● Chooper
●● Battery supplied applications.
Application domain
●● Industrial.
Ambient operating temperature
Ambient storage temperature
Mass
Standard
1)
●● Open loop Hall effect transducer
●● Busbar mounting or panel
mounting.
●● Isolated plastic case recognized
according to UL 94-V0.
Applications
General data
TA
TS
m
Features
- 10 .. + 70
- 20 .. + 85
80
EN 50178
°C
°C
g
Execludes the electrical offset.
Page 1/3
090804/6
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Current Transducer HTR 50 to 500-SB
Isolation characteristics
Vd
Vw
Ve
dCp
dCI
CTI
Rms voltage for AC isolation test, 50 Hz, 1 min
Impulse withstand voltage 1.2/50 µs
Partial discharge extinction voltage rms
Creepage distance 1)
Clearance distance 2)
Comparative Tracking Index (group IIIa)
3
> 6
> 1.5
Min
28.1
17.1
225
kV
kV
kV
mm
mm
Applications examples
According to EN 50178 and IEC 61010-1 standards and following conditions:
●● Over voltage category OV 3
●● Pollution degree PD2
●● Non-uniform field
EN 50178
IEC 61010-1
Rated isolation voltage
Nominal voltage
Single isolation
1000 V
1000 V
Reinforced isolation
500 V
500 V
dCp, dCI, Vw
Notes: 1) On housing from pin to primary hole
2)
On housing from pin to primary hole.
Safety
This transducer must be used in electric/electronic equipment with respect
to applicable standards and safety requirements in accordance with the
manufacturer’s operating instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a build-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
Page 2/3
090804/6
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Dimensions HTR 50 to 500-SB (in mm. 1 mm = 0.0394 inch)
Dimensions HTR 50 to 500-SB
( in mm, 1 mm = 0.0394 inch )
Bottom view
Bottom view
Secondary terminals
Terminal 1
Supply voltage + 12 .. 15 V
Secondary: connections:
Terminal 2
: Supply voltage - 12 .. 15 V
1: Supply voltage
+12 .. 15 V
Terminal 3
: Output
2: Supply voltage
-12 .. 15 V
Terminal
4
: 0V
3: Output
4: 0V
Front view
Front view
Mechanical characteristics
Mechanical
●● General
tolerancecharacteristics: ± 1 mm
●● Primary through hole
• General tolerance
± 1 mm
●● Fastening
•
Primary
aperture
Distance between holes axes∅ 21 mm
• Fastening
2 holes ∅
or
Ø 21 mm
2 holes Ø 3.2
50 x 36 mm
3.2
1 hole Ø 3.2 and
Distance between holes axes: 50 x 36 mm
1 spigot Ø 2.5
or
1 x hole ∅ 3.2 and 1 spigot ∅ 2.5
Distance between hole and sigot axes 36 mm
Distance between hole and sigot axes : 36 mm
●● Connection
of secondary
Molex 5046-04/AG
• Secondary
connection: Molex 5046-04/AG
“Malting connector provided with the transducer“
Remarks
Remarks:
●● VOUT is positive when IP flows in the direction of the arrow.
●● The return busbar and primary conductor elbow must be
• Vout
is positive
Ip xflows
in the
direction
of far
theaway
arrow.
located
at leastwhen
at 2.5
window
length
more
• The
temperature
of
the
primary
busbar
can
not
exceed
90° C
from the transducer case.
•●●The
return
busbar
and
primary
conductor
elbow
must
be
Temperature of the primary busbar cannot exceed 90°C.
located at least at 2,5 x window length more far away from the
●● Dynamic performances are best with a primary busbar
transducer case.
completely filling the primary aperture.
• Dynamic performances are the best with a primary busbar
●● This is a standard model. For different versions (supply
completely filling the primary aperture.
voltages,
different output, unidirectional measurements
• This
is a standard model. For different versions (supply
...),
please
contact
us. unidirectional measurements...),
voltages, different
outputs,
please contact us.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
Page 3/3
090804/6
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Similar pages