LEM HAIS100-TP Current transducer Datasheet

Current Transducer HAIS 50..400-P
and HAIS 50..100-TP
IPN = 50 .. 400 A
For the electronic measurement of currents: DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
All data are given with a RL = 10 kW
Electrical data
Primary nominal
current rms
IPN (A)
50
100
150
200
400
VOUT
GTH
VREF
RL
ROUT
CL
VC
IC
Primary current
Type
measuring range
IPM (A)
± 150
HAIS 50-P, HAIS 50-TP 1)
± 300
HAIS 100-P, HAIS 100-TP 1)
± 450
HAIS 150-P
± 600
HAIS 200-P
± 600
HAIS 400-P
Output voltage (Analog) @ IP
Theoretical sensitivity
Reference voltage 2) - Output voltage
VREF Output impedance
typ.
VREF Load impedance
Load resistance
Output internal resistance
Capacitive loading (± 20 %) Supply voltage (± 5 %)3)
Current consumption @ VC = 5 V
RoHS since
date code
45231, 46272
45231, 46012
46172
45231
47096
VOE ± (0.625· IP/IPN) V
0.625
V/IPN
2.5 ± 0.025
V
200
W
≥ 200
kW
≥ 2
kW
< 5 W
=4.7
nF
5
V
19
mA
Accuracy - Dynamic performance data
X
Accuracy 4) @ IPN , TA = 25°C
Linearity
error 0 .. IPM
L
TCVOE Temperature coefficient of VOE TCVREF Temperature coefficient of VREF, +25°C...+85°C
-40°C...+25°C
TCVOE/VREFTemperature coefficient of VOE / VREF
TCG Temperature coefficient of G
VOE
Electrical offset voltage @ IP = 0, TA = 25°C
VOM
Magnetic offset voltage @ IP = 0,
after an overload of IPM
HAIS 50-(T)P
HAIS 100-(T)P..400-P
tra
Reaction time @ 10 % of IPN
tr
Response time to 90 % of IPN step
di/dt di/dt accurately followed
Vno
Output voltage noise
(DC ..10 kHz)
(DC .. 1 MHz)
BW
Frequency bandwidth (- 3 dB) 5)
ε
Notes:
≤ ± 1
% of IPN
≤ ± 0.5
% of IPN
≤ ± 0.3
mV/K
≤ ± 0.01
%/K
%/K
≤ ± 0.015
≤ ± 0.2
mV/K
≤ ± 0.05% of reading/K
VREF ± 0.025
V
< ± 0.5
< ± 0.4
< 3
< 5
> 100
< 15
< 40
DC .. 50
% of IPN
% of IPN
µs
µs
A/µs
mVpp
mVpp
kHz
Features
●● Hall effect measuring principle
●● Galvanic isolation between
primary and secondary circuit
●● Isolation test voltage 2500V
●● Low power consumption
●● Single power supply +5V
●● Fixed offset & gain
●● Bus bar version available for 50A
and 100A ratings.
●● Isolated plastic case recognized
according to UL94-V0.
Advantages
●● Small size and space saving
●● Only one design for wide current
ratings range
●● High immunity to external
interference.
●● VREF. IN/OUT
Applications
●● AC variable speed drives
●● Static converters for DC motor
drives
●● Battery supplied applications
●● Uninterruptible Power Supplies
(UPS)
●● Switched Mode Power Supplies
(SMPS)
●● Power supplies for welding
applications.
Application domain
●● Industrial
-TP version is equipped with a primary bus bar.
1)
2)
It is possible to overdrive VREF with an external reference voltage
3)
Maximum supply voltage (not operating) < 6.5 V
4)
Excluding Offset and Magnetic offset voltage.
5)
Small signal only to avoid excessive heatings of the magnetic core.
between 1.5 - 2.8 V providing its ability to sink or source approximately 5 mA.
100507/11
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/3
www.lem.com
Current Transducer HAIS 50..400-P and HAIS 50..100-TP
General data
TA
TS
m
Ambient operating temperature
Ambient storage temperature
Mass (in brackets : TP version)
Standards - 40 .. + 85
°C
- 40 .. + 85
°C
20 (30)
g
EN 50178: 1997
Isolation characteristics
Vb
Rated isolation voltage rms with EN50178, IEC61010-1 standards
at following conditions
- Over voltage category III
- Pollution degree 2
- Heterogeneous field
Vd
Ve
Rms voltage for AC isolation test, 50 Hz, 1 min
2.5
Partial discharge extinction voltage rms @ 10pC
HAIS 50..400-P
> 1
HAIS 50..100-TP > 1.4
Impulse withstand voltage 1.2/50 µs
8
Creepage distance
> 8
Clearance distance
> 8
Comparative tracking index (Group I)
> 600
If insulated cable is used for the primary circuit, the
voltage category could be improved with the following table :
Cable insulation (primary)
Category
HAR 03
450V CAT III
HAR 05
550V CAT III
HAR 07
650V CAT III
Vw
dCp
dCl
CTI
kV
kV
kV
kV
mm
mm
Safety
This transducer must be used in electric/electronic equipment with respect
to applicable standards and safety requirements in accordance with the
manufacturer’s operating instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a built-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
Page 2/3
100507/11
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Dimensions HAIS
mm)1 mm = 0.0394 inch)
HAIS 50..400-P
50..400-P and
and HAIS
HAIS 50..100-TP (in
(in mm.
HAIS 50..100-TP
HAIS 50..400-P
Front view
Front view
33
15
Right view
3.5
3
3
1.5
2-D1.0
4-0.25x0.45
Bottom view
Bottom view
5
6
14.5
Terminal Pin Identification
4
4.3
11
6
1.5
11
6.5
5
4
1
1
19.9
3-P1.8
4.3
6
6.5
1.5
14
11
1.5
10
3-P1.8
14.5
2-D1.0
6
25.9
0.5
3.5
0.5
16
29
29
8
33
11
Required
Connection
Circuit circuit
Recommended
connection
1...+5V
2...0V
3...OUTPUT
4...Vref. (IN/OUT)
5...Core Earth (*)
6...NC.
1
2
3
4
47nF
4.7nF
47nF
+5V
0V
OUTPUT
Vref. (IN/OUT)
5
Recommended PCB hole
Operation Principle
Pin 1-4 : 0.7 ±0.1mm
Pin 5-6 : 1.5 ±0.1mm
Primary bus bar : 2.3 ±0.1mm
General tolerance : ±0.2mm
Unit : mm
+Vc
Vout
Vref.(IN/OUT)
Ip
0V
should be connected to 0V of Power Supply for better dv/dt immunity.
Arrow indicates positive current direction.
(*)
Page 3/3
100507/11
080821/8
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Page 3/3
www.lem.com