ETC D4E180-CA02-02 Ac centrifugal fan Datasheet

AC centrifugal fan
D4E180-CA02-02
forward curved, dual inlet
with housing (large flange)
ebm-papst Mulfingen GmbH & Co. KG
Bachmühle 2 · D-74673 Mulfingen
Phone +49 7938 81-0
Fax +49 7938 81-110
[email protected]
www.ebmpapst.com
Limited partnership · Headquarters Mulfingen
County court Stuttgart · HRA 590344
General partner Elektrobau Mulfingen GmbH · Headquarters Mulfingen
County court Stuttgart · HRB 590142
Nominal data
Type
D4E180-CA02-02
Motor
M4E068-LA
Phase
1~
1~
Nominal voltage
VAC
230
230
Frequency
Hz
50
60
Type of data definition
fa
fa
Valid for approval / standard
CE
CE
Speed
min-1
1250
1280
Power input
W
380
495
Current draw
A
1.68
2.16
Motor capacitor
µF
10
10
Capacitor voltage
VDB
400
400
Min. back pressure
Pa
0
0
Min. ambient temperature
°C
-25
-25
Max. ambient temperature
°C
60
35
Starting current
A
3.3
3.1
ml = Max. load · me = Max. efficiency · fa = Running at free air · cs = Customer specs · cu = Customer unit
Subject to alterations
Data according to ErP directive
Request 2013
Request 2015
32
31.4
38.4
42.6
42
49
B
Overall efficiency ηe
Efficiency category
Total
Efficiency grade N
Variable speed drive
No
Power input Pe
kW
0.21
Specific ratio*
1.00
Air flow qv
m³/h
1130
Pressure increase pf
Pa
219
Speed n
min-1
1410
*
Specific ratio = 1 + pf / 100 000 Pa
%
Actual
Installation category
Data definition with optimum efficiency.
LU-105030
The ErP data is determined using a motor-impeller combination in a standardised measurement configuration.
Item no. 11270-5-9980 · Revision 82891 · Release 2014-04-15 · Page 1 / 5
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
AC centrifugal fan
D4E180-CA02-02
forward curved, dual inlet
with housing (large flange)
Technical features
Mass
10.24 kg
Size
180 mm
Surface of rotor
Coated in black
Material of impeller
Sheet steel, hot-galvanised
Housing material
Sheet steel, hot-galvanised
Motor suspension
Motor anti-vibration mounted on both sides
Direction of rotation
Counter-clockwise, seen on rotor
Type of protection
IP 54
Insulation class
"B"
Humidity class
F3-1
Max. permissible ambient motor
temp. (transp./ storage)
+ 80 °C
Min. permissible ambient motor
temp. (transp./storage)
- 40 °C
Mounting position
Any
Condensate discharge holes
None
Operation mode
S1
Motor bearing
Ball bearing
Touch current acc. IEC 60990
(measuring network Fig. 4, TN
system)
< 0.75 mA
Motor protection
Thermal overload protector (TOP) wired internally
Protection class
I (if protective earth is connected by customer)
Product conforming to standard
EN 60335-1
Approval
CCC
Item no. 11270-5-9980 · Revision 82891 · Release 2014-04-15 · Page 2 / 5
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
AC centrifugal fan
D4E180-CA02-02
forward curved, dual inlet
with housing (large flange)
Product drawing
1
Connection line PVC 4G 0.5 mm², 4 x brass lead tips crimped
Connection screen
U1
blue
PE
green/yellow
Z
brown
U2
black
Item no. 11270-5-9980 · Revision 82891 · Release 2014-04-15 · Page 3 / 5
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
AC centrifugal fan
D4E180-CA02-02
forward curved, dual inlet
with housing (large flange)
Charts: Air flow 50 Hz
Druck p f s[Pa]für Rho=1,2kg/m^3
qv[cfm]
270
0
200
400
600
800
1.000
1.200
1.400
260
1,05
250
1
240
0,95
230
0,9
4
220
210
0,85
200
0,8
190
0,75
3
180
pf s[Pa]
160
0,65
150
0,6
140
0,55
130
0,5
120
0,45
110
2
100
0,4
90
0,35
80
0,3
70
60
0,25
50
0,2
40
0,15
30
0,1
a]
pf s[P
20
10
0
p fs_E[IN H2O]
0,7
170
Air performance measured as per ISO 5801
Installation category A. For detailed
information on the measuring set-up, please
contact ebm-papst. Suction-side noise
levels: LwA measured as per ISO 13347 /
LpA measured with 1m distance to fan axis.
The values given are valid under the
measuring conditions mentioned above and
may vary according to the actual installation
situation. With any deviation from the
standard set-up, the specific values have to
be checked and reviewed with the unit
installed.
1
0
200
400
600
800
1.000
1.200
qv[m^3/h]
1.400
1.600
1.800
2.000
2.200
0,05
0
2.400
Measured values
U
f
n
Pe
I
qv
pfs
V
Hz
min-1
W
A
m3/h
Pa
1
230
50
1250
380
1.68
2155
0
2
230
50
1330
302
1.34
1810
100
3
230
50
1385
245
1.10
1375
180
4
230
50
1430
191
0.89
900
220
U = Supply voltage · f = Frequency · n = Speed · Pe = Power input · I = Current draw · qv = Air flow · pfs = Pressure increase
Item no. 11270-5-9980 · Revision 82891 · Release 2014-04-15 · Page 4 / 5
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
AC centrifugal fan
D4E180-CA02-02
forward curved, dual inlet
with housing (large flange)
Charts: Air flow 60 Hz
Druck p f s[Pa]für Rho=1,2kg/m^3
200
400
600
800
1.000
1.200
1.400
1,55
1,5
1,45
1,4
1,35
1,3
1,25
4
1,2
1,15
1,1
3
1,05
1
0,95
0,9
0,85
0,8
0,75
0,7
p fs_E[IN H2O]
pf s[Pa]
qv[cfm]
Air performance measured as per ISO 5801
Installation category A. For detailed
information on the measuring set-up, please
contact ebm-papst. Suction-side noise
levels: LwA measured as per ISO 13347 /
LpA measured with 1m distance to fan axis.
The values given are valid under the
measuring conditions mentioned above and
may vary according to the actual installation
situation. With any deviation from the
standard set-up, the specific values have to
be checked and reviewed with the unit
installed.
0,65
0,6
2
0,55
0,5
0,45
0,4
0,35
0,3
0,25
0,2
0,15
]
pf s[Pa
390
380
370
360
350
340
330
320
310
300
290
280
270
260
250
240
230
220
210
200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
0
1
0
200
400
600
800
1.000
1.200
qv[m^3/h]
1.400
1.600
1.800
2.000
2.200
0,1
0,05
0
2.400
Measured values
U
f
n
Pe
I
qv
pfs
V
Hz
min-1
W
A
m3/h
Pa
1
230
60
1280
495
2.16
2180
0
2
230
60
1470
410
1.79
1915
140
3
230
60
1600
331
1.48
1450
260
4
230
60
1660
280
1.29
1075
300
U = Supply voltage · f = Frequency · n = Speed · Pe = Power input · I = Current draw · qv = Air flow · pfs = Pressure increase
Item no. 11270-5-9980 · Revision 82891 · Release 2014-04-15 · Page 5 / 5
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
Similar pages