ETC1 LPN-RK-4/10SP Dual element, time-delay fus Datasheet

Technical Data 1003
Effective March 2017
Supersedes July 2015
LPN-RK — 250 Vac/125 Vdc, 1⁄10-60 A,
dual element, time-delay fuses
Catalog no.
Catalog symbols:
•
LPN-RK(amp)SP (non-indicating)
•
LPN-RK(amp)SPI (indicating)
Description:
Ultimate protection Class RK1 dual element,
current-limiting, time-delay fuses available with
optional open fuse indication. Time-delay – 10
seconds (minimum) at 500% of rated current (8
seconds for 0-30A sizes).
LPN-RK-1/10SP
LPN-RK-2SP
LPN-RK-9SP
LPN-RK-15/100SP
LPN-RK-21/4SP
LPN-RK-10SP
LPN-RK-2/10SP
LPN-RK-21/2SP
LPN-RK-12SP
LPN-RK-3/10SP
LPN-RK-28/10SP LPN-RK-15SP
LPN-RK-4/10SP
LPN-RK-3SP
LPN-RK-1/2SP
LPN-RK-32/10SP LPN-RK-20SP
LPN-RK-6/10SP
LPN-RK-31/2SP
LPN-RK-25SP
LPN-RK-8/10SP
LPN-RK-4SP
LPN-RK-30SP
LPN-RK-1SP
LPN-RK-41/2SP
LPN-RK-35SP*
LPN-RK-11/8SP
LPN-RK-5SP
LPN-RK-40SP*
LPN-RK-11/4SP
LPN-RK-56/10SP LPN-RK-45SP*
LPN-RK-14/10SP
LPN-RK-6SP
LPN-RK-50SP*
LPN-RK-16/10SP
LPN-RK-61/4SP
LPN-RK-60SP*
LPN-RK-18/10SP
LPN-RK-8SP
* Open fuse indication available by inserting the suffix “I,”
e.g. LPN-RK-50SPI. Requires 75Vac minimum voltage.
Carton quantity
•
•
Volts
• 250 Vac
•
125 Vdc
•
Amps 1/10-60A
•
IR
•
300 kA Vac RMS Sym.
•
100kA Vdc
Agency Information
•
UL Listed, Guide JDDZ, File E4273
•
CSA Certified, Class 1422-02, File 53787,
Class RK1 per CSA C22.2, No. 248.12
•
CE
10
Features and benefits
•
Industry’s only UL Listed and CSA Certified fuse
with a 300 kA interrupting rating that allows for
simple, worry-free installation in virtually any
application.
•
Fast short-circuit protection and dual-element,
time-delay performance provide ultimate
protection.
•
Reduces existing fuse inventory by up to 33%
when upgrading to Low-Peak fuses.
•
Consistent 2:1 ampacity ratios for all Low-Peak
fuses make selective coordination easy.
•
Time-delay permits 130% FLA sizing for back-up
motor protection.
•
Current-limitation protects downstream
components against damaging thermal and
magnetic effects of short-circuit currents.
•
Protects against single-phase motor damage.
•
Proper sizing can provide “no damage” Type 2
coordinated protection for NEMA and IEC motor
controllers.
Specifications:
Ratings
LPN-RK-171/2SP
Technical Data 1003
LPN-RK — 250 Vac/125 Vdc, 1⁄10-60 A, dual element, time-delay fuses
Effective March 2017
Time-current curves - average melt
Recommended fuse blocks
2-Pole
RM25030-2_
RM25060-2_
3-Pole
RM25030-3_
RM25060-3_
For additional information on the 250 volt fuse blocks, see data
sheets no. 10289.
Fuse reducers for Class R fuses
Desired fuse (case)
Equipment fuse clips size
60 A
30 A
30 A
100 A
60 A
200 A
60 A
Dimensions — in
3
0.56
1/10 to 30 A
AMP RATING
100
Catalog no. (pairs)
250V
NO.263-R
NO.213-R
NO.216-R
NO.226-R
For additional information on Class R fuse reducers, see data sheet
no. 1118.
2
300
0.1
0.15
0.2
0.3
0.4
.50
0.6 0.8
1
1.25
1.6 2
2.5
3.2
4
5
6.25
8
10
12
Amps
30
60
1/10 to 12 amps
0.81
10
TIME IN SECONDS
Catalog no.
1-Pole
RM25030-1_
RM25060-1_
1
35 to 60 A
2
Eaton.com/bussmannseries
1000
CURRENT IN AMPS
100
10
0.1
0.01
1
0.1
Technical Data 1003
LPN-RK — 250 Vac/125 Vdc, 1⁄10-60 A, dual element, time-delay fuses
Effective March 2017
Time-current curves - average melt
Current-limitation curves
15 to 60 amps
B
300,000
AMP RATING
INSTANTANEOUS PEAK LET-THROUGH CURRENT IN AMPS
100
10
100,000
90,000
80,000
70,000
60,000
50,000
40,000
30,000
20,000
60A
10,000
9000
8000
7000
6000
30A
5000
4000
3000
A
2000
200,000
300,000
80,000
100,000
60,000
40,000
30,000
20,000
8000
10,000
6000
4000
3000
2000
1000
1000
TIME IN SECONDS
200,000
AMP RATING
60A
300
30A
15A
20A
400,000
RMS SYMMETRICAL CURRENT IN AMPS
A-B = ASYMMETRICAL AVAILABLE PEAK (2.3 X SYM RMS AMPS)
1
Current-limiting effects
CURRENT IN AMPS
10,000
1000
20
0.01
100
0.1
Prosp.
S.C.C.
—
1000
2000
3000
5000
10,000
15,000
20,000
25,000
30,000
35,000
Let-through current (apparent RMS Sym. vs. fuse rating)
30 A
60 A
1000
1000
1000
1000
1000
1000
1000
2000
1000
2000
1000
2000
1000
3000
1000
3000
2000
3000
2000
3000
40,000
50,000
60,000
70,000
80,000
90,000
100,000
150,000
200,000
250,000
300,000
2000
2000
2000
2000
2000
2000
2000
2000
3000
3000
3000
3000
3000
3000
3000
4000
4000
4000
4000
5000
5000
6000
Eaton.com/bussmannseries
3
Technical Data 1003
LPN-RK — 250 Vac/125 Vdc, 1⁄10-60 A, dual element, time-delay fuses
Effective March 2017
The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this document are
by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the
end user with design applications. Eaton reserves the right, without notice, to change design or construction of any products and to discontinue or limit
distribution of any products. Eaton also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once
a product has been selected, it should be tested by the user in all possible applications.
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
Eaton.com
Bussmann Division
114 Old State Road
Ellisville, MO 63021
United States
Eaton.com/bussmannseries
© 2017 Eaton
All Rights Reserved
Printed in USA
Publication No. 1003 — BU-SB13686
March 2017
Eaton.com/bussmannseries
Eaton, Bussmann and Low-Peak are valuable
trademarks of Eaton in the U.S. and other
countries. You are not permitted to use
the Eaton trademarks without prior written
consent of Eaton.
CSA is a registered trademark of the Canadian
Standards Group.
UL is a registered trademark of the
Underwriters Laboratories, Inc.
Follow us on social media to get the
latest product and support information.
Similar pages