Cooper GMF-1 Gmf and grf non-rejection fuses and hlr holder Datasheet

BUSSMANN
Effective June 2016
Supersedes May 2002
Technical Data 2031
SERIES
GMF and GRF non-rejection fuses and HLR holders
Additional information:
GMF, GRF
•
HLR carrier comes with 6” of #18 red
insulated solid copper wire attached to the
line side
•
Customer inserts a #18 insulated solid
copper wire into load side receptacle
•
Order part number HLR-2 to obtain 6”
of #18 black insulated solid copper wire
pre-installed in a load side receptacle
•
Order part number HLR-2L to obtain 6”
of #18 black insulated solid copper wire
packaged loose (un-installed)
•
An alternative to the HLR fuseholder is
the A fuseholder. The A fuseholder comes
WITHOUT leads. The customer inserts #18
insulated solid copper wire into the line
side receptacle as well as into the load side
receptacle. It has the same body dimensions,
utilizes the same mounting hole, and takes
the same mounting clips as the HLR. The A
fuseholder is UL Recognized, 10A, 300Vac,
Guide IZLT2, File E14853 and CSA Certified,
10A, 300Vac, Class 6225-01, File 47235
•
Fuse and knob are an integral one-piece unit.
There are no replacement knobs (caps)
•
Units can be panel mounted with a separate
steel clip. For the knockout hole (see above),
choose #BK/A-104. For the keyhole punch
type hole, choose #6374 for panels 0.043” to
0.062” thick, or #4909 for panels 0.030” to
0.042” thick
•
Do not put tension on line (rear) terminal
of fuseholder
HLR
Catalog symbols:
•
GMF
•
GRF
•
HLR-2
Description:
Bussmann® series non-rejecting, time-delay,
in-line fuses and holders.
Specifications:
Ratings
• Volts - 300 Vac
• Amps
•
GMF 3/10-6 1/4 A
•
GRF 7-10 A
• Interrupting rating - 10 kA
Agency information
GMF and GRF fuse:
•
UL Listed, Std. 248-14, Guide JDYX, File
E19180
•
CSA® Certified, C22.2 No. 248.14, Class
1422-01, File 53787
•
CE
®
Dimensions - in (mm):
Fuse
0.63"
HLR fuseholder:
•
•
•
UL Recognized, 12A, 300 Vac, Guide IZLT2,
File E14853
•
•
Fuse and carrier
0.850"
(21.59mm)
CSA Certified, 12A, 300 Vac, Class 6225-01,
File 47235
CE
HLR-2:
•
(15.9mm)
UL Recognized, 15A, 300 Vac, Guide IZLT2,
File E14853
CSA Certified, 15A, 300 Vac, Class 6225-01,
File 47235
CE
2.250"
(57.15mm)
Line lead
0.850"
(21.59mm)
CL
0.720"
(18.29mm)
Load lead
Mounting hole
0.410"
(10.41mm)
0.870"
(22.10mm)
0.635"
(16.13mm)
0.740"
(18.80mm)
Knockout hole
0.255"
(6.48mm)
Keyhole punch
Technical Data 2031
GMF and GRF non-rejection fuses and HLR holders
Effective June 2016
Holder
Fuse
Holder
HLR
GMF-3
HLR
GMF-1/2
HLR
GMF-3 2/10
HLR
GMF-6/10
HLR
GMF-4
HLR
GMF-8/10
HLR
GMF-5
HLR
GMF-1
HLR
GMF-6 1/4
HLR
GMF-1 1/4
HLR
GRF-7
HLR
GMF-1 6/10
HLR
GRF-8
HLR
GMF-2
HLR
GRF-10
HLR
GMF-2 1/2
HLR
GMF-10
HLR
GMF-2 8/10
HLR
100
Amp
rating
3
3.2
4
1
1.6
2
0.5
0.3
Time-current curves–average melt
RMS symmetrical current in amps
RMS symmetrical current in amps
Eaton.com/bussmannseries
200
100
10
0.1
0.01
1
.1
200
100
0.1
Time in seconds
0.01
1
10
0.1
10
2
1
1
100
Amp
rating
10
Time in seconds
Fuse
GMF-3/10
7
8
10
Time-current curves–average melt
5
Catalog numbers
Technical Data 2031
GMF and GRF non-rejection fuses and HLR holders
Effective June 2016
The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this
document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical
information that will help the end user with design applications. Eaton reserves the right, without notice, to change design or construction
of any products and to discontinue or limit distribution of any products. Eaton also reserves the right to change or update, without notice,
any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible
applications.
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Bussmann Division
114 Old State Road
Ellisville, MO 63021
United States
Eaton.com/bussmannseries
© 2016 Eaton
All Rights Reserved
Printed in USA
Publication No. 2031 – SB02233
June 2016
For Eaton’s Bussmann series
product information,
call 1-855-287-7626 or visit:
Eaton.com/bussmannseries
Eaton and Bussmann are valuable
trademarks of Eaton in the US and other
countries. You are not permitted to use the