PHOENIX EMD-BL-C-10 Electronic monitoring relay for overcurrent Datasheet

EMD-BL-C-10(-PT)
Electronic monitoring relay for overcurrent and undercurrent monitoring of alternating current in
single-phase networks
Data sheet
105670_en_01
1
© PHOENIX CONTACT - 2016-05-03
Description
Safety and system availability requirements are constantly on
the increase – across all industries. Processes are becoming
more and more complex, not only in machine building and the
chemical industry but also in building technology. The demands placed on energy technology are also constantly on
the rise.
It is only by continuously monitoring key network and system
parameters that error-free and therefore cost-effective operation can be achieved. Electronic monitoring relays from the
EMD series are available for a wide range of monitoring tasks
so that the consequences of errors can be avoided or kept within limits.
The operating states are signaled via color LEDs and any errors that occur can be sent to a controller via a floating contact
or can shut down a section of the system. All device versions
are equipped with response delays so that measured values
outside the set monitoring range can be briefly tolerated.
Features
–
–
–
–
–
–
Over/undercurrent monitoring
Window function
Adjustable threshold values
Adjustable response delay
Two adjustable monitoring ranges up to 5 A/10 A
One PDT
WARNING: Risk of electric shock
Never carry out work when voltage is present.
Make sure you always use the latest documentation.
It can be downloaded from the product at phoenixcontact.net/products.
EMD-BL-C-10(-PT)
2
Ordering data
Description
Type
Order No.
Pcs./Pkt.
Electronic monitoring relay for overcurrent and undercurrent monitoring of
alternating current in single-phase networks
EMD-BL-C-10-PT
2903522
1
Electronic monitoring relay for overcurrent and undercurrent monitoring of
alternating current in single-phase networks
EMD-BL-C-10
2903521
1
3
Technical data
Input data
Input name
Measuring input
Measured value
AC sine (48 Hz ... 63 Hz)
Input current range
0 A ... 5 A
0 A ... 10 A
Configurable via rotary switches
Overload capacity
13 A AC
Input resistance current input
3 mΩ
Min. setting range
5 % ... 95 % (From IN)
Max. setting range
10 % ... 100 % (From IN)
Maximum temperature coefficient
≤ 0.05 %
Setting range for response delay
0.1 s ... 10 s
Function
Overcurrent, undercurrent, window
Basic accuracy
≤ 5 % (of the nominal value)
Setting accuracy
± 5 % (of the nominal value)
Repeat accuracy
≤2%
Recovery time
> 500 ms
Output data
Contact type
1 floating PDT
Maximum switching voltage
250 V AC (in acc. with IEC 60664-1)
Interrupting rating (ohmic load) max.
1250 VA (5 A/250 V AC)
Output fuse
5 A (fast-blow)
Supply
Supply voltage
230 V AC ±15 %
Frequency range
48 Hz ... 63 Hz
Nominal power consumption
5 VA (0.8 W)
105670_en_01
PHOENIX CONTACT
2
EMD-BL-C-10(-PT)
General data
Mains type
1-phase
Operating voltage display
Green LED
Status display
Yellow LED
Indication
Red LED
Mechanical service life
15 x 106 cycles
Service life, electrical
1 x 105 cycles
Switching frequency
≤ 6 (per minute at 1250 VA ohmic load)
Operating mode
100% operating factor
Degree of protection
IP40 (housing) / IP20 (connection terminal blocks)
Degree of pollution
2 (DIN EN 60947-5-1)
Overvoltage category
III, 300 V basic insulation (DIN EN 60947-5-1)
Rated insulation voltage
300 V (Supply circuit (DIN EN 60947-5-1))
Mounting
on standard DIN rail NS 35 in accordance with EN 60715
Mounting position
any
Width
17.5 mm
Height
88 mm
Depth
65.5 mm
Type of housing
Polyamide PA66, self-extinguishing
Color
gray
Connection data
Push-in connection
Screw connection
Conductor cross section, solid
0.14 mm² ... 2.5 mm²
0.5 mm² ... 2.5 mm²
Conductor cross section, flexible
0.14 mm² ... 2.5 mm²
0.5 mm² ... 2.5 mm²
AWG
26 ... 14
20 ... 14
Stripping length
8 mm
8 mm
Tightening torque
1 Nm
Ambient conditions
Ambient temperature (operation)
-25 °C ... 55 °C
Ambient temperature (storage/transport)
-25 °C ... 70 °C
Permissible humidity (operation)
15 % ... 85 %
Climatic class
3K3 (in acc. with EN 60721)
Conformance / approvals
Conformance
CE-compliant
UL, USA / Canada

UL, USA / Canada
UL/C-UL listed UL 508
Conformance with EMC Directive 2004/108/EC (valid until April 19, 2016) / 2014/30/EU (valid from April 20, 2016)
Noise immunity according to
EN 61000-6-2
Noise emission according to
EN 61000-6-3
Conformance with Low Voltage Directive 2006/95/EC (valid until April 19, 2016) / 2014/35/EU (valid from April 20, 2016)
Low voltage switchgear according to
105670_en_01
EN 60947-5-1
PHOENIX CONTACT
3
EMD-BL-C-10(-PT)
4
Block diagram
16 18
Li
Lk
N
15
U = 230 V AC
5
Safety notes
WARNING: Risk of electric shock
Never carry out work when voltage is present.
6
Structure
Li
Lk
9
N
3
2
1
Delay
2
4
10
s
6
10 8
20
40
60
0%
5 80
20
40
95
% 60
R O 80
U
W
W
5A
U O 10A
8
7
LED: output relay R
LED: minimum threshold value (Min)
LED: maximum threshold value (Max)
LED: supply U
"DELAY" potentiometer: Response delay
"MAX" potentiometer: Upper threshold value
"MIN" potentiometer: Lower threshold value
Rotary switch for function selection
Snap-on foot for DIN rail mounting
10
EMD-BL-C-10-PT
Min
4
Max
U 0.1
1
2
3
4
5
6
7
8
9
7
6
5
Installation
WARNING: Risk of electric shock
Never carry out work when voltage is present.
The module can be snapped onto all 35 mm DIN rails according to EN 60715.
Supply voltage in the range of 230 V AC ±15%
105670_en_01
PHOENIX CONTACT
4
EMD-BL-C-10(-PT)
8
Diagnostics
The LEDs indicate the following error states:
"U" LED (Green)
–
LED ON: Supply voltage present
"MIN" and "MAX" LEDs (Red)
–
–
LED flashing: indicates response delay for the corresponding threshold
LED ON: indicates error for the corresponding threshold
“R” LED (yellow)
–
–
LED ON: Output relay has picked up
LED OFF: Output relay has dropped out
9
Connection examples
~1
L
N
Lk
Li
N
15
R
16 18
15
16
10
18
Function
The "FUNCTION" rotary switch is used to set the desired function:
– O = Overcurrent monitoring (OVER)
– U = Undercurrent monitoring (UNDER)
– W = Monitoring of the area between thresholds MIN and
MAX (window function) (WIN)
105670_en_01
PHOENIX CONTACT
5
EMD-BL-C-10(-PT)
Overcurrent Monitoring (OVER)
LED U
LED Max
LED Min
If the measured current exceeds the value set at the
“MAX” controller, the set response delay (D = DELAY) starts
(red “MAX” LED flashes).
After the delay time has elapsed (red “MAX” LED is ON), output relay “R” drops out (yellow “R” LED is OFF). If the measured current falls below the value set at the “MIN” controller
(red “MAX” LED is OFF), output relay “R” picks up again
(yellow “R” LED is ON).
Max
Min
D
>D
D
Undercurrent Monitoring (UNDER)
LED U
LED Max
LED Min
If the measured current falls below the value set at the
“MIN” controller, the set response delay (D = DELAY) starts
(red “MIN” LED flashes). After the delay time has elapsed
(red “MIN” LED is ON), output relay “R” drops out
(yellow “R” LED is OFF).
If the measured current exceeds the value set at the “MAX”
controller, output relay “R” picks up again
(yellow “R” LED is ON).
Max
Min
D
>D
D
Window Function (WIN)
LED U
LED Max
LED Min
Max
Min
D
105670_en_01
>D
D
Output relay “R” picks up (yellow “R” LED is ON) if the measured current exceeds the value set at the “MIN” controller. If
the measured current exceeds the value set at the
“MAX” controller, the set response delay (D = DELAY) starts
(red “MAX” LED flashes). After the delay time has elapsed
(red “MAX” LED is ON), output relay “R” drops out
(yellow “R” LED is OFF).
Output relay “R” picks up again (yellow “R” LED is ON) if the
measured current falls below the maximum value again
(red “MAX” LED is OFF). If the measured current falls below
the value set at the “MIN” controller, the set response delay
(D = DELAY) starts (red “MIN” LED flashes). After the delay
time has elapsed (red “MIN” LED is ON), output relay “R”
drops out (yellow “R” LED is OFF).
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
phoenixcontact.com