AIMTEC AMEC40-5DMAZ 40 watt | ac-dc / dc-dc converter Datasheet

Click on Series name for product info on aimtec.com
Series AMEC40-MAZ
40 Watt | AC-DC / DC-DC Converter
FEATURES:




Connectors on input/output
Operating temperature: -40°C to +85°C
Over load, Over voltage, Short circuit protection
Universal Input: 90-264VAC, 47-440Hz, or 130-370VDC




Energy star compliant
4000VAC I/O isolation
Low ripple and noise
CE, cULus, CB approvals
CB
Models
Single output
Model
AMEC40-3.3SMAZ
AMEC40-5SMAZ
AMEC40-12SMAZ
AMEC40-15SMAZ
AMEC40-24SMAZ
Input Voltage
(VAC/Hz)
Input Voltage
(VDC)
90-264/47-440
90-264/47-440
90-264/47-440
90-264/47-440
90-264/47-440
130-370
130-370
130-370
130-370
130-370
Input Voltage
(VAC/Hz)
Input Voltage
(VDC)
Output Voltage
(V)
Output Current
max
(A)
3.3
5
12
15
24
8
8
3.33
2.66
1.66
Efficiency
(%)
78
82
84
83
82
Models
Dual output
Model
Output Voltage
(V)
Output Current
max
(A)
Efficiency
(%)
AMEC40-5DMAZ
90-264/47-440
130-370
±5
±4
80
AMEC40-12DMAZ
90-264/47-440
130-370
±12
±1.66
85
AMEC40-15DMAZ
90-264/47-440
130-370
±15
±1.33
82
AMEC40-24DMAZ
90-264/47-440
130-370
±24
±0.835
77
NOTE: All specifications in this datasheet are measured at an ambient temperature of 25°C, humidity<75%, nominal input voltage and at
rated output load unless otherwise specified.
Input Specifications
Parameters
Conditions
Typical
Maximum
115 VAC
230 VAC
115 VAC
230 VAC





3.15
൑0.5
117
1000
530
25
50
150
Conditions
Typical
Maximum
(LL-HL)
0-100% load single
0-100% load dual
25% load - 1st out, 100% load – 2nd out
Depending of the model
25% load Step
20MHz bandwidth
115VAC
±2
±0.5
±1
±2
±5
470-23 000
±2
50
29
0
Current
Inrush current <2ms
Leakage current
External fuse
Input dissipation
Start-up time
Recommended slow blow type
No load
Units
mA
A
µA
A
W
ms
Output Specifications
Parameters
Voltage accuracy
Line regulation
Load regulation
Cross regulation
Maximum Capacitive load
Transient response deviation
Ripple & Noise*
Hold-up time (min)
Minimum Load Current
Units
%
%
%
%
µF
% of Vout
mV p-p
ms
% of Max
*Ripple & Noise measured with 0.1μF M/C and 1μF E/C
www.aimtec.com
F 052e R7.R
Tel: +1 514 620 2722
1 of 5
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only
Series AMEC40-MAZ
40 Watt | AC-DC / DC-DC Converter
Isolation Specifications
Parameters
Conditions
Tested I/O voltage
Isolation Resistance
Typical
60 sec
Rated
Units
4000
VAC
MΩ
>1000
General Specifications
Parameters
Conditions
Switching frequency
Protection class
Over current protection
Over voltage protection
Short circuit protection
Short Circuit restart
Operating temperature
Maximum case temperature
Storage temperature
Temperature coefficient
Cooling
Humidity
Case material
Weight
Dimensions (L X H X W)
Typical
47
Class II
110
Zener diode clamp
Hiccup mode, indefinite
Auto recovery
-40 - +85
Auto recovery
With derating above 50ºC
Maximum
KHz
140
110
%
%
oC
oC
100
oC
% / oC
-40 to +100
0.02
Free air convection
Non condensing
MTBF
Units
95
% RH
Metal
270
4.92 x 2.56 x 1.38 inches / 125.00 x 65.00 x 35.00 mm
> 800,000 hrs (MIL-HDBK -217F, t=+25 oC)/Full Load
> 200,000 hrs (MIL-HDBK -217F, t=at highest operating temperature)/Full Load
g
Environment Approval
Test
Shock
Vibration
Parameters
Wave form
Acceleration amplitude
Bump duration
Converter operation
Number of bumps
Test mode
Displacement
Acceleration
Converter operation
Conditions
Half sine wave
5gn
30 ms
Before and after test, body mounted (on chassis)
18 (3 in each direction for every axis)
Sweep sine, 10-100Hz, speed 0.05Hz/s
1 mm
3g, 3 loops 30min one cycle, 3h total, every axis tested
Before and after test, body mounted (on chassis)
Safety Specifications
Parameters
Agency approvals
cULus, CE, CB
IEC\EN\UL 60601-1, 2 x MOOP, CSA-C22.2 No. 601.1M90
EN 60950-1:2006+A11:2009
EN55011, class B
IEC/EN 61000-3-2, Class A
IEC/EN 61000-3-3, (EN60555-3)
IEC 61000-4-2 Level 3
IEC 61000-4-3 Level 2
IEC 61000-4-4 Level 3
IEC 61000-4-5 Level 2
IEC 61000-4-6 Level 2
IEC 61000-4-8 Level 2
IEC 61000-4-11
Medical Electrical Equipment
Standards
www.aimtec.com
F 052e R7.R
Information technology Equipment
EMI - Conducted and radiated emission
Harmonic Current Emissions
Voltage fluctuations and flicker
Electrostatic Discharge Immunity
RF, Electromagnetic Field Immunity
Electrical Fast Transient/Burst Immunity
Surge Immunity
RF, Conducted Disturbance Immunity
Power frequency Magnetic Field Immunity
Voltage dips, Short Interruptions Immunity
Tel: +1 514 620 2722
2 of 5
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only
Series AMEC40-MAZ
40 Watt | AC-DC / DC-DC Converter
Pin Out Specifications
Pin
Single
Dual
1
2
3
4
5
6
AC Input (L)
AC Input (N)
+V Output
-V Output
N.C.
N.C.
AC Input (L)
AC Input (N)
+V Output
Common
Common
-V Output
N.C.: Not Connected
Dimensions
www.aimtec.com
F 052e R7.R
Tel: +1 514 620 2722
3 of 5
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only
Series AMEC40-MAZ
40 Watt | AC-DC / DC-DC Converter
Optional DIN Rail Bracket
Derating
Free Air Convection
50º C
Output Power (%)
100
80
Safe Operating Area
60
40
20
0
- 40
- 20
0
20
40
60
80
85
100
Ambient Temperature º C
www.aimtec.com
F 052e R7.R
Tel: +1 514 620 2722
4 of 5
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only
Series AMEC40-MAZ
40 Watt | AC-DC / DC-DC Converter
Earth/Ground Connection EMC EN55022 class B compliant Application circuit
L1
35mH
ASE2501V‐G
+Vout
L
90-264VAC
CX1
0.6uF
CX2
0.6uF
AMExw40‐MAZ
N
-Vout
The Application circuit is EMC compliant for any type of Earth/Ground connection: Input Ground connection, Output Ground connection as
shown or both sides, which is not recommended if the product Isolation is used as a Safety feature.
NOTE: 1. Datasheets are updated as needed and as such, specifications are subject to change without notice. Once printed or downloaded, datasheets are no longer controlled
by Aimtec; refer to www.aimtec.com for the most current product specifications. 2. Product labels shown, including safety agency certifications on labels, may vary based on the
date manufactured. 3. Mechanical drawings and specifications are for reference only. 4. All specifications are measured at an ambient temperature of 25°C, humidity<75%,
nominal input voltage and at rated output load unless otherwise specified. 5. Aimtec may not have conducted destructive testing or chemical analysis on all internal components
and chemicals at the time of publishing this document. CAS numbers and other limited information are considered proprietary and may not be available for release. 6. This
product is not designed for use in critical life support systems, equipment used in hazardous environments, nuclear control systems or other such applications which necessitate
specific safety and regulatory standards other the ones listed in this datasheet. 7. Warranty is in accordance with Aimtec’s standard Terms of Sale available at www.aimtec.com.
www.aimtec.com
F 052e R7.R
Tel: +1 514 620 2722
5 of 5
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only
Similar pages