ETC2 EM11DINAV71X01 Energy management energy analyzer Datasheet

Energy Management
Energy Analyzer
Type EM11 DIN
• Class 1 (kWh) according to EN62053-21
• Class 2 (kvarh) according to EN62053-23
• Accuracy ±0.5 RDG (current/voltage)
• Energy analyzer
• Instantaneous variables readout: 4 DGT
• Energies: 5+1 DGT
• Instantaneous variables: V, A, W, Wdmd, Wdmd max, var,
PF, Hz
• Single phase variables: VLL, VLN, A, VA, W, var, PF
• Energy measurements: total kWh and kvarh
• TRMS measurements of distorted sine waves (voltages/currents)
• Self power supply
• Dimensions: 1-DIN module
• Protection degree (front): IP40
• 1 pulse output on request
• 1 alarm output on request
• MID “annex MI-003” (Measuring Instruments Directive)
compliant
Product Description
How to order EM11 DIN AV8 1 X O1 X
One-phase energy analyzer
with built-in configuration
push button and LCD data
displaying; particularly indicated for active and reactive
energy metering and for cost
allocation. Housing for DINrail mounting, IP40 (front)
protection degree. Direct
connection up to 32A.
Moreover the meter can be
provided with either pulse
output proportional to the
active energy being measured or alarm control on
the available instantaneous
variables.
Model
Range code
System
Power supply
Output
Option
Range code
System
Power supply
Output
AV7:
1:
X:
XX:
O1:
Type Selection
AV8:
120VLN AC - 5(32)A (**)
(direct connection)
230VLN AC - 5(32)A (*)
(direct connection)
1-phase
Option
(*) as standard.
(**) on request.
X:
None (*)
Self power supply
(from 48 to 62Hz).
The instrument
works on the range
from -20% to +20%
of the measuring
input nominal voltage.
R1:
B1:
None (**)
Pulse type (open collector output) (*)
Alarm type (relay output) (*)
Buzzer output (**)
Input specifications
Rated inputs
Current range (by shunt)
Voltage range
System: 1
AV7 and AV8: 5(32)A
AV7: 120 VLN AC
AV8: 230 VLL AC
Accuracy (Display)
(@25°C ±5°C, R.H. ≤60%, 48 to 62Hz)
AV7 model
Ib: 5A, Imax: 32A;
Un: 120VLN (-20% +20%)
AV8 model
Ib: 5A, Imax: 32A;
Un: 230VLN (-20% +20%)
From 0.04Ib to 0.2Ib:
Current
±(0.5% RDG +3DGT)
From 0.2Ib to Imax:
±(0.5% RDG +1DGT).
Voltage
In the Un range: ±(0.5%
RDG +2DGT)
Frequency
±0.1Hz (48 to 62Hz)
Specifications are subject to change without notice
Active power
Reactive power
Active energy
Reactive energy
Reference values
Start up current:
Energy additional errors
Influence quantities
Temperature drift
Sampling rate
EM11DINDS200906
±(1%RDG +2DGT)
±(2%RDG +2DGT)
Class 1 according to
EN62053-21 and MID
Annex MI-003 Class B.
Class 2 according to
EN62053-23.
Ib: 5A, Imax: 32A,
0.1 Ib: 0.5A
20mA
According to EN62053-21,
EN62053-23
≤200ppm/°C
1600 samples/s @ 50Hz
1900 samples/s @ 60Hz
1
EM11 DIN
Input specifications
Display
Type
Instantaneous variables read-out
Min. Max. indication
Energies
LEDs
Measurements
Method
Coupling type
1 line (max: 5+1 DGT)
LCD, h 7mm
4 DGT (V and A)
3 DGT (W, var, Wdmd,
Wdmd max, Hz, PF)
Max. 9 999;
Min. 0 (0.0)
Total: 5+1 DGT
Red LED (Energy consumption), 1000 pulses/kWh
(Max Frequency 16 Hz)
according to EN62053-11
See “Measuring variables
and Min. Max. indications”
TRMS measurements of
distorted wave forms
Direct
Crest factor
Current Overload
Continuous
For 10ms
Voltage Overload
Continuous
For 500ms
Input impedance
120VL-N (AV7)
230VL-N (AV8)
5(32) A (AV7-AV8)
Frequency
Key-pad
Ib 5A ≤4 (45A max. peak)
32A, @ 50Hz
960A, @ 50Hz
1.2 Un
2 Un
>720KΩ
>720KΩ
< 0.5VA
48 to 62 Hz
1 push-button for variable
selection and programming
of the instrument working
parameters
Output specifications
Digital output
Number of outputs
Type
Signal
Pulse duration
Insulation
Alarm output
Number of outputs
Type
Alarm modes
Controllod variables
Set-point adjustment
Hysteresis
2
(on request)
1
Open collector, programmable from 0.001 to 1
kWh for each pulse.
VON 1.2 VDC/ max. 100 mA
VOFF 30 VDC max.
≥100ms < 120msec (ON),
≥120ms (OFF), according
to EN62052-31
By means of optocouplers,
4000 VRMS output to
measuring inputs
(on request)
1
Reed Relay, SPST type
AC 1-5A @ 250VAC
DC 12-5A @ 24VDC
AC 15-1.5A @ 250VAC
DC 13-1.5A @ 24VDC
Up alarm or down alarm
kW, kWdmd, kvar, PF, A, V,
Hz
Programmable on all the
measuring range (see
“Measuring variables and
Min. Max. indications”)
programmable on all the
measuring range (see
On-time delay
Off-time delay
Min. response time
Insulation
Buzzer
Type
Alarm modes
Controlled variables
Set-point adjustment
Hysteresis
On-time delay
Off-time delay
Min. response time
“Measuring variables and
Min. Max. indications”)
0 to 9999s (166min)
0 to 9999s (166min)
≤ 1s, set-point on-time
delay: “0 s”
4000 VRMS output to
measuring inputs
(on request)
It sounds when the alarm is
ON
Beep type 70dB
Up alarm or down alarm
kW, kWdmd, kvar, PF, A, V,
Hz
Programmable on all the
measuring range (see
“Measuring variables and
Min. Max. indications”)
programmable on all the
measuring range (see
“Measuring variables and
Min. Max. indications”)
0 to 9999s (166min)
0 to 9999s (166min)
≤ 1s, set-point on-time
delay: “0 s”
Specifications are subject to change without notice
EM11DINDS200906
EM11 DIN
Software functions
Password
1st level
2nd level
Numeric code of max. 4
digits; 2 protection levels
of the programming data:
Password “0”, no protection;
Password from 1 to 9999,
all data are protected
Displaying
Reset
1 variable per page (See
«Measuring variables and
Min. Max. indications»)
By means of the front
key-pad:
- W dmd max;
- energies: kWh, kvarh
General specifications
Operating temperature
Storage temperature
Installation category
Insulation (for 1 minute)
Dielectric strength
CMRR Noise rejection
EMC
Electrostatic discharges
Immunity to irradiated
electromagnetic fields
Burst
Immunity to conducted
disturbances
-25°C to +55°C (13°F to
131°F) (R.H. from 0 to 90%
non-condensing @ 40°C)
according to EN62053-21
and EN62053-23
-30°C to +70°C (22°F to
140°F) (R.H. < 90% noncondensing @ 40°C)
according to EN62053-21
and EN62053-23
Cat. III (IEC60664,
EN60664)
4000 VRMS between measuring inputs and digital
output (O1 and R1).
4000 VRMS for 1 minute
100 dB, 48 to 62 Hz
According to EN62052-11
8kV air discharge;
Test with applied current:
10V/m from 80 to 2000MHz;
Test without any applied
current: 30V/m from 80 to
2000MHz;
On current and voltage
measuring input circuits:
4kV
Surge
Radio frequency suppression
Standard compliance
Safety
Metrology
Pulse output
Approvals
Connections
Cable cross-section area
DIN Housing
Dimensions (WxHxD)
Material
Mounting
Protection degree
Front
Screw terminals
Weight
On current and voltage
measuring input circuits:
4kV;
According to CISPR 22
IEC60664, IEC61010-1
EN60664, EN61010-1
EN62052-11
EN62053-21, EN62053-23.
MID ”annex MI-003”
DIN43864, IEC62053-31
CE, PTB (Revenue
Approvals)
Screw-type
Min. 2.5 mm2, Max. 10 mm2
(measuring inputs);
Other terminals: 1.5 mm2
Min./Max. screws tightening torque: 1 Nm / 4 Nm
17.5 (+0.5 -0) x 90 x 67.5 mm
Nylon PA66,
self-extinguishing: UL 94 V-0
DIN-rail
IP40
IP20
Approx. 100 g (packing
included)
10V/m from 150KHz to
80MHz
Power supply specifications
Self supplied version
120VLN, 230 VLN (-20%
+20%) 48-62Hz
Specifications are subject to change without notice
Power consumption
EM11DINDS200906
≤ 3VA
3
EM11 DIN
Accuracy
kWh, accuracy (RDG) depending on the current
kvarh, accuracy (RDG) depending on the current
Error
Error
+1.5%
+1%
+2.5%
+2%
0%
0%
-1%
-1.5%
-2%
-2.5%
PF=1
PF=L0.5
or C0.8
0.10A
(0.02Ib)
0.25A
(0.05Ib)
0.25A
(0,05Ib)
0.5A
(0,1Ib)
5A (Ib)
32A (Imax)
sinϕ=1
5A (Ib)
32A (Imax)
sinϕ=0.5
Class 1 accuracy limits (Active energy)
5(32)A Start-up current: 20m
0.1A
(0.02Ib)
0.25A
(0.05Ib)
0.25A
(0.05Ib)
0.5A
(0.1Ib)
5A (Ib)
32A (Imax)
5A (Ib)
32A (Imax)
Class 2 accuracy limits (Reactive energy)
5(32)A Start-up current: 20mA
MID “Annex MI-003” compliance
Accuracy
0.9 Un ≤ U ≤ 1.1 Un;
0.98 fn ≤ f ≤ 1.02 fn;
fn: 50 or 60Hz;
cosϕ: 0.5 inductive to 0.8
capacitive.
Class B
I st: 0.025A;
I min: 0.32A;
I tr: 0.64A;
I max: 32A.
Operating temperature
EMC compliance
-25°C to +55°C (13°F to
131°F) (R.H. from 0 to 90%
non-condensing @ 40°C)
E2
Used calculation formulas
Phase variables
Energy metering
Instantaneous effective voltage
Instantaneous active power
Instantaneous power factor
Instantaneous effective current
Instantaneous apparent power
Where:
P= active power;
Q= reactive power;
t1, t2 =starting and ending time points
of consumption recording;
nj= time unit;
∆t= time interval between two
successive power consumptions;
n1, n2 = starting and ending discrete
time points of consumption recording
Instantaneous reactive power
Where: n= sample number
4
Specifications are subject to change without notice
EM11DINDS200906
EM11 DIN
Measuring variables and Min. Max. indications
Page number
Variable
Min. Max. Indication
Notes
1
kWh
from 0.0 to 99999.9
Total (only consumed energy)
2
kvarh
from 0.0 to 99999.9
Total (only consumed energy)
3
kW
from 0.00 to 9.99
4
kW dmd
from 0.00 to 9.99
Integration time progammable from 1 to
30 minutes
5
kW dmd max
from 0.00 to 9.99
Max value with data storage (in EEprom)
6
V
from 0.0 to 999.9
7
A
from 0.0 to 32.00
8
Hz
from 48.0 to 62.0
9
PF (cosϕ)
from L/C. 00 to L/C. 99
10
kvar
from 0.00 to 9.99
Insulation between inputs and outputs
Measuring inputs
Relay output
Open collector
output
AC self-power supply
-
4kV
4kV
0kV
Relay output
4kV
-
4kV
4kV
Open collector
output
4kV
4kV
-
4kV
AC self-power supply
0kV
4kV
4kV
-
Measuring inputs
Wiring diagrams and relay output (R1)
1-phase connection
Fig. 1
1 relay output
Fig. 2
NOTE: The 3 and 4 terminals, in the instrument, are wired together
Specifications are subject to change without notice
EM11DINDS200906
5
EM11 DIN
Wiring diagrams and open collector output (O1)
1-phase connection
Fig. 1
1 open collector output
VDC
VDC
VDC Reference
NOTE: The 3 and 4 terminals, in the instrument, are
wired together
Fig. 2
GND Reference
The load resistances (RC) must be designed so that the close
contact current is lower than 100mA; the VDC voltage must be
lower than or equal to 30VDC.
Frontal panel description
3
2
1
1. Push button
To program the configuration parameters and the display
of the variables.
2. LED
Red LED to show the consumed energy.
3. Display
LCD-type with alphanumeric indication to:
- display configuration parameters;
- display all the measured variables.
Dimensions and panel cut-out
45.5mm
45mm
90mm
18mm
44mm
67.5mm
6
17.5 +0.5/-0mm
Specifications are subject to change without notice
EM11DINDS200906
Similar pages