PHOENIX IEG45-3LA40021 Voltage indication module Datasheet

IEG 45-3LA/400/21
Voltage indication module
INTERFACE
Data sheet
104160_en_00
1
© PHOENIX CONTACT - 11/2009
Description
Correct invoicing on the basis of a measuring instrument
can only be ensured if the three phases L1, L2, and L3 are
available.
1.1
Function
L1 failure:
Glow lamp 1 does not light up,
relay drops
L2 failure:
IEG 45-3LA/400/21 voltage indication modules are used for
monitoring, for example, on a tariff changing board. These
modules indicate all three phases with high-accuracy
reading, even in case of reverse voltages.
Glow lamp 2 does not light up,
relay drops
L3 failure:
Glow lamp 3 does not light up,
relay drops
These modules also have a floating PDT contact, thereby
offering the convenience of voltage monitoring through
remote querying.
Failure of two
phase conductors: No glow lamps light up,
relay drops
14 12
L1
L2
L3
11
Figure 1
Make sure you always use the latest documentation.
It can be downloaded at www.phoenixcontact.net/download.
This data sheet is valid for all products listed on the following page:
Circuit diagram
IEG 45-3LA/400/21
2
Ordering data
Description
Type
Order No.
Pcs./Pkt.
Voltage indication module, with relay contact output, SPDT, 400 V AC
operating voltage
IEG 45-3LA/400/21
2963268
5
3
Technical data
General data
Ambient temperature range
-20°C … +40°C
Rated insulation voltage according to EN 50178
300 V
Pollution degree according to EN 50178
2
Surge voltage category according to EN 50178
3, basic insulation
Mounting position
Any
Installation
Can be aligned without spacing
Width
45 mm
Height
47.5 mm
Length
75 mm
Connection data
Conductor cross-section, solid
0.2 mm² ... 4 mm²
Conductor cross-section, stranded
0.2 mm² ... 4 mm²
Conductor cross-section, AWG
24 - 12
Stripping length
8 mm
Connection method
Screw connection
Input
Operating voltage UN (phase conductor/phase conductor)
400 V AC ±10%
Operating voltage range
0.93 … 1.1 x UN (at 20°C)
Indication range
≥ 100 V AC
Indication elements
Glow lamp (green cover)
Current consumption of each light indicator at UN
5.3 mA
5.3 mA
7.9 mA
L1
L2
L3
Relay output
Contact type
Single contact, SPDT
Contact material
AgSnO
Maximum switching voltage
250 V AC/DC
Limiting continuous current
6A
Output fuse
6.3 A (fast-blow)
Maximum interrupting rating (ohmic load)
144 W
1500 VA
At 24 V DC
At 250 V AC
2 x 107 cycles, approximately
Mechanical service life
Conformance/approvals
Conformance
CE-compliant
Conformance with EMC Directive 2004/108/EC
Noise immunity according to
EN 61000-6-2
Noise emission according to
EN 61000-6-4
Conformance with Low Voltage Directive (LVD) 2006/95/EC