XP Power FCM400PS24 Integral low noise fan Datasheet

FCM400 Series
•
Integral Low Noise Fan
•
400 W Output Power
•
600 W Peak Rating 500 ms
•
Screw Terminals
•
Class B Conducted Emissions
•
5 V Standby Rail
•
80 V - 275 VAC Input Operation
•
IT & Medical Safety Approvals
•
Remote On/Off & Power Fail Signal as Standard
The FCM400 AC-DC power supply provides upto 400 W continuous and 600 W peak output power for up to 0.5 seconds.
Packaged in a compact 6” (152 mm) x 4” (102 mm) x 1.9” (49 mm) and certified to IEC60950 & IEC60601 family safety approvals, the
FCM400 can be easily integrated into a wide range of both industrial and medical applications. A low noise fan allows quiet operation
at full power from -10 ºC to 50 ºC and 50% power at +70 ºC.
The unit comprises of a main output with voltages from 12-48 VDC and a peripheral output providing a 5 VDC standby supply which
can be utilitsed with the signals and control features of the unit to provide detection of loss of AC input and remote on/off control.
xppower.com
Models and Ratings
Output Power
P nom
P peak
Output Voltage V1
(1)
Output Current V1
I nom
I peak
(1)
Standby Supply V2
Model Number
FCM400PS12
400 W
600 W
12.0 VDC
33.3 A
50 A
5.0 V/0.5 A
400 W
600 W
15.0 VDC
26.6 A
40 A
5.0 V/0.5 A
FCM400PS15
400 W
600 W
24.0 VDC
16.6 A
25 A
5.0 V/0.5 A
FCM400PS24
400 W
600 W
28.0 VDC
14.2 A
21.4 A
5.0 V/0.5 A
FCM400PS28
400 W
600 W
36.0 VDC
11.1 A
16.7 A
5.0 V/0.5 A
FCM400PS36
400 W
600 W
48.0 VDC
8.3 A
12.5 A
5.0 V/0.5 A
FCM400PS48
Notes:
1. Peak duration is 500 ms max, average power must not exceed 400 W.
Input Characteristics
Characteristic
Minimum
Typical
Maximum
Units
Notes & Conditions
Derate output power <90 VAC. See fig 1.
Power fail signal cannot be used <90 VAC.
Input Voltage - Operating
80
115/230
275
VAC
Input Frequency
47
50/60
>0.9
63
Hz
Power Factor
EN61000-3-2 class A compliant
Input Current - No Load
0.11/0.15
A
115/230 VAC
Input Current - Full Load
4.1/2.1
A
115/230 VAC
Inrush Current
60
Earth Leakage Current
Input Protection
100/165
260
A
230 VAC, 25 şC
μA
115 VAC 60 Hz/230 VAC 50 Hz (Typ),
264 VAC/60 Hz (Max.)
F10 A/250 V internal fuse in both line and neutral
Output Characteristics
Characteristic
Output Voltage - V1
Minimum
Typical
12
Initial Set Accuracy
Output Voltage Adjustment
Minimum Load
Maximum
Units
Notes & Conditions
48
VDC
See Models and Ratings table
±0.5 (V1) , ±5 (V2)
%
50% load, 115/230 VAC
±10
%
V1 only via potentiometer. See mech. details (page 11).
0
A
Start Up Delay
1
s
35
ms
90 VAC full load (see fig.3)
±0.2
%
After 20 min warm up
Line Regulation
±0.5
%
90-264 VAC
Load Regulation
±1 (V1) , ±5 (V2)
%
0-100% load.
%
Recovery within 1% in less than 500 μs
for a 50-75% and 75-50% load step
Hold Up Time
20
Drift
Transient Response - V1
4
Over/Undershoot - V1
Ripple & Noise
0.5
5
%
1 (V1), 2 (V2)
% pk-pk
Overvoltage Protection
115
140
%
Overload Protection
150
165
% I nom
0.05
%/˚C
Short Circuit Protection
Temperature Coefficient
Overtemperature Protection
2
230 VAC full load (see fig.2)
20 MHz bandwidth (see fig.4 & 5)
Vnom DC. Output 1 only, recycle input to reset
Output 1 only, auto reset (see fig.6)
Continuous (see fig. 6)
°C
Auto recovery - temperature of main transformer
xppower.com
Input Voltage Derating
600
Figure. 1
Output Power (W)
540
Peak Power Availability
400
360
320
300
80
85
90
Input Voltage (VAC)
264
275
Start Up Delay From AC Turn On
AC
Figure. 2
V1 & V2 start up example
from AC turn on (1.5 s)
V1
V2
Hold Up Time From Loss of AC
AC
V1
Figure 3
V1 hold up example at 400 W
load with 90 VAC input (42 ms)
3
xppower.com
Output Ripple & Noise
Figure 4
V1 FCM400PS12 (full load)
50 mV pk-pk ripple. 20 MHz BW
Figure 5
V1 FCM400PS24 (full load)
38 mV pk-pk ripple. 20 MHz BW
Output Overload Characteristic
14
12
Figure 6
Typical V1 Overload
Characteristic
(FCM400PS12 shown)
Output Volts (V)
10
8
6
4
2
0
0
2
4
6
32
34
Output Current (A)
4
36
38
40
xppower.com
General
Specifications
Xxxxxxxxxx
Characteristic
Minimum
Typical
Efficiency
Maximum
Units
87
%
4000
Isolation: Input to Output
Input to Ground
Output to Ground
Notes & Conditions
Full load (see fig.7 & 8)
VAC
1500
VAC
500
VAC
Switching Frequency
70 / 65
kHz
Power Density
Mean Time Between Failure
Weight
PFC / Main Converter.
W/in3
13.9
236
kHrs
1.8 (800)
lb (g)
MIL-HDBK-217F, Notice 2
+25 °C GB
Efficiency Versus Load
100%
90%
70%
60%
230Vac input
50%
40%
10
20
30
40
50
60
70
80
90
100
Load (%)
Figure 7
FCM400PS12
100%
90%
80%
Efficiency
Efficiency
80%
70%
60%
230VAC input
50%
40%
10
20
30
40
50
60
70
80
90
100
Load (%)
Figure 8
FCM400PS24
5
xppower.com
Characteristic
Notes & Conditions
Signals
Power Fail
Uncomitted opto isolated transistor, normally off when AC is good (see fig.9 - 11)
Provides ≥ 5 ms (typically 20-30ms) warning of loss of output from AC failure
Remote On/Off (Inhibit/Enable)
Uncommited isolated optocoupler diode, powered diode inhibits the supply (see fig.12-17)
Standby Supply V2
Isolated 5 V/0.5 A supply, always present when AC supplied.
Signals
Power Fail
POWER SUPPLY
Pin 2, 4 & 6
CON 8
5 V Standby
8V Max 3 mA
2K2
Pin 7 CON 8
Power Fail
Collector
Figure 9
Transistor On (<0.8 V): Input & Output Not OK
Transistor Off (>4.5 V): Input & Output OK
Power Fail
Emitter
Pin 8 CON 8
5 V Standby Rtn
Pin 1, 3 & 5
CON 8
Signal Connector
PF
PF
V1
V1
AC
V2
Figure 10
Power Fail signal example
at AC switch off
6
Figure 11
V1 warning time example at Power Fail signal 230
VAC 400 W load (31 ms)
xppower.com
Signals
Remote On/Off (Inhibit/Enable)
POWER SUPPLY
POWER SUPPLY
5 V Standby
2, 4 & 6 CON 8
5 mA
5 V Standby
Pin 2, 4 & 6
CON 8
8 V Max
Inhibit Hi
Pin 10 CON 8
Inhibit Lo
Pin 9 CON 8
8 V Max
Inhibit Hi
Pin 10
CON 8
5 mA
1K
1K
Logic GND
Pin 1, 3 & 5
CON 8
Logic GND Pin
1, 3 & 5 CON 8
Figure 12
Inhibit (Hi)
Inhibit Lo
Pin 9 CH 1
Signal Connector
Figure 13
Inhibit (Lo)
Signal Connector
Inhibit
V1
Figure 14
Example of outputs
switching off when
Inhibit (Lo) configuration
used & switch closed
V2
Inhibit
Figure 15
Example of outputs
switching on when
Inhibit (Lo) configuration
used & switch open
V1
V2
7
xppower.com
Signals
Xxxxxxxxxx
Remote On/Off (Inhibit/Enable)
1K
Figure 16
Enable (Hi)
POWER SUPPLY
5 V Standby
Pin 2, 4 & 6 CON 8
1K
Inhibit Hi
Pin 10 CON 8
5 mA
Inhibit Lo
Pin 9
CON 8
Logic GND
Pin 1, 3 & 5 CON 8
Signal Connector
1K
POWER SUPPLY
Figure 17
Enable (Lo)
5 V Standby
Pin 2, 4 & 6 CON 8
1K
Inhibit Hi
Pin 10
CON 8
5 mA
Inhibit Lo
Pin 9
CON 8
Logic GND
Pin 1, 3 & 5, CON 8
Signal Connector
Notes
1. At AC switch on the output (VI) may momentarily rise when the unit is disabled using the 5 V standby in conjunction with the Remote On/Off function.
Environmental
Characteristic
Operating Temperature
Minimum
-10
Warm up Temperature
Storage Temperature
Typical
Maximum
Units
+70
şC
20
-40
Operating Altitude
8
Derate linearly from +50 şC at 2.5%/şC
to 50% at 70 şC. See fig.18.
Minutes
+85
şC
Cooling
Humidity
Notes & Conditions
Forced cooled via low noise intregal fan
5
95
%RH
3000
m
Non-condensing
Shock
3 x 30 g/11 ms shocks in both +ve & -ve
directions along the 3 orthogonal axis,
total 18 shocks.
Vibration
Single axis 10-500 Hz at 2 g x 10 sweeps
xppower.com
Derating Curve
Figure 18
Output Power (W)
600
500
Peak Power Availability
400
300
200
100
0
-10
0
10
40
Ambient Temperature (°C)
50
60
70
Electromagnetic Compatibility - Immunity
Phenomenon
Standard
Test Level
Criteria
EN61204-3
High severity level
as below
Harmonic Current
EN61000-3-2
Class A
Radiated
EN61000-4-3
3
A
EFT
EN61000-4-4
3
A
Surges
EN61000-4-5
Installation class 3
A
Conducted
EN61000-4-6
3
A
Low Voltage PSU EMC
EN61000-4-11
Dips and Interruptions
EN60601-1-2
(EN61000-4-11)
Dip:
30% 10 ms
A
Dip:
60% 100 ms
B
Dip: 100% 5000 ms
B
Dip:
30% 500 ms
A
Dip:
60% 100 ms
A
Dip:
100% 10 ms
A
Int.: >95% 5000 ms
B
Notes & Conditions
Requires load derating to approx TBA% with
100 VAC input.
Electromagnetic Compatibility - Emissions
Phenomenon
Conducted
Radiated
Voltage Fluctuations
Standard
Test Level
EN55011/22
Class B
EN55011/22
Class A
Criteria
Notes & Conditions
EN61000-3-3
9
xppower.com
Safety Agency Approvals
Safety Agency
Safety Standard
Category
CB Report
UL Cert #US/15598/UL, IEC60950-1:2005 Ed 2
Information Technology
UL
UL File #E139109-A43-UL, UL60950-1 (2007), CSA 22.2 No.60950-1-07 Ed 2
Information Technology
TUV
TUV Certificate # B 10 09 57396 081, EN60950-1/A11 2009
Information Technology
CE
LVD
Safety Agency
Safety Standard
Category
CB Report
Certificate #US/17946/UL, IEC60601-1 Ed 3 Including Risk Management
Medical
UL
UL File # E146893, ANSI/AAMI ES 60601-1:2005 & CSA C22.2 No. 60601-1:08
Medical
TUV
EN60601-1:2006
Medical
Primary to Secondary
2 x MOPP (Means of Patient Protection)
Primary to Earth
1 x MOPP (Means of Patient Protection)
Equipment Protection Class
Safety Standard
Notes & Conditions
IEC60950-1:2005 Ed 2 & IEC60601-1 Ed 3
See safety agency conditions of
acceptibility for details
Means of Protection
Class I
10
Category
IEC60601-1 Ed 3
xppower.com
Xxxxxxxxxx Details
Mechanical
6.00 ±0.02
(152.4 ±0.5)
NOT INCLUDING OUTPUT
TERMINAL SCREWS
OUTPUT VOLTAGE
ADJUSTMENT
2
1
4.00 ±0.02
(101.6 ±0.5)
OUTPUT TERMINALS
ALLOW CONNECTION
FROM EITHER TOP OR SIDE
OUTPUT TERMINALS
M4 SCREWS IN 2
POSITIONS. TORQUE
TO 90 cNm Max.
INPUT CONNECTOR
M3 MOUNTING HOLES (IN 4 POSITIONS). MAX. PENETRATION
BY SCREW TO BE 2.5mm FROM BOTTOM FACE OF CHASSIS
0.52
(13.3)
2.95
(75.0)
Pin 2
Pin 1
Pin 10
Pin 9
SIGNALS CONNECTOR CON8
10-WAY JST-BIOB-PDHSS
3.94
(100.0)
1.03
(26.2)
M3 MOUNTING HOLES (IN 2 POSITIONS). MAX. PENETRATION
BY SCREW TO BE 3.5mm FROM OUTSIDE FACE OF CHASSIS
1.93 ±0.02
(49.0 ±0.5)
0.96
(24.3)
2.10
(53.4)
3.35
(85.0)
Notes
1. Dimensions shown in inches (mm).
Tolerance: ±0.02 (±0.5)
2. Weight: 1.8 lb (800g).
HEIGHT INCLUDES
EMBOSSED FAN COVER
1
2
3
4
5
6
7
8
9
10
Signals Connector CON 8
5 V Standby Return
5 V Standby
5 V Standby Return
5 V Standby
5 V Standby Return
5 V Standby
Power Fail (Collector)
Power Fail (Emitter)
Remote On / Off (Cathode)
Remote On / Off (Anode)
Pin 1
Pin 2
Pin 3
Line
Neutral
Earth
J1 mates with Tyco MTA-156 & 5L-156 product lines
Mating plug: JST p/n PHDR-10VS
Contact: 26-22 AWG JST p/n SPHD-001T-P0.5
07-Nov-11
Similar pages