Kemet FLLD31K6AP-I1 High current 3-phase emc filter Datasheet

FLLD3 … PV
High current 3-phase EMC Filter
Overview
The three phase filter series is intended to be used in energy
conversion inverter systems (e.g. photo voltaic and wind power),
between the inverter and the line or in motor drive systems.
The filters are optimized for geometry and power loss.
Technical specifications
Rated voltage
Rated frequency
Rated current
Leakage current
Rated temperature
Temperature range
Climate category
Voltage test
520 VAC
50-60 Hz
250 – 2500 A
< 5 mA *)
50°C
-40°C to +100°C
40/100/21
P -> P 2250 VDC (520 VAC)
P -> E 3000 VDC (520 VAC)
The FLLD3…PV series is designed according to IEC/EN 60939 and UL 1283.
*) Maximum leakage current under normal operating conditions.
If two phases are interrupted, leakage current can be much higher.
Filters without Y-capacitors have no leakage current.
Rated current
@ 50°C
(A)
250
320
400
600
800
1000
1600
2500
Part Number
FLLD3250AP-I1
FLLD3320AP-I1
FLLD3400AP-I1
FLLD3600AP-I1
FLLD3800AP-I1
FLLD31K0AP-I1
FLLD31K6AP-I1
FLLD32K5AP-I1
Power loss
@ 25°C/50Hz
(W)
15
15
25
40
50
75
130
230
Weight
(kg)
7
10
10
11
17
17
26
55
V = 520VAC
X = 520VAC without Y-capacitors
Typical insertion loss
250 to 1000 A
Asym
Sym
Asym no Y-cap
100
100
90
90
80
80
70
70
Attenuation (db)
Attenuation (db)
Sym
1600 and 2500 A
60
50
40
30
Asym no Y-cap
60
50
40
30
20
20
10
10
0
0
0.01
Asym
0.1
1
Frequency (MHz)
November 2015
10
100
0.01
0.1
1
Frequency (MHz)
10
100
KEMET EMC Filters
1
FLLD3 … PV
High current 3-phase EMC Filter
Mechanical dimensions
Z
L
Z
W
M
U
U
ØN
ØN
H
Y
ØN
K
K
I
X
J I
250 to 1000 A
J I
1600 A
2500 A
W1 W2
L1
Part Number
FLLD3250APVI1
FLLD3320APVI1
FLLD3400APVI1
FLLD3600APVI1
FLLD3800APVI1
FLLD31K0APVI1
FLLD31K6APVI1
FLLD32K5APVI1
L1
L
300
300
300
300
350
350
400
450
Ø12 (x6)
W
180
210
210
210
230
230
250
300
H
125
115
115
135
170
170
160
220
L1
120
120
120
120
145
145
170
200
W1
205
235
235
235
255
255
275
330
Dimensions in mm
W2
U
X
Y
230 55
5
20
260 60
6
25
260 60
6
25
260 60
8
25
280 60
8
40
280 60
8
40
300 60 10 60
370 100 15 80
Z
45
45
45
45
55
55
95
110
I
15
15
15
15
20
20
17
20
J
K
26
35
26
35
N
9
10.5
10.5
10.5
14
14
14
14
M
M10
M12
M12
M12
M12
M12
M12
M12
Tolerances, if not stated, according to: ISO 2768-m
Legal disclaimer notice
All product specifications, statements, information and data (collectively, the “information”)
are subject to change without notice.
products is given gratis, and we assume no obligation or liability for the advice given or
results obtained.
All information given herein is believed to be accurate and reliable, but is presented
without guarantee, warranty, or responsibility of any kind, expressed or implied.
Although we design and manufacture our products to the most stringent quality and
safety standards, given the current state of the art, isolated component failures may still
occur. Accordingly, customer applications which require a high degree of reliability or
safety should employ suitable designs or other safeguards (such as installation of
protective circuitry or redundancies) in order to ensure that failure of an electrical
component does not result in a risk of personal injury or property damage.
Statements of suitability for certain applications are based on our knowledge of typical
operating conditions for such applications, but are not intended to constitute – and we
specifically disclaim – any warranty concerning suitability for a specific customer application
or use.
This information is intended for use only by customers who have the requisite experience
and capability to determine the correct products for their applications. Any technical advice
inferred from this information or otherwise provided by us with reference to the use of our
November 2015
Although all product-related warnings, cautions and notes must be observed, the
customer should not assume that all safety measures are indicated or that other
measures may not required
KEMET EMC Filters
2
Similar pages