XP Power ECS65US28 65/100/130 watts ecs sery Datasheet

AC-DC
65/100/130 Watts
xppower.com
ECS Series
•
IT & Medical Safety Approvals
•
65/80/100 W - Convection-cooled Ratings
•
Class I & Class II Construction
•
Industry Standard 2”x 4”Package
•
<0.5 W No Load Input Power
•
Low Leakage Current
•
3 Year Warranty
Specification
Input
General
• 80-264 VAC (275 VAC ECS65)
(120-370 VDC), derate output power
<90 VAC, see derating curves
Input Frequency
• 47-400 Hz(1)
Input Current
• 65 W: 1.0/0.6 A typical at 115/230 VAC
100 W: 1.5/0.9 A typical at 115/230 VAC,
130 W: 1.9/1.1 A typical at 115/230 VAC
full load
Inrush Current
• 40 A max at 230 VAC, cold start at 25 ˚C
Power Factor
• EN61000-3-2, class A
No Load Input Power • <0.5 W
Earth Leakage Current • 65/130 W: 260 µA at 264 VAC/60 Hz max
100 W: 230 µA at 264 VAC/60 Hz max
Input Protection
• Internal T3.15/T5 A/250 V fuse in line and
neutral
Input Voltage
Output
Output Voltage
Output Voltage Trim
Initial Set Accuracy
Minimum Load
Start Up Delay
Start Up Rise Time
Hold Up Time
Drift
Line Regulation
Load Regulation
Over/Undershoot
Transient Response
•
•
•
•
•
•
•
•
•
•
•
•
Ripple & Noise
Overvoltage Protection
Overload Protection
Short Circuit Protection
Temperature
Coefficient
•
•
•
•
•
12-48 VDC (see tables)
±10%
±1%
No minimum load required
1 s typical
50 ms
16 ms min at 115 VAC
±0.2% after 20 min warm up
±0.5% max
±1%
5% typical
4% max. deviation, recovery to within
1% in 500 µs for a 50-75-50% load
change
1% pk-pk, 20 MHz bandwidth
115-140% Vnom, recycle input to reset
110-160%
Continuous trip and restart (hiccup mode)
0.05%/˚C
Notes
1. Safety approvals cover frequency 47-63 Hz.
Efficiency
Isolation
Switching Frequency
Power Density
MTBF
• Up to 90% model dependent
• 4000 VAC Input to Output, 2 x MOPP,
1500 VAC Input to Ground, 1 x MOPP,
500 VDC Output to Ground, 1 x MOPP
• 65 KHz typical
• 65 W: 7.7 W/in3, 100 W: 10 W/in3,
130 W: 13 W/in3
• 65 W: 850 kHrs, 100 W: 834 kHrs,
130 W: 715 kHrs to MIL-HDBK-217F
at 25 ˚C, GB
Environmental
Operating Temperature • -20 ˚C (-40 ˚C, ECS130) to +70 ˚C derate
linearly from +50 ˚C at 2.5%/˚C to 50%
load at +70 ˚C.
Cooling
• Convection & fan cooled ratings (see tables)
Operating Humidity
• 95% RH, non-condensing
Storage Temperature
• -40 ˚C to +85 ˚C
Operating Altitude
• 65-100 W: 3000 m, 130 W: 5000m
Shock
• 30 g pk, half sine, 6 axes
Vibration
• 2 g rms, 5 Hz to 500 Hz, 3 axes
EMC & Safety
Low Voltage PSU EMC • EN61204-3, high severity level
Emissions
• EN55011/22 level B conducted
EN55011/22 level A radiated, level B
Suffix ‘-B’ models
Harmonic Currents
• EN61000-3-2, class A
Voltage Flicker
• EN61000-3-3
ESD Immunity
• EN61000-4-2, ±6 kV Contact, ±15 kV Air
Discharge, Perf Criteria A
Radiated Immunity
• EN61000-4-3, level 3 Perf Criteria A
EFT/Burst
• EN61000-4-4, level 3 Perf Criteria A
Surge
• EN61000-4-5, installation class 3
Perf Criteria A
Conducted Immunity
• EN61000-4-6, level 3 Perf Criteria A
Dips & Interruptions
• EN61000-4-11, 30% 10 ms, 60% 100 ms,
100% 5000 ms, Perf Criteria A, B, B,
EN60601-1-2, 30% 500 ms, 60% 100 ms,
100% 10 ms, 100% 5000 ms, Perf Criteria
A, A, A, B - 230 VAC. Consult longform
datasheet for 115 V operation.
Safety Approvals
• IEC60950-1 CB report, CSA 22.2
No. 60950-1, UL60950-1, TUV EN60950-1
IEC60601-1 CB report, CSA 22.2
No. 60601-1, ANSI/AMMI ES60601-1,
TUV 60601-1, including risk management
Equipment Protection • Class I & II (ECS65 Non ‘-B’ models,
Class
Class I only)
Output Power
Output Voltage
65 W
65 W
65 W
65 W
65 W
65 W
12.0 VDC
15.0 VDC
18.5 VDC
24.0 VDC
28.0 VDC
48.0 VDC
Output Current
5.4
4.3
3.4
2.7
2.3
1.4
Model Number(1)
A
A
A
A
A
A
ECS65US12
ECS65US15
ECS65US18
ECS65US24
ECS65US28
ECS65US48
Notes
1. For Class B radiated emissions models, add suffix -B to model number. For covered versions, add suffix ‘-C’ to model number or order part no. ECM40/60 COVER
KIT for standalone cover. Derate output power by 20% with cover. The cover is not suitable for Class II installations.
Mechanical Details
4.00 (101.6)
1.05
(26.7)
3.750 (95.25)
0.125 (3.17)
C4
1
2.00 (50.8)
1.75 (44.45)
C5
J1 2
1
T1
1
0.95 (24.1)
4
0.25 Faston Ground Tab
0.125 (3.18)
Q1
J2
0.96 (24.5)
0.20 (5.1)
4 X ø.156 (3.96) Mounting Holes
ø.312 (7.92) Clearance top and bottom
0.20 (5.1)
Input Connector J1
Molex PN 09-65-2038
Pin 1
Line
Pin 2
Neutral
0.25” Faston
Earth
0.14 (3.5)
SMD Component Height
Output Connector J2
Molex PN 09-65-2048
Pin 1
+V1
Pin 2
+V1
Pin 3
RTN
Pin 4
RTN
J1 mates with Molex Housing PN 09-50-1031, J2 mates with
Molex Housing PN 09-50-1041 and both with Molex Series 5194
Crimp Terminals
Notes
1. All dimensions in inches (mm).
Tolerance .xx = ±0.02 (0.50); .xxx = ±0.01 (0.25)
2. Weight: 0.386 lbs (175 g)
100
100
90
90
80
80
Output Power (%)
Output Power (%)
Derating Curve - ECS65 Models
70
60
50
40
80
85
275
90
Input Voltage (VAC)
Open Frame
70
60
50
40
37.5
30
-20
40
50
Ambient Temperature (ºC)
60
75
AC-DC
ECS65
Models and Ratings
Output Power
Forced Cooled (10 CFM)
Convection-cooled
100 W
80 W
100 W
80 W
100 W
80 W
100 W
80 W
100 W
80 W
100 W
80 W
Output Voltage
Output Current
12.0 VDC
15.0 VDC
18.0 VDC
24.0 VDC
28.0 VDC
48.0 VDC
8.3
6.7
5.5
4.2
3.6
2.1
Model Number(1)
A
A
A
A
A
A
ECS100US12
ECS100US15
ECS100US18
ECS100US24
ECS100US28
ECS100US48
Notes
1. For Class B radiated emissions models, add suffix -B to model number. For covered versions, add suffix ‘-C’ to model number or order part no. ECM40/60 COVER
KIT for standalone cover. Derate output power by 20% with cover. The cover is not suitable for Class II installations. ‘-C’ not available for ‘-B’ models.
Mechanical Details
1.25 (31.8)
4.00 (101.6)
3.750 (95.25)
0.125 (3.18)
C4
1.750
(44.45)
2.00
(50.8)
Voltage
Adj.
J1
C5
T1
J2
1.01
(25.7)
1.00
(25.4)
Q1
0.25 Faston
Ground Tab
0.125 (3.18)
0.20 (5.1)
0.14 (3.5)
SMD Component
Height
4 X ø.156 (3.96) Mounting Holes
ø.312 (7.92) Clearance top and bottom
0.20 (5.1)
‘ B’Model
1.25 (31.8)
4.50 (114.3)
0.37 (9.52)
2.00
(50.8)
Output Connector J2
Molex PN 09-65-2048
Pin 1
+V1
Pin 2
+V1
Pin 3
RTN
Pin 4
RTN
Input Connector J1
Molex PN 09-65-2038
Pin 1
Line
Pin 2
Neutral
0.25” Faston
Earth
J1 mates with Molex Housing
PN 09-50-1031, J2 mates with
Molex Housing PN 09-50-1041
and both with Molex Series 5194
Crimp Terminals
3.75 (95.25)
1.75 J1
(44.45)
Notes
J2
0.20
(5.1)
1.00
(25.4)
1. All dimensions in inches (mm).
Tolerance .xx = ±0.02 (0.50);
.xxx = ±0.01 (0.25)
2. Weight: 0.386 lbs (175 g)
1.01
(25.7)
0.20 (5.1)
0.125 (3.18)
4 X ø.156 (3.96) Mounting Holes
ø.312 (7.92) Clearance top and bottom
0.14 (3.5)
SMD Component
Height
0.10 (2.5)
0.25 Faston Ground Tab
Derating Curve - ECS100 Models
100
100
90
90
80
80
Output Power (W)
Output Power (%)
AC-DC
ECS100
Models and Ratings
70
60
50
40
70
60
Force-cooled >10 CFM
Convection-cooled
Convection-cooled with cover
50
40
30
80
85
264
90
Input Voltage (VAC)
-20
+40
+50
Ambient Temperature (ºC)
+60
+70
Output Power
Forced Cooled (10 CFM)
Convection-cooled
130 W
100 W
130 W
100 W
130 W
100 W
130 W
100 W
130 W
100 W
130 W
100 W
Output Voltage
Output Current
12.0 VDC
15.0 VDC
18.0 VDC
24.0 VDC
28.0 VDC
48.0 VDC
10.9
8.7
7.3
5.4
4.7
2.7
Model Number(1)
A
A
A
A
A
A
ECS130US12
ECS130US15
ECS130US18
ECS130US24
ECS130US28
ECS130US48
Notes
1. For covered versions, add suffix ‘-C’ to model number or order part no. ECM40/60 COVER KIT for standalone cover, see derating curve.
The cover is not suitable for Class II installations. ‘-C’.
Mechanical Details
4.00 (101.6)
0.125 (3.17)
1.28
(32.5)
3.750 (95.25)
Voltage Adjust
C4
2.00 (50.8)
1.75 (44.45)
N
J1
L
2
1
1
T1
J2
C5
1.00 (25.4)
4
0.12 (3.18)
0.20 (5.1)
Q1
0.20 (5.1)
1.05 (26.7)
0.15 (3.8)
SMD COMPONENT HEIGHT
.25 FASTON
GROUND TAB
4X 0.156 (3.96) MOUNTING HOLES
0.312 (7.92) CLEARANCE TOP AND BOTTOM
Output Connector J2
Molex PN 09-65-2048
Pin 1
+V1
Pin 2
+V1
Pin 3
RTN
Pin 4
RTN
Notes
Input Connector J1
Molex PN 09-65-2038
Pin 1
Line
Pin 2
Neutral
0.25” Faston
Earth
1. All dimensions in inches (mm).
Tolerance .xx = ±0.02 (0.50); .xxx = ±0.01 (0.25)
2. Weight: 0.386 lbs (175 g)
J1 mates with Molex Housing PN 09-50-1031, J2 mates with Molex Housing PN 09-50-1041
and both with Molex Series 5194 Crimp Terminals
Derating Curve - ECS130 Models
130
130
120
Forced-cooled >10 CFM
110
110
100
90
Convection-cooled
80
Output Power (W)
Output Power (W)
100
70
60
Convection-cooled with cover
50
90
80
70
60
50
40
40
30
30
20
20
10
10
80
90
100
Input Voltage (VAC)
264
-40
Forced-cooled >10 CFM
Some specification parame ters may not be met
120
Convection-cooled
Convection-cooled with cover
-20
0
Ambient Temperature (ºC)
50
60
70
AC-DC
ECS130
Models and Ratings
AC-DC
ECS65/100/130
Mechanical Details
Covered Version (not available for ECS100-B Models)
4.49 (114.0)
2.52
(64.0)
Input Connector
Output Connector
0.25 (0.6) Ground
Faston Terminal
0.807
(20.50)
1.54
(39.0)
2 x M3 x 0.5 THD
0.16 (4.0)
Max Screw Penetration
4.055 (103.00)
0.22
(5.5)
4.055 (103.00)
0.22
(5.5)
0.79
(20.0)
0.984
(25.00)
4 x M3 x 0.5 THD
0.16 (4.0) Max Screw Penetration
Notes
1. All dimensions in inches (mm).
Tolerance .xx = ±0.02 (0.50); .xxx = ±0.01 (0.25)
2. Weight: 0.8 lbs (360 g)
Thermal Considerations - All Models
In order to ensure safe and reliable operation of the PSU in the most adverse conditions permitted in the end-use equipment, the temperature of the components
listed in the table below must not be exceeded. See mechanical drawing for component locations. Temperature should be monitored using K type thermocouples
placed on the hottest part of the component (out of any direct air flow).
Component
Temperature Measurements (Ambient ≤ 50 °C)
Max Temperature °C
T1
110 °C
C5
100 °C
C4
100 °C
Q1
110 °C
16-Aug-16