Bel LDN240-48P Single phase ac input 120 / 240 vac (with switch) Datasheet

LDN240 Series are single phase DIN Rail Switching Power Supplies,
suitable for worldwide applications such as process control, heavy
duty applications, but also building automation.
These units have received excellent market approval for their high
efficiency, excellent reliability and compactness. Simple but elegant
look and ease of installation due to pluggable connectors make them
market leaders for various industrial applications.
LDN240 Series are Class I isolation devices suitable for SELV and
PELV circuitry and are designed to be mounted on DIN rail and
installed inside a protective enclosure.

Single phase AC input 120 / 240 VAC (with switch)

High efficiencies and in compact size

130% overload capability

Adjustable output voltage

Short circuit, overload and over temperature protection

RoHS Compliant

Automation

Process Control

Communication

Instrumentation Equipment
LDN240 Series
2
LDN240-12
120 / 240 VAC (270 - 345 VDC)
1
12 VDC
16 A
No ORing diode
LDN240-24
120 / 240 VAC (270 - 345 VDC)
1
24 VDC
10 A
No ORing diode
LDN240-24P
120 / 240 VAC (270 - 345 VDC)
1
24 VDC
10 A
Internal ORing diode
LDN240-48P
120 / 240 VAC (270 - 345 VDC)
1
48 VDC
5A
Internal ORing diode
LDN240-72P
120 / 240 VAC (270 - 345 VDC)
1
72 VDC
3.5 A
Internal ORing diode
Specifications are measured at 25°C, at 240 VAC / 50 Hz, typical unless otherwise stated.
Input AC Voltage Range
Rated, UL certified – settable with Input voltage selector
Operating
120 / 240 VAC
92 – 132 / 187 - 264 VAC
Input DC Voltage Range
Rated
270 - 345 VDC
Input Frequency Range
47 - 63 Hz
Vin = 120 VAC
Vin = 240 VAC
Vin = 270 VDC
Vin = 345 VDC
Input AC Current
Input DC Current
Inrush Peak Current
4.0 A
2.0 A
1.3 A
1.0 A
< 40 A
Internal Protection Fuse
Not user replaceable
Fuse 6.3AT / 250 VAC
External Protection on AC Line
It is strongly recommended to provide external surge
arresters (SPD) according to local regulations
Fuse AT 10A or MCB 10A C curve
LDN240-12
LDN240-24 / LDN240-24P
LDN240-48P
LDN240-72P
LDN240-12
LDN240-24 / LDN240-24P
LDN240-48P
LDN240-72P
LDN240-12
LDN240-24 / LDN240-24P
LDN240-48P
LDN240-72P
LDN240-12
LDN240-24 / LDN240-24P
LDN240-48P
LDN240-72P
LDN240-12
LDN240-24
LDN240-24P
LDN240-48P
LDN240-72P
LDN240-12
LDN240-24 / LDN240-24P / LDN240-48P / LDN240-72P
240 W
12 VDC (12 – 15 VDC)
24 VDC (23 – 28 VDC)
48 VDC (45 – 55 VDC)
72 A
(72 – 85 VDC)
16 A
10 A
5A
3.5 A
19 A @ Vo + 12 V / 16 A @ Vo = 15 V
13.5 A
6.8 A
4.6 A
42 A / 140 ms
35 A / 150 ms
20 A / 160 ms
14 A / 150 ms
≤ 1.5%
≤ 1%
≤ 2.5%
≤ 1.5%
≤ 1.5%
≤ 150 mVpp
≤ 100 mVpp
> 70 ms
Output Power
Rated Voltage
(Adjustable Voltage Range)
Continuous Current
Overload Limit
Short Circuit Peak Current
Load Regulation
Ripple & Noise
Hold up Time
[email protected]
LDN240 Series
3
LDN240-12
> 84%
LDN240-24
> 88%
Efficiency
LDN240-24P
> 86%
LDN240-48P
> 88%
LDN240-72P
> 88%
LDN240-12
< 36.5 W
LDN240-24
< 33 W
Dissipated Power
LDN240-24P
< 39 W
LDN240-48P
< 33 W
LDN240-72P
< 34.5 W
LDN240-12
> 18 VDC
LDN240-24 / LDN240-24P
> 33 VDC
Output Over Voltage Protection
LDN240-48P
> 68 VDC
LDN240-72P
> 100 VDC
LDN240-12 / LDN240-24
Possible with external ORing diode
Parallel Connection
LDN240-24P / LDN240-48P / LDN240-72P
Internal Oring diode

Hiccup at the overload limit with auto reset
Protections

Over temperature

Overvoltage
Green LED = DC OK
Status Signals
Dry contact (1 A / 30 V)
Note: Power rating, losses, efficiency, ripple, thermal behavior may change outside of the nominal rated input range.
UL certified up to 50°C
(Start-up type tested: - 40°C)1
Operating Temperature
- 40 to + 70°C
Storage Temperature
- 40 to + 80°C
Derating
- 5 W / °C over 50°C
Humidity
Non-condensing
5 - 95% RH
Life Time Expectation
Overvoltage Category
Pollution Degree
At 25°C ambient full load
77894 h (8.8 years)
III
2 (IEC 664-1)
4.2 kVDC
2.2 kVDC
0.75 kVDC
Protection Degree
Input to Output
Input to Ground
Output to Ground
UL508 (certified)
EN60950 (reference)
EN55022:2010 (CISPR22)
EN55011:2009 /A1:2010
EN61000-4-2:2008
EN61000-4-3:2006 /A2:2010
EN61000-4-4:2012
EN61000-4-5:2014
EN61000-4-11:2004 /A1:2010
EN60529:1989 / A:2013
Vibration sinusoidal
IEC 60068-2-6:2007
Shock
IEC 60068-2-27:2008
Isolation Voltage
Safety Standards & Approvals
Emission
EMC Standards
Immunity
1
Class A
Class A
Level 3
Level 3
Level 3
Level 3
Level 2
IP20
5-17.8 Hz: ±1.6 mm; 17.8-500 Hz:
2 g 2 Hours / axis (X,Y,Z)
30 g 6 ms, 20 g 11 ms;
3 bumps / direction, 18 bumps total
Possible with load derating.
Weight
750 g
Dimensions (W x D x H)
63 x 140 x 117 mm
Mounting Rail
IEC 60715/H15/TH35-7.5(-15)
Connection Terminals
Screw type pluggable (24 - 12 AWG)
Case Material
Aluminum
2.5 mm²
Europe, Middle East
+353 61 225 977
North America
+1 408 785 5200
© 2016 Bel Power Solutions & Protection
BCD.00717_AA
Asia-Pacific
+86 755 298 85888
LDN240 Series
4
Figure 1. Mechanical Drawing
1
AC/DC input
2
4
DC output (load)
Diagnostic Output
(dry contact, NC output OK)
Green LED: Output OK
5
Output voltage adjustment
6
Input voltage selector
3
INPUT CONNECTION
Single phase:
L = Line
N = Neutral
= Earth ground
DC:
L = +/- / N = -/+
OUTPUT CONNECTION
+ = Positive DC
- = Negative DC
Dry contact = NC
/
= Earth ground
NUCLEAR AND MEDICAL APPLICATIONS - Products are not designed or intended for use as critical components in life support systems,
equipment used in hazardous environments, or nuclear control systems.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the
date manufactured. Specifications are subject to change without notice.