LEM AV100-50 Voltage transducer av 100 sery Datasheet

Voltage Transducer AV100 Series
VPN = 50...1500 V
For the electronic measurement of voltages : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high voltage)
and the secondary circuit (electronic circuit).
Electrical data
Primary nominal
R.m.s or DC voltage
V̂P
RM
ISN
VC
Ic
Ve
Primary Voltage R.m.s. voltage for AC
Type
1)
measuring range
isolation test
(50 Hz/1min)
VPN (V)
VPmax (V)
Vd (kV)
50
± 75
3.3
AV 100-50
125
± 187.5
3.3
AV 100-125
150
± 225
3.3
AV 100-150
250
± 375
3.3
AV 100-250
500
± 750
3.3
AV 100-500
750
± 1125
4.3
AV 100-750
1000
± 1500
5.5
AV 100-1000
1500
± 2250
6.5
AV 100-1500
Not measurable overload
2 x VPmax (1s/h)
VDC
Measuring resistance
RM min
RM max
@ VC=11.4V
0
47
Ω
@ VC=22.8V
0
184
Ω
Secondary nominal r.m.s. current
50
mA
Supply voltage (± 5 %)
DC ± 12 .. 24
V
Current consumption
50+IS
mA
Max Common mode voltage
U HT+ + U HT- ≤ 4.2 k V DC
and
UHT+ - U HT-≤ VPMAX
R.m.s. voltage for partial discharge
1.1 2)
kV
extinction @ 10pC
2.2 3)
kV
Accuracy - Dynamic performance data
XG
XG
XG
ε
L
IO
tr
f
Overall Accuracy @ VPN , TA = + 25°C
Overall Accuracy @ VPN , TA = - 25 .. + 70°C
Overall Accuracy @ VPN , TA = - 40 .. + 85°C
Linearity @ TA = 25°C
Offset current @ VP = 0, TA = 25°C
Response time @ 10 % of VPmax
Frequency bandwidth (- 3 dB)
± 0.7
%
± 1.5
%
± 1.7
%
< 0.1
%
± 0.15
mA
Between 10 and 13 µs
DC .. 13
kHz
Features
• Insulated plastic case recognized
according to UL 94-V0.
• Included primary resistor
Advantages
•
•
•
•
•
•
•
Low power
Excellent accuracy
Very good linearity
Low thermal drift
Low response time
High bandwidth
High immunity to external
interference
• Low disturbance in common mode.
Applications
• AC variable speed drives and servo
motor drives
• Static converters for DC motor drives
• Battery supplied applications
• Uninterruptible Power Supplies
(UPS)
• Power supplies for welding
applications .
General data
TA
TS
m
Ambient operating temperature
Ambient storage temperature
Mass
Standards
- 40 .. + 85
- 50 .. + 90
375
EN 50155
EN 50124-1
NFF16101/2
°C
°C
g
Notes : 1) Between primary and secondary
2)
For models AV 100-50 to 750
3)
For models AV 100-1000 & AV 100-1500
030523/4
LEM Components
Dimensions AV100 Series (in mm. 1 mm = 0.0394 inch)
Front view
Left view
HT+
HT+
M
-
Secondary terminals
Terminal + : Supply voltage +12 .. 24 V
Terminal M : Measure
Terminal - : Supply voltage - 12 .. 24V
Connection
AV100
AV100
TOP view
Mechanical characteristics
Remarks
• General tolerance
• Fastening
• IS is positive when VP is applied on terminal +HT.
• This is a standard model. For different versions, please
± 1 mm
2 holes ∅ 6.5 mm
Distance between holes axes :
124mm
• Fastening & connection of primary
2 x M5
• Fastening & connection of secondary 3 x M5 or 3 Faston
6.35 x 0.8mm
Output connections must be made with screened cables
• Fastening torque:
2.2 Nm
contact us.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.