PHOENIX EMD-SL-C-UC-10 Undercurrent monitoring Datasheet

EMD-SL-C-UC-10
Electronic monitoring relay for undercurrent
monitoring of direct and alternating current in
single-phase networks
INTERFACE
Data sheet
103231_en_01
1
© PHOENIX CONTACT - 09/2009
Description
Increasingly higher demands are being placed on safety and
system availability – across all sectors. Processes are
becoming more and more complex, not only in mechanical
engineering and the chemical industry, but also in plant and
automation technology. Demands on power engineering are
also increasing constantly.
Features
–
–
–
–
–
Undercurrent monitoring
Adjustable threshold values
Adjustable hysteresis
Adjustable response delay
Power supply via power module can be selected
Error-free and therefore cost-effective operation can only be
achieved through continuous monitoring of important network
and system parameters. Electronic monitoring relays in the
EMD series are available for a wide range of monitoring tasks
to avoid the consequences of errors or to keep them within
limits.
The operating states are indicated using colored LEDs, errors
that may occur can be sent to a control system via a floating
contact or can shut down a part of the system. Some device
versions are equipped with startup and response delays in
order to briefly tolerate measured values outside the set
monitoring range.
WARNING: Risk of electric shock
Never carry out work when voltage is present.
Make sure you always use the the latest documentation.
It can be downloaded at www.phoenixcontact.net/download.
EMD-SL-C-UC-10
2
Ordering data
Description
Type
Order No.
Pcs. / Pkt.
Electronic monitoring relay for undercurrent monitoring of direct and
alternating current in single-phase networks
EMD-SL-C-UC-10
2867937
1
Accessories
Type
Order No.
Pcs. / Pkt.
Power modules, pluggable, for EMD-SL-..., supply voltage:
20 V DC ... 30 V DC
EMD-SL-PS- 24DC
2885359
1
Power modules, pluggable, for EMD-SL-..., supply voltage:
20.2...26.4 V AC
EMD-SL-PS- 24AC
2866103
1
Power modules, pluggable, for EMD-SL-..., supply voltage:
88...121 V AC
EMD-SL-PS-110AC
2866116
1
Power modules, pluggable, for EMD-SL-..., supply voltage:
108 V AC ... 132 V AC
EMD-SL-PS-120AC
2885731
1
Power modules, pluggable, for EMD-SL-..., supply voltage:
195...264 V AC
EMD-SL-PS-230AC
2866129
1
3
Technical data
Input data
Input name
Measuring input
Measured value
DC, AC sine
Input current range
0 mA ... 100 mA AC/DC (Connection terminals: I1 and GND)
0 A ... 1 A AC/DC (Connection terminals: I2 and GND)
0 A ... 10 A AC/DC (Connection terminals: I3 and GND)
Overload capacity
800 mA (at IN = 100 mA)
3 A (at IN = 1 A)
12 A (at IN = 10 A)
Input resistance current input
470 mΩ (at IN = 100 mA)
47 mΩ (at IN = 1 A)
5 mΩ (at IN = 10 A)
Maximum temperature coefficient
< 0.1 %/K
Setting range for response delay
0.2 s ... 10 s
Min. setting range
5 % ... 95 % (From IN)
Max. setting range
10 % ... 100 % (From IN)
Function
Undercurrent
Basic accuracy
± 5 % (of scale end value)
Setting accuracy
≤ 5 % (of scale end value)
Repeat accuracy
≤2%
Recovery time
500 ms
Output data
Contact type
1 floating PDT
Nominal insulation voltage
250 V AC (in acc. with IEC 60664-1)
Interrupting rating (ohmic load) max.
750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing)
1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing)
Output fuse
5 A (fast-blow)
103231_en_01
PHOENIX CONTACT
2
EMD-SL-C-UC-10
Supply
Range of supply voltages
24 V AC ... 230 V AC (see Power modules)
24 V DC (see Power modules)
Frequency range
48 Hz ... 63 Hz
Nominal power consumption
2 VA (1.5 W)
General data
Mains type
1-phase
Service life mechanical
Approx. 2 x 107 cycles
Service life, electrical
2 x 105 cycles at ohmic load, 1000 VA
Switching frequency
max. 60 (per minute at 100 VA ohmic load)
max. 6 (per minute at 1000 VA ohmic load)
Voltage drop
> 30 % (Relative to the supply voltage)
Operating mode
100% operating factor
Degree of protection
IP40 (housing) / IP20 (connection terminal blocks)
Pollution degree
2 (according to EN 50178)
Surge voltage category
III, basic insulation (as per EN 50178)
Rated insulation voltage
300 V (According to EN 50178)
Assembly
on TS 35 profile rail acc. to EN 60715
Mounting position
Any
Width
22.5 mm
Height
113 mm
Length
90 mm
Type of housing
Polyamide PA, self-extinguishing
Color
green
Weight
160 g
Connection data
Conductor cross section, solid
0.5 mm² ... 2.5 mm²
Conductor cross section, stranded
0.25 mm² ... 2.5 mm²
Stripping length
8 mm
Type of connection
Screw connection
Tightening torque
1 Nm
Ambient conditions
Ambient temperature (operation)
-25 °C ... 55 °C
-25 °C ... 40 °C (corresponds to UL 508)
Ambient temperature (storage/transport)
-25 °C ... 70 °C
Permissible humidity (operation)
15 % ... 85 %
Climatic class
3K3 (in acc. with EN 60721)
Conformance / approvals
Conformity
CE compliant
UL, USA / Canada
UL/C-UL listed UL 508
Conformance with EMC directive 2004/108/EC
Immunity to interference according to
EN 61000-6-2
Emitted interference according to
EN 61000-6-3
Conformance with LV directive 2006/95/EC
Electronic equipm. for electrical power installations according to
103231_en_01
EN 50178
PHOENIX CONTACT
3
EMD-SL-C-UC-10
4
Block diagram
16 18
I1
100 mA
I2
1A
I3
10 A
15
GND
A1
POWER
MODULE
A2
5
U = 24 V DC
24...230 V AC
Safety notes
WARNING: Risk of electric shock
Never carry out work when voltage is present.
6
Structure
D
I2
15
I3
MA
40
70
X( 100
%)
MIN
(% 95
)
5
REL
DE
16
LA
18
Y( 10
s)
7
8
A2
5
"U" LED: Supply voltage
"MAX" LED: Upper threshold value
"MIN" LED: Lower threshold value
"REL" LED: Output relay
"DELAY" potentiometer: Response delay
"MIN" potentiometer: Lower threshold value
"MAX" potentiometer: Upper threshold value
Universal snap-on foot for EN DIN rails
Power module
9
60
5
0
4
current monitor
50
10
MIN
3
GN
EMD-SL-C-UC-10
MAX
2
A1
I1
C
0A
-2312 9
-PS 6
SL 8 6
D- o.:2
EM .-N
rd
O
~
0V
23 2VVA
Hz 64
/60 0 2
505 23
19
U
1
1
2
3
4
5
6
7
8
9
6
7
Power supply
The power module for power supply is supplied in a transport casing to prevent the connection legs from being bent.
To install the power module in the relay housing, remove the transport casing and position the power module in the recess
in the side of the housing (ensure that it is the right way round). The red locking latches snap in with an audible click when
the power module is securely positioned.
To remove the power module, press the two red locking latches together and pull out the power module.
103231_en_01
PHOENIX CONTACT
4
EMD-SL-C-UC-10
8
Installation
WARNING: Risk of electric shock
Never carry out work when voltage is present.
The module can be snapped onto all 35 mm DIN rails according to EN 60715.
9
Diagnostics
The LEDs indicate the following error states:
"U" LED (Green)
–
LED ON: Supply voltage present
"MIN" and "MAX" LEDs (Red)
–
–
–
"MIN" LED flashes: Minimum value not reached, set delay time is running
"MIN" LED ON: Minimum value not reached, delay time has elapsed
Both LEDs flash alternately: Lower set threshold value is greater than upper threshold value
"REL" LED (Yellow)
–
–
10
LED ON: Output relay has picked up
LED OFF: Output relay has dropped out
Connection examples
L1
L2
L3
N
L1
L2
L3
N
24 V ~~
0V
A1 GND 15
I1
16
I2
I3
I1
I2
15
15
16 18
16 18
18
A2
100 mA (I1) measuring range with 24 V AC power module
103231_en_01
A1 GND 15
16
18
I3
A2
1 A (I2) measuring range with 230 V AC power module
PHOENIX CONTACT
5
EMD-SL-C-UC-10
L1
L2
L3
N
A1 GND 15
I1
I2
I3
15
16
16
18
18
A2
10 A (I3) measuring range with 230 V AC power module
11
Function
Undercurrent Monitoring (UNDER)
U
LED U
LED MAX
LED MIN
LED REL, R
MAX
MIN
DELAY
103231_en_01
< DELAY
DELAY
When supply voltage U is applied, output relay "R" picks up
(yellow "REL" LED is ON).
If the measured current falls below the value set at the "MIN"
controller, the set response delay (DELAY) starts (red "MIN"
LED flashes). After the delay time has elapsed (red "MIN"
LED is ON), output relay "R" drops out (yellow "REL" LED is
OFF).
If the measured current exceeds the value set at the "MAX"
controller, output relay "R" picks up again (yellow "REL" LED
is ON).
The "MIN" and "MAX" LEDs flash alternately if the minimum
value selected for the measured current is greater than the
maximum value.
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49-(0) 5235-3-00
PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300
www.phoenixcontact.com
6
Similar pages