GENERAL C8103

Description:
A.
Tinned Copper conductor, FEP Insulation, twisted pairs, overall foil shield and PVDF Jacketed Plenum Cable.
Construction:
1.0
Primaries:
1.1
1.2
Conductor:
AWG
Stranding
Nom. Dia
Insulation:
Material
Nom. thickness
Nom. OD
22 AWG
7/30 Tinned Copper;
.030"
FEP
.006”
.042"
2.0
Pair construction:
2.1
No. of Pairs
2.2
Pair Color Code:
Two insulated conductors twisted together
1
Black & Red
3.0
4.0
Overall shield:
3.1
Separator:
3.2
Shield:
3.3
Drain Wire:
Jacket
Material:
Polyester tape
Aluminum/Polyester Tape; 100% coverage; (Aluminum Side out)
22 AWG Stranded Tinned Copper
PVDF
Nom. wall:
.014”
Color:
TBD
5.0
Overall Diameter of Cable Nom.
.120”
6.0
Marking:
Characteristics:
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
Conductor DC Resistance @20C Max. (Ohm):
Capacitance between conductors Nom. (pF/ft):
Capacitance Cond. To other Cond.& Shield Nom. (pF/ft):
Inductance Nom. (µH/ft):
Shield Resistance Nom.(Ohms/1000’):
Velocity of propagation Nom.:
Characteristic Impedance Nom. (Ohms):
Operating Voltage Nom.:
Continuous Operating Temp:
Min. Bend Radius (inches):
Max. Pulling Tension Lbs:
C.
Approvals:
UL –CMP ; C(UL) CMP
R
E
V
DATE
B.
Surface Print:
GENERAL CABLE (F) C8103 2C 22 AWG SHIELDED CMP (UL) C(UL) ---- ROHS
AAAAA*
* Indicates Shop Order number
16
35
65
.15
12
69
48
300 V
-40C to + 150C
1.2
25.0
CHANGE DETAIL
General Cable
20 Forge Park, Franklin, Ma 02038
Phone: 508-541-7100 Fax: 508-541-8122
Title:
C8103
Description:
1 PR 22 AWG Shielded Plenum Cable
Created By:
A 06/30/09
Initial Release -DB
Final Approval:
VM 6/29/09
PAGE 1 of 1