ETC2 NAC-06-472 High attenuation of common mode noise from 150khz to 1mhz single phase 250 vac Datasheet

Home > Product Details
NAC
Features
High attenuation of common mode noise from 150kHz to 1MHz
Single Phase 250 VAC
Selectable leakage current
Quick and easy push-down terminal. Just connect the wires, push
down and tighten the screws with a screwdriver.
DIN rail installation (option)
RoHS Compliant
Safety Agency Approvals
UL1283
CSA C22.2 No.8 (C-UL)
DIN EN133200 VDE0565 Teil 3-1
ENEC
Rated
Voltage
[V]
Rated
Current
[A]
NAC-06-472
AC 1- 250 / DC250
6
NAC-10-472
AC 1- 250 / DC250
10
NAC-16-472
AC 1- 250 / DC250
16
NAC-20-472
AC 1- 250 / DC250
20
NAC-30-472
AC 1- 250 / DC250
30
NAC-04-472
AC 1- 250 / DC250
4
Model
Ordering information
High-attenuation type of common mode noise from 150kHz to 1MHz
NAC series
NAC -10 -472
1
2
3
-O
4
1Model Name
2Rated Current
3Line to ground capacitor code:See table 1.1.
table1.1 Line to ground capacitor code
Code
681
102
222
332
472
*1
Line to ground
Leakage Current
capacitor
(Input 125/250V 60Hz)
(nominal value)
680pF
75.5 A/ 150 A max
0.13mA/ 0.25mA max
1000pF
0.25mA/ 0.5 mA max
2200pF
0.38mA/ 0.75mA max
3300pF
0.5 mA/ 1.0 mA max
4700pF
When the line to ground capacitor code is
different, the attenuation characteristic is
different.
4Options
D :DIN rail installation type
The terminal cover is retracted inside the unit
DIN rail installation type is option
* The dimensions change when the option is set.
Refer to External view.
Features of NAC series
High-attenuation type of common mode noise from 150kHz to 1MHz
- Single Phase 250 VAC
- Quick and easy push-down terminal
Just connect the wires, push down and tighten
the screws with a screwdriver
Specifications
No.
Items
NAC-04-472
1
Rated Voltage[V]
AC 1f 250 / DC250
NAC-06-472
2
Rated Current[A]
4
3
Test Voltage (Terminal-Mounting Plate)
2,500 VAC (Cutoff Current = 20mA), 1minute at room temperature and humidity
6
NAC-10-472
NAC-16-472
NAC-20-472
NAC-30-472
10
16
20
30
4
Isolation Resistance (Terminal-Mounting Plate)
500 VDC 100MW minute at room temperature and humidity
5
Leakage current 125/250V 60Hz
0.5mA/1.0mA max
6
Voltage drop
1.0V max
7
Safety agency approval temperatures
-25 to +85C (Refer to Derating Curve)
8
Operating temperature
-40 to +85C (Refer to Derating Curve)
9
Operating humidity
20 to 95%RH (Non condensing)
10
Storage temperature/humidity
-40 to +85C/20 to 95%RH (Non condensing)
11
Vibration
10 to 55Hz, 19.6m/s2 (2G), 3min. Period, 1hour each X, Y and Z axis
12
Impact
196.1m/s2 (20G), 11ms Once each X, Y and Z axis
13
Safety agency approvals
UL1283, CSA C22.2 No.8 (C-UL), DIN EN133200 VDE0565 Teil3-1, ENEC (At only AC input)
14
Case size (without projection) /Mass
53X41X92 mm (WXHXD) /300g max (Option : -D refer to external view)
Circuit Diagram
Derating Curve
Case
3
1
CY
LINE
LOAD
CY
4
2
Noise
Filter
Load Factor [%]
100
80
60
40
20
0
-40
CY : Line to ground capacitor
I-2
: Mounting Plate
-30
-20
40
50 55 60
Ambient Temperature [C]
70
80
90
NAC,NAM,NAP,NAH series
External view
This product is shipped in the following condition, because it is equipped with push-down terminals.
1The terminal cover is retracted inside the unit.
2The screws for connecting the terminals are held in the up right position.
Standard Type
92
82 ±0.5
2-f4.8
Mounting Hole
(2.5)
77
27
2-Protection Earth
8
12
53
Output
Terminal
Name Plate
15
45 ±0.5
Input
Terminal
Output
Terminal
Input
Terminal
6-M4
Mounting Plate
Terminal cover
(2)
Terminal cover
¶ Closed the terminal cover
¶ Tolerance : ±1
¶ Mass : 300g or less
41
¶ Mounting Plate : Iron (surface finishing:nickel plating) t=1.0
¶ Case : PBT
¶ Dimensions in mm
¶ Terminal block screw tighting torque M4:1.6N-m (16.9kgf-cm) max
DIN rail installation Type
92
77
(2.5)
(11)
2-Protection Earth
27
8
Input
Terminal
12
Output
Terminal
15
Input
Terminal
53
Output
Terminal
Name Plate
6-M4
Terminal cover
Mounting Plate
(2)
Terminal cover
¶ Closed the terminal cover
41
¶ Tolerance : ±1
¶ Mass : 300g or less
¶ Mounting Plate : Iron (surface finishing:nickel plating) t=1.0
¶ Case : PBT
(9)
¶ Dimensions in mm
7
¶ Terminal block screw tighting torque M4:1.6N-m (16.9kgf-cm) max
DIN rail
¡Note when installing the noise
filter on a DIN rail.
Noise
Filter
When the noise filter is grounded through the
DIN rail, the proper noise attenuation may not be
achieved.
Be sure to connect the protection earth (PE) of
the noise filter body to the earth.
I-6