TTC-1000 Transformer Temperature Controller Instruction & Operation Manual One or Two Probe Four Output Advanced Power Technologies 215 State Route 10, Building 2 Randolph, NJ 07869 Phone: (973) 328-3300 Fax: (973) 328-0666 Website: advpowertech.com e-mail: [email protected] V4.42, December 16, 2007 Table of Contents 1 INTRODUCTION ...........................................................................................1 2 PRODUCT DESCRIPTION............................................................................3 3 4 2.1 Controls & Indicators ..............................................................................3 2.2 Connection Overview Small Form Panel Unit.........................................5 2.3 Connection Overview Large Form Panel Unit.........................................6 2.4 Connections Overview - NEMA Enclosure .............................................7 2.5 Specifications .........................................................................................8 2.6 Part Number Details .............................................................................10 INSTALLATION and CONNECTIONS.........................................................11 3.1 Mounting...............................................................................................11 3.2 Power Hookup ......................................................................................12 3.3 Temperature Probes.............................................................................13 3.3.1 TTC-PROBE-01 Installation ..........................................................13 3.3.2 TTC-PROBE-11 Installation ..........................................................14 3.3.3 Magnetic Mount Probe (TTC-PROBE-02) Installation ...................15 3.3.4 Probe Lead Connections ...............................................................16 3.4 Auxiliary CT Input for Calculated Winding Temperature.......................18 3.5 Cooling Control and Condition Alarm Connections...............................18 3.6 Unit Alarm Connections ........................................................................20 3.7 Telemetry Connections.........................................................................20 3.7.1 RS-232 Terminal Connections ......................................................20 3.7.2 Analog Outputs..............................................................................21 3.7.3 RS-485 for DNP3.0 Communications ............................................22 3.7.4 Fiber Optic Interface for DNP3.0 Communications........................23 3.8 Optically Isolated Inputs........................................................................24 3.9 Heater Connections..............................................................................25 SETTINGS...................................................................................................26 4.1 Programming Settings Through Front Panel ........................................26 4.2 Programming Settings Through a PC...................................................27 4.3 Settings for Calculated Winding Temperature ......................................29 4.3.1 CT RATIO......................................................................................30 i V4.42, December 16, 2007 Table of Contents 4.3.2 Rated Load....................................................................................30 4.3.3 Hot Spot Rise over Top Oil............................................................31 4.3.4 Winding Rise Time Constant .........................................................32 4.3.5 Calculated Winding Exponent Setting ...........................................32 4.3.6 Checking Winding Temperature ....................................................33 4.4 Setting Probe Names ...........................................................................34 4.5 Temperature Set Points........................................................................35 4.5.1 Setting Liquid Pickup and Drop Out Temperatures .......................37 4.5.2 Setting Calculated Winding Pickup and Drop Out Temperatures ..38 4.6 LTC Condition Monitoring .....................................................................39 4.6.1 LTCDIFF Temperature Monitoring.................................................40 4.6.2 LTCDIFF Rate of Rise Monitoring .................................................43 4.7 Load Pickup Set Points.........................................................................45 4.7.1 Setting Load Pickup Set Point .......................................................46 4.7.2 Setting Load Pickup Timer ............................................................47 4.8 Optically Isolated Input Settings ...........................................................48 4.9 Programmable Logic Settings...............................................................50 4.9.1 Assigning Liquid Temperature Set Points......................................51 4.9.2 Assigning Winding Temperature Set Points ..................................53 4.9.3 Assigning LTCDIFF for LTC Condition Monitoring Alarm ..............54 4.9.4 Assigning Load Pickup Set Points.................................................56 4.9.5 Assigning IN1 and IN2...................................................................57 4.9.6 Assigning OUT1, OUT2, OUT3 and OUT4....................................58 4.9.7 Time Set Points .............................................................................59 4.9.8 Setting Output Timers....................................................................61 4.9.9 Setting Output Invert......................................................................62 4.9.10 Application Examples ....................................................................63 4.10 Setting Output Control With Alarm........................................................66 4.11 Alternate Fan Banks .............................................................................67 4.12 Auto and Manual Control ......................................................................68 4.13 Setting Control of Unit Alarm ................................................................69 ii V4.42, December 16, 2007 Table of Contents 4.13.1 Device Alarm Setting .....................................................................70 4.13.2 Temperature Probe Alarm Setting.................................................70 4.13.3 Manual Mode Alarm Setting ..........................................................71 4.13.4 Winding Circuit Alarm Setting........................................................71 4.14 5 4.14.1 Setting Time and Date Via the Front Panel ...................................73 4.14.2 Setting Time and Date Via the PC.................................................74 4.15 Setting Password..................................................................................74 4.16 Setting Unit ID ......................................................................................75 TELEMETRY OPTIONS ..............................................................................76 5.1 Setting the Analog Output Range ..................................................77 5.1.2 Setting the Analog Source.............................................................78 5.1.3 Enabling Negative Scaling.............................................................79 8 DNP3.0 .................................................................................................79 5.2.1 Setting BAUD Rate........................................................................82 5.2.2 Setting NODE Address..................................................................82 5.2.3 Setting Remote Blocking ...............................................................83 5.3 7 Analog Outputs.....................................................................................76 5.1.1 5.2 6 Setting Date and Time ..........................................................................72 Telemetry Via RS232............................................................................83 VIEW TEMPERATURES .............................................................................85 6.1 Single Probe .........................................................................................85 6.2 Dual Probe............................................................................................86 6.3 Single Probe With Calculated Winding .................................................87 6.4 Dual Probe With Calculated Winding....................................................88 6.5 Reset Min/Max......................................................................................89 VIEW SETTINGS.........................................................................................90 7.1 View Settings Via Front Panel ..............................................................90 7.2 View Settings Via PC............................................................................90 STATUS ......................................................................................................93 8.1 View Status Via Front Panel .................................................................93 8.2 View Status Via PC ..............................................................................93 iii V4.42, December 16, 2007 Table of Contents 9 SETTING FILES ..........................................................................................95 9.1 Upload Setting Files .............................................................................95 9.1.1 Upload Settings Using HyperTerminal...........................................95 9.1.2 Upload Settings Using HyperAccess .............................................96 9.2 Download Setting Files .........................................................................97 9.2.1 Download Settings Using HyperTerminal ......................................97 9.2.2 Download Settings Using HyperAccess ........................................98 10 DATA LOGGING......................................................................................99 10.1 Data Storage ........................................................................................99 10.2 Data Points .........................................................................................100 10.3 Setting the Time Base ........................................................................100 10.4 Selecting Data Points .........................................................................100 10.4.1 Add or Delete P1 From Log.........................................................101 10.4.2 Add or Delete P2 From Log.........................................................101 10.4.3 Add or Delete Calculated Winding From Log ..............................102 10.4.4 Add or Delete Load From Log .....................................................102 10.5 Viewing the Data Log .........................................................................103 10.6 Saving the Data Log as a Text File Using HyperTerminal ..................104 10.7 Import Data Log as a Comma Delimited Text File Using HyperAccess 104 10.8 Import to Excel....................................................................................105 11 DOWNLOAD PROGRAM UPDATES.....................................................109 11.1 Download Firmware Using HyperTerminal .........................................110 11.2 Download Firmware HyperAccess......................................................110 12 Front Panel Setting SheetsThe following worksheet is a comprehensive list of all the settings programmable through the Front Panel interface and possible settings. A blank space is provided to write-in the desired setting: .....112 13 PC Setting Sheets..................................................................................125 14 DNP3.0 PROFILE DOCUMENT.............................................................139 iv V4.42, December 16, 2007 Table of Figures Figure 2.1: Controls and Indicators – all versions .................................................3 Figure 2.2: Small Panel Mount Connection Overview...........................................5 Figure 2.3: Large Panel Mount Connection Overview...........................................6 Figure 2.4: NEMA Mount Connection Overview...................................................7 Figure 3.1: Mounting Bracket..............................................................................11 Figure 3.2: Power Connections..........................................................................12 Figure 3.3: PROBE-01 Installation ......................................................................13 Figure 3.4 PROBE-11 Installation .......................................................................14 Figure 3.5: Magnetic Mount, Application of Thermal Compound ........................15 Figure 3.6: Magnetic Mount Views......................................................................16 Figure 3.7: Probe Connections ...........................................................................17 Figure 3.8: Temperature Probe Shield Grounding ..............................................17 Figure 3.9: Split Core CT Installation ..................................................................18 Figure 3.10: Auxiliary CT Connections................................................................18 Figure 3.11: Connections to Relay Outputs ........................................................19 Figure 3.12: Connections to Unit Alarm ..............................................................20 Figure 3.13: Connections to Analog Outputs ......................................................21 Figure 3.14: Panel Mount and NEMA 4 RS-485 Connections ............................23 Figure 3.15: Outline of Fiber Optic Interface .......................................................24 Figure 3.16: Optically Isolated Input Connections...............................................25 Figure 4.1: Over Temperature Operation............................................................36 Figure 4.2: Under Temp Operation .....................................................................36 Figure 4.3: LTC Differential Set Point Operation.................................................40 Figure 4.4: LTCDIFF Rate of Rise Method .........................................................43 Figure 4.5: Load Pickup Set Point Operation......................................................45 Figure 4.6: Input Set for LEVEL ..........................................................................48 Figure 4.7: Input Set for PULSE..........................................................................49 Table 4.1: Operands ...........................................................................................50 Table 10. 1: Maximum Records ..........................................................................99 v V4.42, December 16, 2007 Warranty All new products sold to customers are warranted against defects in design, materials, and workmanship for the life of their use to the original end user. If it is determined that the new product defect is covered under this warranty, Advanced Power Technologies, LLC (the “Company”) will repair, replace, or substitute an identical unit at its own discretion to the customer at no charge. The Company requires the customer to ship the unit back to the factory for diagnosis under all circumstances. In such event, the Company may, at its own discretion, decide to provide the customer with a substitute unit which may be sent to the customer either from the Company’s factory or from an authorized representative or distributor from their inventory. All expenses related to the shipment of defective units back to the Company or the provision of a substitute unit to the customer are the responsibility of the customer. This expense may include, but is not limited to, freight, insurance, Customs clearance, and duties. All expenses related to the shipment of repaired units back to customers (or the provision of a new unit to the customer) will be borne by the Company. Product Upgrade Policy From time to time, the Company makes product upgrades to add or enhance the performance of the products. Customers of a particular product being issued an upgrade will be notified either by the Company directly or through its authorized representatives or distributors. Customers who have purchased an annual upgrade policy will receive all upgrades during the calendar year free of charge. Customers who did not purchase the annual upgrade policy may purchase each unit upgrade individually. The annual upgrade policy can be purchased at any time. Regardless of whether the upgrade policy is purchased, the Company will make reasonable efforts to notify all customers of all available upgrades. Equipment Repair and Warranty Repair costs of products not covered under this warranty are paid for by customers. Customers are responsible for the cost of shipping the products to the Company located at: 215 State Route 10, BLDG 2, Randolph, NJ 07869, USA. All products repaired by the Company will continue to be warranted against defects in material and workmanship for its installed life at the original end user. Limitations The Company's warranty does not extend to (A) The Company's products subject to (i) improper installation, connection, operation, maintenance, or storage; (ii) accident, damage, abuse, or misuse; (iii) abnormal or unusual operating conditions or applications outside the specifications for the product; (iv) a purpose or application in any way different from that for which the products were designed; (v) repairs conducted by persons other than the Company employees or an authorized representative or distributor; or (vi) modifications made to the product by the customer or end user, (B) Equipment and products not manufactured by the Company. Such equipment and products may be covered by a warranty issued by the respective manufacturer. This warranty is in lieu of any other warranties, express or implied, including without limitation, any warranty of merchantability or fitness for a particular purpose, and is in lieu of any and all other obligations or liability of the Company. Under no circumstances shall the Company be liable for any accidental or consequential damages or for any other loss, injury, damage, or expense of any kind including loss of profits arising hereunder. To the extent any court, arbitration panel, or other governmental body of competent jurisdiction shall declare any provision of this warranty invalid or unenforceable by reason of a rule of law or public policy, all the other provisions hereof shall remain in full force and effect. vi V4.42, December 16, 2007 1 INTRODUCTION The TTC-1000, Transformer Temperature Controller is a mission specific programmable controller that measures up to two different probe temperatures, load and calculated winding temperature. The user can program four (4) independent outputs based on the state of pre-programmed temperature set points, time set points, load set points or the outputs themselves. The controller can measure any two of top oil, winding, LTC tank, or ambient temperature to accuracy of ± 1 ºC and does not require calibration. Calculated winding temperature is based on the methods of ANSI C57.91 and uses measured top oil temperature and load current. The outputs can be used to: Control cooling fans and pumps. Provide high temperature, LTC condition, and cooling system performance alarms. Provide a trip output. The TTC-1000 is substation hardened and designed to operate over a wide temperature range of –50 to 85 ºC suitable for installation in outdoor cabinets. The TTC-1000 contains many features including: Measures temperature from -35 to 160 ºC. Does not require calibration. Optional 0-1 or 4 - 20 mA analog outputs. Optional dual probe version for top oil and the heated well. Optional aux CT input for calculated winding temperatures. Patented Load pickup set points for early activation of cooling based on sudden increases in load. Comprehensive LTC condition monitoring for the detection of both slowly and quickly evolving problems. Patent Pending. Universal probe kit includes thermo well fitting adapters and probe sleeves. Optional magnetic mount temperature probe when a thermo well is not available. Reports Min and Max Temperatures, time stamped with date and time. Data logging. Periodic exercise of cooling fans. Automatic swapping of lead and lag fan banks. 1 V4.42, December 16, 2007 Four independent temperature set points per probe. Cooling system performance monitor to alarm when cooling is commanded but the current draw of the cooling fans or pumps is outside a specified range. Four scheme logic programmable form C relay outputs, all trip duty rated. Dedicated programmable for B alarm relay in small form panel units and form C alarm relay in large form panel units and NEMA units. Remote/Local Communications through RS-232, no special software required. Flash memory for convenient firmware upgrades. Same unit operates from 38 to 160VDC or 120VAC and is immune to reversal of battery voltage polarity. Available in either compact panel mount or a 304 Stainless Steel NEMA 4X enclosure. Optional MODBUS or DNP3.0 Level 1 communications for reading analogs plus status and remotely commanding cooling via RS-485 or Multi-Mode Fiber Optics. Two optional optically isolated inputs for remote cooling control by SCADA, reporting status from liquid level or sudden pressure alarms over DNP3.0, or for selective blocking of outputs. Each TTC-1000 is burnt-in for a total of 48 hours prior to shipping and comes with a lifetime warranty. U.S. Patent No.: 6,714,022, 6,222,714 and Patents Pending. 2 V4.42, December 16, 2007 2 PRODUCT DESCRIPTION The following section describes the front panel display, indicators, and switches, connection points, mounting, physical size and panel cutout requirements 2.1 Controls & Indicators Figure 2. shows the front panel display, indicators, and switches for all versions. The overall panel size will vary, however the layout is identical. Advanced Power Technologies TTC-1000 CLEAR WINDOW NO TEXTURE 9 ALARM ACTIVE YES NO RS-232 10 1 2 3 4 5 6 7 8 Figure 2.1: Controls and Indicators – all versions 1 UP arrow button for navigating forward into menu categories and increasing settings. 2 DOWN arrow button for navigating backward into menu categories and decreasing settings. 3 LEFT arrow button used for moving to the next character to the left when changing settings. 4 RIGHT arrow button used for moving to the next character to the right when changing settings. 5 YES button is used to enter a menu category, request to change a setting, and acknowledge a setting change. 3 V4.42, December 16, 2007 6 NO button is used to leave a menu category or abort a setting change. 7 ACTIVE indicator is a green LED that illuminates when power is applied. 8 ALARM indicator is a red LED that illuminates whenever an alarm condition is present. Alarms can be caused by a failure detected in the electronics, or a broken temperature probe. In NEMA 4 mounting models, this indicator will flash when using the light activated Min/Max reset feature. 9 16 character by 2 line Liquid Crystal Display. 10 9 pin 15KV ESD protected RS-232 interface. 4 V4.42, December 16, 2007 2.2 Connection Overview Small Form Panel Unit 0.52 in. 5.70 in. Set Screw 6.10 in. Advanced Power Technologies CLEAR WINDOW NO TEXTURE 2.83 in. TTC-1 0 0 0 2.63 in. ALARM ACTIVE YES NO RS-232 .32 in. TB1 1 2 3 4 Main circuit board Power In 38 to 160VDC or 120VAC Aux CT Input Must use EXTERNAL CT Supplied TB2 NC COM Front Panel DB9 RS-232 N/C 1 Rx 2 Tx 3 N/C 4 GROUND 5 N/C 6 RTS 7 CTS 8 N/C 9 1 To Alarm 2 3 _ 5 + _ 6 + 4 REF 7 TMP 8 COM 9 REF 10 TMP 11 COM 12 A2 A1 BLK Connections for RS485 Option GND B GND A Connections for Analog Out Option REF RTD RED WHT TTC-PROBE-YY-XXX Probe 2 Shield Connect to ground BLK REF RTD RED WHT TTC-PROBE-YY-XXX Probe 1 Relay Board TB3 NO OUT 1 OUT 2 OUT 3 OUT 4 COM SHIELD 1 2 NC 3 NO 4 COM 5 NC 6 NO 7 COM NC 9 10 COM NC OUT3 OUT2 OUT1 GND TB1 TB2 8 NO OUT4 TB3 PROBE 1 PROBE 2 C O M C O M T M P R E F T M P R E F ANALOG OUT + A1 + A2 ALARM 4 3 Aux CT 2 1 Power 5.35 Cutout 11 12 Phoenix connector for probes , analog and alarm shown unplugged for clarity CHASSIS GROUND Figure 2.2: Small Panel Mount Connection Overview 5 V4.42, December 16, 2007 2.65 in. Cutout 2.3 Connection Overview Large Form Panel Unit Advanced Power Technologies TTC-1 0 0 0 No Connection A2 A1 4.779 _ 1 TB5 + 2 _ 3 ALARM ACTIVE TB3 + 4 _ 5 NO + 6 COM NC Front Panel DB-9 RS-232 N/C Rx Tx N/C GROUND N/C RTS CTS N/C Multi-Mode Fiber Optic DNP 3.0 or MODBUS Interface 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 DNP 3.0 or MODBUS Interface – only one connection method, wired or fiber, can be present Rx Tx OUT 1 B 1 A 2 GND 3 4 5 6 REF 7 TMP 8 COM 9 REF 10 TMP 11 COM 12 COM NC NO OUT 2 COM NC NO OUT 3 COM NC TB1B NO OUT 4 COM NC 1 YES RS-232 NO Power In 38 to 160VDC or 120VAC 7.559 To Alarm 6.0 in. Aux CT Input Must use supplied Aux CT 1 TB4 2 3 IN2 4 IEEE 485 DNP or MODBUS 3.558 No Connection Probe 2 BLK REF Set Screw RTD RED 0.40 WHT BLK REF RTD RED Connect All Cable Shields to Chassis Ground Stud Terminal blocks are shown less plugs for clarity. All terminals are on plug-in blocks as illustrated above WHT 2 Probe 1 3 4 5 6 7 8 9 Note that while the Analog Out shows A3, this output is not available for this version 1 ANALOG OUT 2 3 4 IN1 TB2 TB1A NO Optically Isolated Inputs 5 + No Connection SHIELD 4 3 IN1 2 1 IN2 N C TB4 C OUT6 N O N C C OUT5 N O N C C OUT4 6 N O TB1B Rpt N C C OUT3 N O A1 N C - + C A2 N O OUT2 N C + A3 OK TB5 C TB1A OUT1 N O GROUND Tx Rx 7 TB2 8 C O M T M P R C E O F M T M P R C E O F M T M P R E F G A B N RS485 D Rx Tx 7 6 5 4 3 ALARM 9 7.20 Case 7.3 Panel Cutout CHASSIS GROUND Figure 2.3: Large Panel Mount Connection Overview 6 2 1 TB3 AuxCT V4.42, December 16, 2007 POWER 3.558 3.7 Case Panel Cutout Connections Overview - NEMA Enclosure Advanced Power Technologies Multi-Mode Fiber Optic DNP 3.0 Interface - OR Wired IEEE 485 Interface TTC-1 0 0 0 CLEAR WINDOW NO TEXTURE ALARM ACTIVE YES NO RS-232 7.00 1 Rx Tx 2 N/C 4 GROUND 5 3 N/C 6 RTS 7 CTS 8 N/C 9 TB2 NC COM NO A1 + 1 TB4 2 3 4 5 6 RED TMP 8 WHT COM 9 REF 10 TMP 11 NO 11 Probe 2 10 9 REF 8 RTD WHT Probe 1 TTC-PROBE-YY-XXX Optically Isolated Inputs 14 15 D0/RI D0/RI 16 DNP output daughter board, if present, may be either IEEE485 or Multi-Mode fiber OR No Connection 7 6 5 Aux CT 4 3 Alarm 3 12 RED 7 NO 8 COM 9 NC NO 10 11 COM NC 12 13 - + Probe 1 TB2 BLK 1 COM 3 NC 4 NO 5 COM 6 NC Analog daughter card may have connections for 3 analogs, only up to two are available A2 A1 - + RTD Probe 2 2 OUT 1 CHASSIS GROUND - + REF TTC-PROBE-YY-XXX COM 12 TB1 IN2 Liquid-Tight Probe Cable Strain Relief No Connection BLK OUT 2 Lexan Window To Alarm 3 7 IN1 14.5 2 6 OUT 4 MEMBRANE BREATHER 1 REF OUT 3 15.25 Connect All Cable Shields to Chassis Ground Stud 5 D0/RI 1 D0/RI 2 + _ 38 to 160VDC or 120VAC Aux CT Input Must use supplied 4 TB5A A2 Power In Aux CT Tx _ Oblong 0.312 X 0.500 1 2 3 4 Rx No Connection 5.00 TB3 2 1 Power 2 1 TB3 4 COM TMP REF COM TMP REF 5.25 4 Output 1.63 DIA 3.00 OUT4 1/4-20x1/2 OUT3 OUT2 TB1 1.38 DIA 0.000 IN2 1.00 5.50 4 Output with Digital Inputs IN1 OUT4 0.000 3.00 OR OUT1 1.73 OUT3 OUT2 OUT1 Connection Layout Connections for Analog and DNP are on daughter cards mounted on the main board Figure 2.4: NEMA Mount Connection Overview 7 V4.42, December 16, 2007 Tx Front Panel DB-9 RS-232 N/C Rx 2.4 2.5 Specifications Power Supply Input Operating Range: 38 VDC to 160 VDC or 120VAC ±10%, 3 Watts max Operating Temperature Range: -50 to +85 °C Liquid Temperature Measurement Range: -35 to +160 °C LTC Differential Temperature Measurement Range: -20 to +20 °C Winding Temperature Measurement Range: -35 to 180 °C Temperature Measurement Accuracy: Average error over the entire measurement range of ± 1 °C. Current Measurement Range: Instantaneous 0 to 10 A RMS. Measurement accuracy ± 3.5%. Using split core CT provided. Output Contact Rating: 30 amps make for 250 msec. 10 amps continuous at 230VAC 0.4 amps break at 160VDC. See Section 4.3 for note on breaking under load Alarm Contact Rating: 0.4 amp continuous at 160VDC. See Section 4.3 for note on breaking under load Analog Output: Selectable, 0 to 1 mA or 4 to 20 mA current source referenced to chassis ground Maximum load 9,500 ohms for 0 to 1 mA and 450 ohms for 4 to 20 mA 8 V4.42, December 16, 2007 Dimensions: Small Panel Mount: 5.32” W x 2.61” H x 6” D. Aluminum Large Panel Mount: 7.20” W x 3.558” H x 6.0”D Aluminum NEMA 4X: 10” H x 6” W x 3.25” D. 304 Stainless Steel Surge Withstand/Fast Transient: Relay outputs, and station battery inputs: ANSI C37.90.1 EMI Withstand: ANSI C37.90.2 Dielectric Withstand: 1500 VDC for 10 seconds Electrostatic Discharge: IEC 801-2 Timers: Output and Load Pick Up Timer: 0 to 255 seconds (actual minimum delay 32 msec) Optically Isolated Inputs: External wetting required. Picks up between 38 and 160 VDC. Maximum input 160 VDC. Fiber Optic Interface: Transmit/Receive Wavelength 850nm. Supports 50 or 62.5 micron multi-mode fiber. Optical budget is 9.1 dB. Modulation is Non Return to Zero (NRZ). 9 V4.42, December 16, 2007 2.6 Part Number Details TTC- 1000- U V W X Y Panel Mounting 0 NEMA 4X Enclosure 3 Z 0 No Extra CT Inputs 1 1 Extra CT Input 2 ? 2 ? 8 Extra CT Inputs 8 NEMA 4X with Heater 4 No telemetry outputs 0 RS485 w/MODBUS 1 Single analog output 2 0 No option selected 1 Extra RS-232 Port Dual analog output 3 Triple analog output 4 3 Multi-Mode Fiber for DNP or MODBUS RS485w/Dnp3 Level 1 5 RS485Dnp3 w/1 analog out 6 4 Extra RS-232 Port & Fiber 5 12 Digital Inputs RS485Dnp3 w/2 analog out 7 RS485Dnp3 w/3 analog out 8 MODBUS w/1 analog out 9 6 12 Digital Inputs & Fiber 7 12 Digital Inputs & Extra RS-232 8 12 Digital Inputs, Fiber & RS-232 MODBUS w/2 analog out A MODBUS w/3 analog out B 0 4 form C Outputs, No inputs Single Probe 1 Dual Probe AUX CT, Single Probe 2 3 AUX CT, Dual Probe Three Probe (NEMA) Three Probe w/AUX CT (NEMA) 4 6 7 1 6 form C Outputs, No inputs 2 4 form C Outputs, 2 inputs 4 Connectorized 4 form C Outputs 5 6 form C Outputs, 2 inputs 6 Form C. Outputs with LTC Position 6 Monitoring TTC- PROBE- 0 t -zzz Ambient Temperature Probe 0 0 zzz Probe lead length,10 to 250 ft Universal Well Probe w/Snap Elbow 0 1 Magnetic Surface Mount Probe 0 2 ANSI C57 Well Probe w/Snap Elbow 0 5 Universal Well Probe Liquid Tight Rdy 1 1 ANSI C57 Well Probe Liquid Tight Rdy 1 2 5/16" Well Probe w/Snap Elbow 2 1 1/4" Well Probe w/Snap Elbow 3 1 Note that grayed out items are not available for this firmware version. 10 V4.42, December 16, 2007 3 INSTALLATION and CONNECTIONS The following section gives information on hookup of power, temperature probes, split core CT, outputs, optically isolated inputs, analog outputs along with connections to RS232 and RS485 or fiber optics for DNP3.0 communications. 3.1 Mounting There are three mounting configurations available. Panel Mounts are intended for installation inside the transformer control cabinet and NEMA 4X for mounting either inside or outside the control cabinet. Figure 2.2 shows the outline & cutout required for small panel mounting . The larger panel mount unit is designed to incorporate the additional features available in the NEMA package. The outline for the larger panel configuration is shown in Figure 2.3 Figure 2.4 shows the outline of the NEMA 4X enclosure. A mounting bracket, P/N:80001000167, suitable for retrofit or new applications is shown in Figure 3.4. The bracket is constructed from 1/8” THK 5052 Aluminum. 1.000 7.122 2.122 0.000 Ø 0.312 4 PLACES 9.250 8.250 16.500 R 0.375 4 PLACES 15.875 15.127 13.252 Ø 0.516 6 PLACES 9.500 8.500 7.500 6.750 4.875 45 2 PLACES 0.625 0.000 0.000 2.000 Figure 3.1: Mounting Bracket 11 V4.42, December 16, 2007 3.2 Power Hookup The TTC-1000 can be powered from either DC substation battery between voltages of 38 to 160 VDC or from AC voltage of 120 ±10% VAC. On small panel mount units (Figure 3.2a) power is connected to terminals 1 and 2 of barrier style terminal block TB1 and on TB3, terminals 1 and 2 (Figure 3.2b) on the large panel unit. On NEMA units (Figure 3.2c) power is connected to terminals 1 and 2 on TB-3. The TTC-1000 is not sensitive to polarity because it uses a bridge rectifier on the power input. This feature eliminates the risk of damage due to the reversal of power applied to this input. Aux CT NC C NO NC TB1 4 3 Aux CT a) Small Panel Mount 7 2 1 Power C 4 GROUND NO TB1A TB2 OUT1 OUT2 6 5 4 3 2 1 TB3 AuxCT ALARM 3 Power 2 TB1A 1 TB3 TB1 POWER b) Large Panel Mount c) NEMA 4 Figure 3.2: Power Connections NOTE: 1. The chassis of the panel mount unit or NEMA 4 enclosure MUST be bonded to ground. Panel mount units must be bonded to the ground bus in the control cabinet and NEMA units must be bonded to the main transformer grounding on the transformer tank. It is especially important to ground the unit when operating from 120 VAC. 2. For NEMA 4 units it is strongly recommended that the external ¼-20 ground stud be utilized for proper grounding. 3. When powering from AC substation service, it is essential that appropriate surge suppression for lightning protection is installed on the AC mains feeding the unit. An application note, ANTC003.PDF, is available on our web site, www.advpowertech.com. This note has detailed information on addressing this problem. 12 V4.42, December 16, 2007 WARNING: NEVER CONNECT POWER TO TERMINALS DESIGNATED FOR THE AUX CT. SERIOUS DAMAGE WILL OCCUR. 3.3 Temperature Probes The TTC-1000 can be equipped with either one or two probes. Universal thermowell probe types TTC-PROBE-01 and TTC-PROBE-11 are each provided with three thermometer well adapter fittings: 7/8-UNF (ANSI/IEEE C57 thermometer well), ½-NPT and ¾-NPT and three probe sleeves: 0.481, 0.625 and 0.675 OD. Temperature probes are interchangeable and do not require calibration. The temperature probes and measurement circuitry are intrinsically accurate to the stated accuracy specification. The probe leads are connected to a plug gable compression style terminal block. A terminal block is supplied with each unit and plugs into TB2. 3.3.1 TTC-PROBE-01 Installation Probe type TTC-PROBE-01 is provided with a strain relief that seals the thermometer well and holds the probe from pulling out of the well. Figure 3.3 shows the outline drawing for this probe type. Washer Snap Elbow (Included) Probe Cable Washer Spring (Included) (Included) Probe Probe Sleeve (Included) Thermometer Well Brass Fittings (Included) Figure 3.3: PROBE-01 Installation To install the probe into the thermo well: 1. Select the appropriate thermo well adapter fitting and either wrap the male threads with Teflon tape or coat with suitable pipe dope compound. Once the male threads are prepared, thread the adapter fittings into the thermo well. 13 V4.42, December 16, 2007 2. If the probe well’s ID is greater than 0.390 select the appropriate probe sleeve and slide over the probe. Tighten the set screw with the accompanying Allen Key. 3. Slide the probe into the thermo well. 4. Ensure that the snap elbow fitting is fully open. Apply Teflon tape to the male threads of the snap elbow fitting. Thread the snap elbow into the female threads of the thermo well adapter fitting. The spring holds the probe at the end of the well. 5. Close the elbow, forming a 90 degree right angle. Tighten the domed strain relief until the insert is tight against the probe cable. 3.3.2 TTC-PROBE-11 Installation Probe type TTC-PROBE-11 allows coupling of flexible conduit directly to the thermometer well adapter fittings provided. Its unique design allows the probe to be held in the well. Figure 3.4 illustrates this assembly. 1/2 NPT Liquid Tight Fitting Washer Not Included (Included) Spring (Included) Washer (Included) Probe Flexible Conduit Not Included Probe Sleeve (Included) Thermometer Well Brass Fittings (Included) Figure 3.4 PROBE-11 Installation To install the probe into the thermo well: 1. Select the appropriate thermo well adapter fitting and either wrap the male threads with Teflon tape or coat with suitable pipe dope compound. Once the male threads are prepared, thread the adapter fittings into the thermo well. 2. If the probe well’s ID is greater than 0.390 select the appropriate probe sleeve and slide over the probe. Tighten the set screw with the accompanying Allen Key. 3. Slide the probe into the thermo well. 4. Thread the appropriate brass fitting into the thermometer well. The spring holds the probe at the end of the well. 14 V4.42, December 16, 2007 5. Thread the appropriate conduit fitting into the ½-NPT female threads. 3.3.3 Magnetic Mount Probe (TTC-PROBE-02) Installation A magnetic mount probe (P/N: TTC-PROBE-02-xxx) is available for surface mounting to the LTC or transformer tank when a thermo well is unavailable. To mount the probe you will need: RTV silicone sealant suitable for the outdoor applications and rated for the maximum operating temperature. Thermal grease (supplied with probe). To install the probe: 1. Coat center probe area with a liberal coating of thermal grease as shown in Figure 3.5. Apply a liberal coating of Thermal Grease Figure 3.5: Magnetic Mount, Application of Thermal Compound 2. Place probe on the wall of the transformer or LTC tank to be monitored. The location should be as high as possible on the tank, but bellow the top level of the transformer’s or LTC tank’s oil level. It is recommended that the probe be installed on the LTC tank wall away from direct exposure to the sun. Direct exposure of the tank to sunlight can cause the surface to be at a slightly elevated temperature above normal, which may cause the differential temperature to be in error. See Figure 3.6. 15 V4.42, December 16, 2007 3. Place a bead of RTV silicone or other suitable sealing compound around the perimeter of the probe to seal the probe surface from moisture. See Figure 3.6. RTV Seal Tank Wall Figure 3.6: Magnetic Mount Views 3.3.4 Probe Lead Connections The probe leads are color-coded and are inserted into the terminal block in the following sequence: Probe Panel Marking Wire Color Terminal # 1 COM White 12 1 TMP Red 11 1 REF Black 10 2 COM White 9 2 TMP Red 8 2 REF Black 7 The resistance from the white to black probe leads is 1000 ohms and from white to red leads is 1000 ohms at 23 C and increases as a function of temperature. Figure 3.7a shows the probe connections for small panel mount units, Figure 3.7b shows the probe connections for large panel mount units, and Figure 3.7c shows probe connections for NEMA units. 16 V4.42, December 16, 2007 TB2 PROBE #1 PROBE #2 SHIELD 4 3 IN1 2 1 IN2 C T R C T R O M E O M E M P F M P F TB4 12 11 10 9 C O M T M P R E F C O M T M P R E F 8 7 6 5 4 3 2 1 TB1 TB2 a) Small Panel Mount C O M T M P R E F C O M T M P R E F C O M T M P R E F A B RS485 G N D b) Large Panel Mount c) NEMA 4 Figure 3.7: Probe Connections NOTE: It is extremely important that the probe shields be bonded to the TTC-1000 case. Failure to do this will allow surges to enter through these leads and do internal damage to the TTC-1000 For dual probe units, you must use both temperature probes for proper operation. The unit will continuously alarm if you fail to use both probes. If a second probe is unavailable, you can use two 1,000 ohm resistors. One end of one resistor to REF, the end of the second resistor to TMP. Tie the loose end of both resistors to COM. It is noted that probes can be supplied from lengths of 10 foot to 250 feet. When using existing substation wiring with probe lengths less than 250 feet, it is important to connect the probe’s shield drain wire to the shield the cable and observe that the total wiring length does not exceed 250 feet. Also it is important to ensure that the TTC-1000’s chassis is grounded to a point close to where the shield drain wire terminates as shown in Figure 3.8. Temperature Probe Substation Cable SHIELD TB3 OUT4 OUT3 OUT2 OUT1 GND TB2 PROBE #1 PROBE #2 C O M T M P R E F C O M T M P R E F TB1 + A1 + A2 ALARM 4 3 Aux CT 2 1 Power Probe Drain Wire Cable's Drain Wire Local Ground Bus Figure 3.8: Temperature Probe Shield Grounding 17 V4.42, December 16, 2007 3.4 Auxiliary CT Input for Calculated Winding Temperature Models TTC-1000-xx3x and TTC-1000-xx4x are equipped with an auxiliary CT input. A split core CT is supplied with these models and is intended to be applied over the secondary leads from the bushing CT. To apply the CT, first open the window by inserting a small screwdriver in the clasp holding the core halves closed. Select a CT secondary tap BUSHING CT SECONDARY ensuring that it is either shorted or SPLIT CORE already in use. It is recommended CT ELECTRICAL TAPE that B phase CT be used for this purpose. Wrap the wire with several CABLE TIE layers of electrical tape and apply the split core CT over the wire and snap it closed. It is highly recommended that a cable tie be applied under the split core CT to keep it from sliding down against the lug. Figure 3.9 illustrates the assembly of the split core CT onto the bushing CT secondary. Figure 3.9: Split Core CT Installation Figure 3.10a illustrates the CT connections to TB1 for small Panel Mount models, Figure 3.10b for large panel units, and Figure 3.10c illustrates the connections to TB2 of the NEMA 4X models. Aux CT NC NO C NC C GROUND NO TB1A OUT1 OUT2 TB2 TB1 4Aux3 CT 2 1 Power a) Small Panel Mount 7 6 5 4 3 2 ALARM 4 3 2 1 TB3 1 TB3 AuxCT Power TB1A TB1 POWER b) Large Panel Mount c) NEMA 4 Figure 3.10: Auxiliary CT Connections WARNING: SEVERE DAMAGE WILL RESULT IF THE SECONDARY LEADS OF THE BUSHING CT ARE CONNECTED DIRECTLY TO THE UNIT. 3.5 Cooling Control and Condition Alarm Connections Figure 3.11a illustrates the connections of the (4) form c dry relay contacts for small panel mount models. Figure 3.11b shows these connections on large panel 18 V4.42, December 16, 2007 mount units, Figure 3.11c illustrates the NEMA unit with optically isolated digital inputs, and 3.11d illustrates the NEMA unit with no digital inputs. Each relay is capable of carrying 10 Amps at 230 VAC. Configure these contacts for cooling control, high temperature alarms, or LTC condition alarm. Programming these contacts will be discussed in Section 4.9. NOTE: The ability for these contacts to break its load is based on a number of factors including voltage applied and the type of load. In general, there is a higher tendency for contacts to become welded shut at higher voltages. Therefore, protection devices, such as MOV’s are highly recommended if these contacts will be required to break more load current than that shown in the Specifications. SHIELD OUT4 TB3 OUT3 OUT2 OUT1 a) Small Panel Unit SHIELD 4 3 IN1 2 1 IN2 TB4 N C C OUT6 N O N C C N O OUT5 N C N O TB1B C N C OUT4 C N O OUT3 N C C N O OUT2 N C C N O TB1A GROUND OUT1 b) Large Panel Unit IN 2 IN 1 OUT4 OUT3 OUT1 OUT2 c) NEMA with Inputs OUT4 OUT3 OUT2 OUT1 d) NEMA without Inputs Figure 3.11: Connections to Relay Outputs 19 V4.42, December 16, 2007 3.6 Unit Alarm Connections The single form B relay is utilized to provide a dry contact closure for alarm conditions. While the unit is energized, the alarm relay is energized. This allows the unit to provide an alarm should the device lose DC power or becomes deenergized. The TTC-1000 monitors five conditions: Processor (DEVICE), Temperature (TPROBE), Winding (WNDG), Communications Processor (CPROC) and Manual Mode (MANUAL). The TTC-1000 allows the user to enable or disable any or all of the alarm conditions, except the Communications Processor alarm, through programming. The user can also program how each output reacts when an alarm occurs. Figure 3.12a illustrates the connections to small panel mount models, Figure 3.12b illustrates connections to large panel mount models, and Figure 3.12c the NEMA 4 models. Note: NEMA 4 models with board serial numbers ending in A with DNP3.0 and analog outputs will only have a normally closed alarm relay contact. GROUND Probe Probe 2 Probe 3 Alarm 1 3 2 1 TB2 12 11 10 9 8 7 6 5 4 Rx Tx Rpt TB2 C T R C T R + O M E O M E A1 M P F M P F + A2 ALARM a) Small Panel Unit Tx TB3 AUX CT ALARM POWER b) Large Panel Unit c) NEMA Unit Figure 3.12: Connections to Unit Alarm The user can program each output in how it reacts when either a Processor or Temperature alarm occurs. The user can set an output to pick up, drop out, or stay in its current state when either alarm occurs. 3.7 Telemetry Connections TTC-1000 provides a 9 pin female subminiature D connector on all models. Panel mount models can either have analog outputs or an RS-485 interface for DNP3.0 communications. NEMA 4 models can be equipped with both analog interfaces and an RS-485 interface for DNP3.0 communications. 3.7.1 RS-232 Terminal Connections Connection to this interface is through the front panel mounted DB-9 connector. When connecting to a standard RS-232 port in a PC, either desktop or laptop, 20 V4.42, December 16, 2007 use a 9 pin female to 9 pin male null modem cable. The following table lists the pin connections to the DB-9 connector. PIN 1 2 3 4 5 6 7 8 9 FUNCTION No connection Receive Data Transmit Data No connection Ground No connection Request to send Clear to send No connection 3.7.2 Analog Outputs The TTC-1000 is available with up to two analog outputs configured as current loops. The source for each analog output can be selected from probe 1 (P1), probe 2 (P2), or calculated winding temperature. The analog output is designed to operate with a series resistance of 9,500 Ohms when set to 0 to 1 mA or 450 Ohms when set to 4 to 20 mA. The analog outputs are connected to either terminal block TB2 on both panel mount and NEMA 4 models with serial letter suffix ‘A’. For these models Figure 3.13a illustrates the connections to both panel and NEMA, Figure 3.13b illustrates the large panel, and Figure 3.13c NEMA 4 models with a plug-in daughter board. NEMA 4 models equipped with a plug-in analog output module utilize TB4 for connections to the analog outputs.. The terminal marked + is the current source output. The connection marked – is the current transmitter’s return and is tied directly to the chassis ground. Analog output daughter card TB2 C T R C T R + O M E O M E A1 M P F M P F TB5 + A2 ALARM A2 May have connections for 2 or 3 analog outputs A3 A2 A1 A3 - + N C a) Small Panel Unit and NEMA “A” boards. A1 C OUT 3 N O N C C OUT 2 N O N C C OUT1 N O b) Large Panel Unit - + - + TB 4 GROUND c) NEMA Unit Figure 3.13: Connections to Analog Outputs 21 V4.42, December 16, 2007 NOTE: Connect to the analog outputs through shielded cable. Connect the drain wire of the shield to one of the ground stud on the rear of the TTC1000 or inside the NEMA 4 enclosure. Twisted pair cable is recommended. The analog outputs A1 and A2 can be programmed for 0 to 1 mA or 4 to 20 mA. Both analog outputs are identically programmed. Consult Section 5.4 or 6.3 for programming the scaling of the analog outputs. 3.7.3 RS-485 for DNP3.0 Communications Units equipped with the optional DNP3.0 communications interface contain a separate microprocessor to handle all overhead functions associated with the DNP3.0 protocol without affecting operation of the transformer cooling control and monitoring. The small panel unit and the NEMA units use a plug-in module that contains a half duplex RS-485 asynchronous communications interface capable of supporting multi-drop topologies with a single shielded twisted pair cable. This circuit is part of the main board in the large panel unit but still uses a separate processor. On the Small panel and the NEMA units, A jumper, J2, can be selectively installed if the TTC-1000 is either the first or last device on the two wire communications bus. Figure 3.19c illustrates the location of J2 on the Communications Processor Module. Jumper J2 must be installed if the TTC1000 is either the first or last device on the multi-drop communications bus. Installation of the jumper connects a 120 ohm termination resistor. Termination is vital to reduce reflections which affect proper operation when the length of the communications bus is long and/or there are many devices connected. The two wire module uses a fail-safe RS-485 transceiver that insures that incorrect operation does not occur due to an open or short circuit on the communications bus. While the TTC-1000 is immune from shorted or open communications link, other devices may require the use of bias resistors. On the large panel unit, an external resistor can be placed between the A & B terminals as there is no internal jumper. NOTE: For small panel mount versions, the unit contains the jumper but it is not installed. To install jumper J2, the unit must be disassembled. The Relay Board must be removed to gain access to the Communications Processor Module. J2 is located on the Communications Processor Module. It is noted that an 120 ohm resistor (a carbon or metal film resistor recommended) may be installed externally between rear panel terminals A & B on the plug-in terminal block TB2. The use of shielded twisted pair wire or cable is essential between nodes of the communications bus. Connection of devices on the bus should carefully considered. Every device on the bus must be connected in a daisy chain fashion like a string of Holiday lights. The devices on the bus should never be connected 22 V4.42, December 16, 2007 in a star configuration. Polarity of the connections are also critical and should be carefully observed and followed. For example, the “A” connection also known as the TD/RD should be connected to every other node’s “A” connection. Likewise for the “B” or the not TD/RD line. Figures 3.14a, b, & c illustrate connections to panel mount and NEMA 4 models. If using a wired RS-484 connection, it is essential that the termination be in the vicinity of the TTC-1000. As this is al low voltage communication circuit, ground potential rise or other surge phenomenon will damage the unit. It is preferred to use a fiber connection directly from the TTC-1000. The RS485 output is intended for connection to a LOCAL wired to fiber conversion or other device located on the transformer or in the control cabinet. . J2 IEEE 485 Bus Termination Jumper PROBE1 TB2 C T R C T R A G B G N N ALARM O M E O M E D D M P F M P F a) Small Panel Unit PROBE2 PROBE3 DO DO /RI /RI TB2 C O M T M P R E F C O M T M P R E F C O M T M P R E F A TB4 B DNP AB c) NEMA Unit b) Large Panel Unit Figure 3.14: Panel Mount and NEMA 4 RS-485 Connections There are many good references on implementing multi-drop RS-485 communication links from the semiconductor divisions of Texas Instruments, National Semiconductor, and MAXIM Integrated Products. 3.7.4 Fiber Optic Interface for DNP3.0 Communications NEMA 4X units and large panel units can be equipped with the optional DNP3.0 communications interface. The NEMA units use a plug-in Communications Processor module with a multi-mode fiber optic interface. This feature is installed on the main circuit board of the large panel unit and cannot be field installed. The circuit contains a separate microprocessor to handle all overhead functions associated with the DNP3.0 protocol without affecting operation of the transformer cooling control and monitoring. Fiber optics are recommended for substation installations as it avoids the problems of ground potential rise issues commonly associated with direct metallic connection. The optical interface operates at a wavelength of 850nm with 50 or 62.5 micron multi-mode fiber terminated with ST style connectors. As with all fiber optic communication links, the optical budget is an important number in determining the maximum distance that can be spanned with a specific manufacturer’s fiber. 23 V4.42, December 16, 2007 All optical fiber, whether it is glass or plastic core, has a specific loss in dB per kilometer. It is important to remember that optical losses can vary from manufacturer to manufacturer for the same core diameter and material. The maximum distance which can be spanned is defined by the following equation: DISTANCE in kM = (Optical Budget – 3dB) / Optical Loss in dB/kM The optical budget for the TTC-1000’s optical interface is 9.1dB. Therefore, using 62.5 micron glass core fiber, with a loss of 4.0 dB / kM the maximum distance spanned is approximately 1.5 kM or 4,900 feet. The fiber optic interface has the ability to operate either point to point or can be daisy chained with other intelligent electronic devices. A switch, S1, is provided to allow the user to select either point-to-point or repeat. Setting S1 to REPEAT passes the signal received on the fiber to the Tx fiber port without any delay. In the panel configuration, this switch is in software and is programmed via the settings from the front panel, computer, or settings file. In addition, three diagnostic indicators are provided for troubleshooting: Tx indicates that the fiber interface is transmitting data to the DNP master, Rx indicates that the fiber interface is receiving data from the DNP master, and ReTx if S1 is in the REPEAT position and received data is being re-transmitted through the Tx port to the next IED in the chain. Figure 3.15 is an outline drawing showing the fiber interface and the location of switch S1 and diagnostic indicators Tx, Rx, and Re-Tx. Rx Tx Rpt Rx Tx b) NEMA Unit a) Large Panel Unit Figure 3.15: Outline of Fiber Optic Interface 3.8 Optically Isolated Inputs These inputs are not available on the small panel unit, but are available on both the large panel unit and the NEMA units. Models equipped with inputs contain two optically isolated inputs, IN1 and IN2. These inputs must be wetted from an external power supply between 38 and 160 VDC. Connections are made through plug-in terminal block TB1. These optically isolated inputs may be used by the 24 V4.42, December 16, 2007 programmable logic to control or supervise any output. These inputs can also be used to communicate status information from devices such as the liquid level alarm or sudden pressure over DNP3.0. IN1 and IN2 can be programmed to be LEVEL or PULSE active. Figure 3.16 illustrates these connections. The use of shielded cable is recommended. GROUND TB4 IN2 IN1 TB1B IN2 IN1 OUT4 a) Large Panel Unit b) NEMA Unit Figure 3.16: Optically Isolated Input Connections 3.9 Heater Connections NEMA 4X Models, TTC-1000-4XX, are equipped with a 13 Watt thermostatically controlled heater and a specially designed vent that allows moisture to escape and does not allow moisture to re-enter. The heater can be operated from DC voltages of 38 to 160 or at 120 VAC. For convenience, the heater circuit is connected to TB3 terminals 1 and 2. However, the user can connect the heater to a separate power source. The thermostat turns off the heater circuit when the internal ambient temperature rises above 86 F (30 C) +/-10 F. The thermostat turns the heater back on at an internal ambient temperature between 80 to 75 F. 25 V4.42, December 16, 2007 4 SETTINGS Settings can be made either through the front panel or using a PC equipped with terminal emulation software. Proper operation of the TTC-1000 has been verified with Windows Terminal, Windows HyperTerminal, HyperTerminal Private Edition, and HyperAccess HyperTerminal as supplied in Windows XP has a bug that prevents backscrolling once 500 lines of information has been transferred, this problem is corrected in HyperTerminal Private Edition available from Hilgraeve.com. The terminal portion of some SEL software will work for programming though file transfer is not possible with them. For settings through a PC you will need a female to male DB-9 null modem cable (A standard SEL cable used with their relays is a null modem cable). The TTC-1000 is fixed to communicate at 9600 bits/sec with 8 bits, no parity and one stop bit. Setting sheets for programming from the front panel are in Section 12.1. Setting sheets for programming from a PC is in Section 12.2. The user should thoroughly familiarize themselves with the necessary settings and record their desired settings on the sheets provided. 4.1 Programming Settings Through Front Panel To access the PROGRAM menu press the or arrow buttons two times from the scrolling temperature display until the display reads: ENTER PROGRAM PASSWORD=0 You cannot enter PROGRAM unless you enter the correct password. The TTC1000 recognizes two passwords, one programmed and a super user password. The password programmed at the factory is 0000. The super user password is 0905 and cannot be changed. First, you must press YES to begin entering the password. The zero will flash. Use the or buttons to scroll between the digits. Each digit moved to will flash. Use the or arrow buttons to scroll through the digits 0 – 9. Press YES after you have entered all four digits. If the password is correct, you will see the 1st setting, SP11PICKUP. Pressing the NO button at any time will bounce you back to the password entry display. If the password is incorrect the display will read: WRONG PASSWORD PASSWORD=0 There is no limit to the number of times you may try to enter a password. 26 V4.42, December 16, 2007 4.2 Programming Settings Through a PC Data communications from the TTC-1000 is implemented through the front panel mounted DB-9 connector at a fixed data rate of 9600 bits per second, 8 bits of data, no parity, and one stop bit. Operation has been verified Windows Terminal 3.1, Procomm Plus and HyperTerminal. It is recommended that the terminal emulation be set for either ANSI or TTY. The pin out of this port is designed to use a 9 pin female to 9 pin male null modem cable. You will need to configure your terminal emulation program before you get started. Press the “Enter” key and observe that the Main Menu is displayed. On the “Enter Code:” line type “2/” followed by the four password digits. If this is a new unit type “2/0000 “. If you are unsure if a password has been programmed, or you are having trouble type “2/0905 “ for the super user password. The list of settings will scroll on the screen as follows: PROGRAM 01 SP11 PICKUP=60 øC 02 SP11 DRPOUT=55 øC 03 SP12 PICKUP=65 øC 04 SP12 DRPOUT=60 øC 05 SP13 PICKUP=100 øC 06 SP13 DRPOUT=95 øC 07 SP14 PICKUP=00 øC 08 SP14 DRPOUT=00 øC 09 SP21 PICKUP=00 øC 10 SP21 DRPOUT=00 øC 11 SP22 PICKUP=00 øC 12 SP22 DRPOUT=00 øC 13 SP23 PICKUP=00 øC 14 SP23 DRPOUT=00 øC 15 SP24 PICKUP=00 øC 16 SP24 DRPOUT=00 øC 17 WSP1 PICKUP=80 øC 18 WSP1 DRPOUT=75 øC 19 WSP2 PICKUP=85 øC 20 WSP2 DRPOUT=80 øC 21 WSP3 PICKUP=130 øC 22 WSP3 DRPOUT=125 øC 23 WSP4 PICKUP=00 øC 24 WSP4 DRPOUT=00 øC 25 LTCDIFF PICKUP=05 øC 26 LTCDIFF DRPOUT=00 øC 27 LTCDIFF PICKUPTMR=480 MIN 28 LSP1 PICKUP=4.0 A 29 LSP1 DRPOUT=3.5 A 30 LSP2 PICKUP=5.0 A 31 LSP2 DRPOUT=4.5 A 32 LOAD PICKUP TMR1 =180 sec 33 LOAD PICKUP TMR2 =120 sec 34 IN1 CTRL=LEVEL (0) 35 IN2 CTRL=LEVEL (0) 36 OUT1 PICKUP TMR=00 sec 37 OUT1 AUTO (0) 38 OUT1 SUPVS (2) w/ALRM 39 OUT2 PICKUP TMR=00 sec 40 OUT2 AUTO (0) 41 OUT2 SUPVS (2) w/ALRM 42 OUT3 PICKUP TMR=00 sec 43 OUT3 AUTO (0) 44 OUT3 UNCHG (0) w/ALRM 45 OUT4 PICKUP TMR=00 sec 46 OUT4 AUTO (0) 47 OUT4 UNCHG (0) w/ALRM 48 SP11 + TO OUT1 27 V4.42, December 16, 2007 49 SP12 + TO OUT2 50 SP13 + TO OUT3 51 SP14 Not Assigned 52 SP21 Not Assigned 53 SP22 Not Assigned 54 SP23 Not Assigned 55 SP24 Not Assigned 56 LTC * TO OUT4 57 WSP1 + TO OUT1 58 WSP2 + TO OUT2 59 WSP3 + TO OUT3 60 WSP4 Not Assigned 61 LSP1 + TO OUT1 62 LSP2 + TO OUT2 63 OUT1 Not Assigned 64 OUT2 Not Assigned 65 OUT3 Not Assigned 66 OUT4 Not Assigned 67 IN1 Not Assigned 68 IN2 Not Assigned 69 TIME1 02:00 TO 02:15 Assigned TO OUT1 70 TIME2 02:30 TO 02:45 Assigned TO OUT2 71 TIME3 00:00 TO 00:00 Not Assigned 72 OUT1 =INVERT (1) 73 OUT2 =INVERT (1) 74 OUT3 =Not INVERT (0) 75 OUT4 =Not INVERT (0) 76 CT RATIO=00 77 RATED LOAD=00 A 78 WINDING RISE @ RATED LOAD=20 øC 79 WINDING TC=06 MIN 80 COOLING TYPE=Not DIRECTED FOA (0) 81 TPROBE1 NAME=TOP OIL (0) 82 TPROBE2 NAME=LTCDIFF (3) 83 ALTERNATE=DSABL (0) 84 ANALGOUT=N/A 85 A1 SOURCE=P1 (0) 86 A2 SOURCE=WINDING (2) 87 BAUD RATE= 1200 (0) 88 NODE ADDR=00 89 REMOTE BLK=DSABL (0) 90 TIMEBASE=15 sec 91 INCLUDE P1 IN LOG=YES (1) 92 INCLUDE P2 IN LOG=NO (0) 93 INCLUDE WINDING IN LOG=NO (0) 94 INCLUDE LOAD IN LOG=NO (0) 95 TIME=07:58 96 DATE=07/09/03 97 WNDCKT ALRM ENABLED (0) 98 DEVICE ALRM ENABLED (0) 99 TEMPERATURE ALRM ENABLED (0) 100 MANUAL ALRM ENABLED (0) 101 TIME SP CNTR=00 102 UNIT ID= 103 NEG ANALGOUT SCALING=NO (0) 104 LTCDIFF RISE=00 øC 105 LTCDIFF RATE=000 MIN 106 PASSWORD=0000 Enter Code: 28 V4.42, December 16, 2007 4.3 Settings for Calculated Winding Temperature Models equipped with the Aux CT input are supplied with a split core CT which is snapped over the secondary leads from the bushing CT. You may skip this section if your model does not contain this feature. The winding hot spot temperature is calculated using the measured load current and top oil temperature along with certain settings including the primary CT’s ratio, hot spot rise over top oil temperature at rated load, rated load current, winding rise time constant and if the transformer cooling is directed FOA or FOW. The ranges for these settings are: Setting Setting Range Comments CT Ratio 1:1 to 9999:1 Can be set to 0 Hot Spot Rise over Top Oil 0 to 99 C 18 to 22 C Rated Load Current 0 to 65,535 A Enter top rating Winding Rise Time Constant 0 to 999 minutes Minimum 32msec m Constant 0.8 or 1 The steady state winding temperature is calculated based on the following equation1: HSn g ( fl)n * ( Loadn * CRation / RatedLoadn) 2m TO [1] Where: n = 1, 2, 3 HSn Ultimate calculated windng temperature g (fl)n Hot Spot Rise #n over Top Oil temperature at rated load Loadn Measured load current #n CTRation Primary CTn ratio Rated Loadn Rated load of #n CT current m 1.0 for directed FOA or FOW, 0.8 for all other cooling TO Measured Top Oil Temperature 1 ANSI C57.91-1995 29 V4.42, December 16, 2007 It is noted that the Hot Spot Rise over Top Oil at rated load is not always available. In this case we recommend using a value between 18 to 22 ºC. To accommodate the transient affect of changing load current, the winding temperature can be estimated at any point in time by entering the winding time constant. Therefore, the displayed winding temperature is calculated as follows: HS (t ) ( HSU HSI )(1 e t / HS ) TO [2] Where: θ HS (t) Winding temperature at time t θ HS U Ultimate winding temperature using equation [1] above θ HS I Initial winding temperature using equation [1] HS Winding time constant in minutes θTO Measured top oil temperature Because data to calculate W may not be available, the recommended setting for the winding time constant is between 5 to 10 minutes. 4.3.1 CT RATIO The CT RATIO is the CT ratio of the bushing CT which the split core CT is applied to. The CT ratio must be relative to 1. Therefore, if the CT ratio is 240:5 the CT ratio to enter is 48. Programming from the front panel, press the arrow button until the setting 017 is displayed: PRGM SETTING 017 CT RATIO=0000 Press the YES button. The first digit will flash. Use the or arrow buttons to scroll through the digits 0 – 9. Use the or buttons to scroll between the digits. Each digit moved to will flash. Press YES after you have entered all four digits. For programming from a PC just type the CT ratio on the “Enter:” line as follows: Enter:76/48 4.3.2 Rated Load The Rated Load setting is the top name plate rating in Amps. If the nameplate indicates ratings of 1000/1200/1400, use 1400 as the rated load. On some transformers the nameplate might only list the rating in MVA. In this case you will 30 V4.42, December 16, 2007 need to divide the top MVA rating by the voltage of winding monitored with the CT. The rated load for a 3 phase transformer is calculated as follows: Rated Load = MVA / (Voltage x 1.732) Programming from the front panel, press the arrow button until the setting 018 is displayed: PRGM SETTING 018 RATED LOAD=00000 Press the YES button. The first digit will flash. Use the or arrow buttons to scroll through the digits 0 – 9. Use the or buttons to scroll between the digits. Each digit moved to will flash. Press YES after you have entered all digits. For programming from a PC just type the Rated Load on the “Enter:” line as follows: Enter:77/1473 This will program the Rated Load to 1473 Amps. 4.3.3 Hot Spot Rise over Top Oil The Hot Spot Rise over Top Oil setting is either a number that can be obtained from the transformer manufacturer, deduced from heat run data or estimated in the range of 18 to 22 º C. Programming from the front panel, press the arrow button until the setting 019 is displayed: PRGM SETTING 019 WINDINGRISE=00 ºC Press the YES button. The first digit will flash. Use the or arrow buttons to scroll through the digits 0 – 9. Use the or buttons to scroll between the digits. Each digit moved to will flash. Press YES after you have entered all digits. For programming from a PC just type the Winding Rise @ Rated Load on the “Enter:” line as follows: Enter:78/20 This will program the hot spot rise to 20 degrees Celsius. 31 V4.42, December 16, 2007 4.3.4 Winding Rise Time Constant The Winding Rise Time Constant is the amount of time, in minutes, for the winding hot spot temperature to reach 67 percent of its final value. A number of factors including the volume and type of oil used and the mass of the transformer are factors that influence this setting. Because calculating this value is cumbersome, we recommend a setting from 5 to 10 minutes. Programming from the front panel, press the arrow button until the setting 020 is displayed: PRGM SETTING 020 WINDINGTC=000MIN Press the YES button. The first digit will flash. Use the or arrow buttons to scroll through the digits 0 – 9. Use the or buttons to scroll between the digits. Each digit moved to will flash. Press YES after you have entered all digits. For programming from a PC just type the Winding TC on the “Enter:” line as follows: Enter:79/7 This will program the winding rise time constant to 7 minutes. 4.3.5 Calculated Winding Exponent Setting The m exponent used to calculate winding temperature can be modified. The two choices are 0.8 for non-directed FOA type transformers and 1.0 for directed FOA or FOW types. Programming from the front panel, press the arrow button until the setting 021 is displayed: PRGM SETTING 021 DIRECTED FOA=NO Press the YES button. The first character will flash. Use the or arrow buttons to scroll between NO and YES. Press YES when you have made the correct selection. For programming from a PC just type the Cooling Type on the “Enter:” line as follows: Enter:80/1 This will program the Cooling Type to directed FOA/FOW. Enter 0 for all other cooling types. 32 V4.42, December 16, 2007 4.3.6 Checking Winding Temperature A built in WNDGCAL test function is provided to verify proper operation of the calculated winding temperature function. All settings described in Sections 4.3.1 through 4.3.5 must be made before performing this check. To verify correct operation of calculated winding temperature: Connect the split core CT to the unit as described in Section 3.3. Loop a conductor from a suitable test set capable of generating 5.0 Amps RMS through the window of the split core CT. Press the arrow button until the display reads: VIEW SETTINGS PRESS YES TO VIEW Press the YES button. Press the arrow button once. The display will read: VIEW SETTING 104 WNDGCAL=45C Record this number. Press the NO button. Press the arrow button once. The display will read: 07/21/03 13:35 TOPOIL=23C Wait until the display scrolls to winding temperature: 07/21/03 13:35 WINDING=45C Check the measured winding temperature against the WNDGCAL value. If the winding temperature is not within three degrees, re-check the connections to the split core CT and the current passing through the CT’s primary. 33 V4.42, December 16, 2007 4.4 Setting Probe Names After connecting the probe or probes and verifying that they are measuring temperature, you can choose one of the following names for each probe: TOP OIL WINDING AMBIENT LTCDIFF BOTMOIL NOTE: The MIN/MAX log should always be reset after changing probe names. This is especially critical for the LTCDIFF as its range is different from the TOP OIL, WINDING, BOTMOIL and AMBIENT temperatures. Programming from the front panel, press the arrow button until the setting 074 or 075 is displayed: PRGM SETTING 074 P1 NAME=TOP OIL Or PRGM SETTING 075 P2 NAME=LTCDIFF Press the YES button. The first character will flash. Use the or arrow buttons to scroll through the available names. Press YES after you have made your selection. When programming from a PC the following are the valid codes for the probe names available: 0...... TOP OIL 1...... WINDING 2...... AMBIENT 3...... LTCDIFF 4...... BOTMOIL 34 V4.42, December 16, 2007 Therefore to display TOPOIL for probe 1 type: Enter:81/0 This will program the probe 1’s name to TOPOIL. To program probe 2’s name to LTCDIFF type: Enter:82/3 4.5 Temperature Set Points The TTC-1000 has four independent temperature set points per temperature probe and four calculated winding set points. Dual probe units with calculated winding temperature have a total of 12 temperature set points. Each set point has its own pick up and drop out temperatures. The pick up and drop out temperature can be set at different temperatures and allows the controller to operate as either an under or over temperature controller. The following two equations describe how the controller reacts depending on the setting of the pick up and drop out temperature for liquid temperature probes: If SPpn Pick UP > = SPpn Drop Out then operate as over temperature If SPpn Pick UP < SPpn Drop Out then operate as under temperature Where: p = Probe # (1 or 2) & n = Set point # (1, 2, 3, 4) The equation for winding temperature pickup and drop temperatures are: If WSPn Pick UP > = WSPn Drop Out then operate as over temperature If WSPn Pick UP < WSPn Drop Out then operate as under temperature Where: n = Set point # (1, 2, 3, 4) The over temperature set point is ideal for handling the pickup of fans or pumps as well as generating over temperature alarms and trip signals. The under temperature feature is useful to block the operation of pumps at low temperatures. Figure 4.1 and 4.2 show when the SP picks up and drops out for when the controller is configured to operate in the over and under temperature modes respectively. 35 V4.42, December 16, 2007 Temperature SPpn Pick Up Temperature SPpn Drop Out Temperature Time SPpn Figure 4.1: Over Temperature Operation Temperature SPpn Drop Out Temperature SPpn Pick Up Temperature Time SPpn Figure 4.2: Under Temp Operation 36 V4.42, December 16, 2007 Once a set point has picked up, it will not drop out until the pre-programmed conditions are met. This feature is especially useful to allow the fans to continue to run until the top oil temperature drops to some lower temperature. Each output can be controlled directly by a temperature set point. The flexible programmable logic allows simple configuration to handle more complicated tasks. You will need to set pickup and drop out temperatures for each set point you wish to use. Once set, temperature set points take up to 16 seconds to take affect. Once you have established the pickup and drop out settings you are ready to assign the set points to a specific output. A set point will not pickup an output until you assign it to OUT1, OUT2, OUT3, or OUT4. When changing pickup or drop out temperature set points, the new value takes effect the next time temperature data is updated which occurs every 16 seconds. However, once a SP is picked up, changing the pickup temperature to a higher (if over temperature) or lower (if under temperature) value will not cause the SP to drop out. Once a temperature set point is picked up, the only way it can drop out is if the drop out condition is met. When changing pickup or drop out temperature set points, the new value takes effect the next time temperature data is updated which occurs every 16 seconds. However, once a SP is picked up, changing the pickup temperature to a higher (if over temperature) or lower (if under temperature) value will not cause the SP to drop out. Once a temperature set point is picked up, the only way it can drop out is if the drop out condition is metSP21, SP22, SP23, and SP24 drop out and pick up are settable in single probe models, but do not have any function. WSP1, WSP2, WSP3, WSP4 drop out and pick up are settable in models without the calculated winding feature, but do not have any function. 4.5.1 Setting Liquid Pickup and Drop Out Temperatures These settings are used to start a stage of cooling or indicate a high temperature alarm for either probe 1 or probe 2 liquid temperatures. Models with a single probe channel measuring either Top Oil temperature or Winding temperature through a heated well will use SP11, SP12, SP13 & SP14. Models with two probe channels where one probe measures Top Oil and the second probe measures the winding temperature using a heated well may use SP11, SP12, SP13, SP14, SP21, SP22, SP23, SP24. 37 V4.42, December 16, 2007 Programming liquid set points from the front panel, press the or arrow buttons until the setting 001 is displayed: PRGM SETTING 001 SP11PICKUP= 60C Press the YES button. The first digit will flash. Use the or arrow buttons to scroll through the digits. Use the or buttons to scroll between the digits. Each digit moved to will flash. The first digit will scroll ‘-‘, 0, 1. The second digit will scroll 0 to 9 if the first digit is 0, 0 to 6 if the first digit is 1 and last digit is 0, 0 to 5 if the first digit is 1 and the last digit is greater than 0. The last digit will scroll 0 to 9 if the first two digits are less than 16. Press YES after you have entered all digits. After setting the pickup temperature, press the arrow button once: Use the procedure described above to change the drop out setting. PRGM SETTING 002 SP11 DRPOUT= 5 5C The remaining liquid set points can be changed by pressing the arrow button and following the above procedure. For programming from a PC just type the desired temperature on the “Enter:” line as follows: Enter:1/75 This will program SP11 pickup to 75C. Enter:2/70 This will program SP11 drop out to 70C. 4.5.2 Setting Calculated Winding Pickup and Drop Out Temperatures Four separate set points are allocated for units equipped with calculated winding temperature. It is important that the winding calculation be set as per Section 4.3.1 through 4.3.5 and checked prior to making these settings as per Section 4.3.6. 38 V4.42, December 16, 2007 Set points WSP1, WSP2, WSP3 and WSP4 pickup and drop out temperatures can be set by the front panel by using the or arrow buttons until the setting 022 is displayed: PRGM SETTING 022 WSP1PICKUP= 7 5C Press the YES button. The first digit will flash. Use the or arrow buttons to scroll through the digits. Use the or buttons to scroll between the digits. Each digit moved to will flash. The first digit will scroll ‘-‘, 0, 1. The second digit will scroll 0 to 9 if the first digit is 0, 0 to 6 if the first digit is 1 and last digit is 0, 0 to 5 if the first digit is 1 and the last digit is greater than 0. The last digit will scroll 0 to 9 if the first two digits are less than 16. Press YES after you have entered all digits. After setting the pickup temperature, press the arrow button once: PRGM SETTING 023 WSP1DRPOUT= 80C Use the procedure described above to change the drop out setting. The remaining liquid set points can be changed by pressing the arrow button and following the above procedure. For programming from a PC just type the desired temperature on the “Enter:” line as follows: Enter:17/85 This will program WSP1 pickup to 85C. 4.6 LTC Condition Monitoring The TTC-1000 uses two mechanisms to detect tap changer problems. The first is based on measuring the arithmetic difference between the LTC tank temperature and top oil temperature and therefore is only available in dual temperature probe units. The range of the LTCDIFF temperature is from –20 to +20 ºC. A timer can be employed to supervise the pickup of the LTCDIFF set point to allow setting with greater sensitivity and security. This method is particularly well suited to detect slowly evolving problems in the tap changer compartment from coking, polymerization of contacts, or loose connections. 39 V4.42, December 16, 2007 The second method uses a rate of rise algorithm that subtracts an initial LTCDIFF temperature from the LTCDIFF temperature at the end of a time period defined as LTCDIFF RATE. The difference between the initial temperature and final temperature is programmable from 0 to 40 ºC and is defined as LTCDIFF RISE. This method is particularly well suited to detected rapid increases in temperature possibly associated with an evolving arc in the tap changer compartment. Both the LTCDIFF comparison against the LTCDIFF pickup temperature set point and the LTCDIFF rate of rise operate a single LTC point which is mapped into the programmable logic of the TTC-1000. NOTE: When using LTC condition monitoring, it is important to remember to name one of the probes LTCDIFF. Evaluation of the LTC set point is not done unless one of the probes is named LTCDIFF. 4.6.1 LTCDIFF Temperature Monitoring Figure 4.3 illustrates how the LTC differential set point operates for LTC condition monitoring. Temperature Top Oil Temperature LTC Tank Temperature LTC DIFF Pickup LTC DIFF Drop Out Time LTC Tank Temp - Top Oil Temp LTC Pickup Timer LTC Set Point Figure 4.3: LTC Differential Set Point Operation 40 V4.42, December 16, 2007 The TTC-1000 uses an LTC pickup timer settable from zero to 999 minutes to supervise the LTC set point. The above example shows that the LTCDIFF set point does not pickup until after the timer is complete. If the differential temperature drop down below the pick up temperature while the timer is in progress, the timer will reset. This timer allows the LTCDIFF set point to “ride” through daylight heating and hence permits a more sensitive setting. The above example shows that the LTC set point does not drop out because the difference between the LTC Tank temperature and the Top Oil temperature does not drop down to the LTCDIFF drop out temperature set point. NOTE: The LTCDIFF temperature displayed is the calculated differential. The corresponding analog output tracks this differential temperature. The LTCDIFF temperature is designed to read negative, because sometimes the LTC tank runs cooler than the top oil temperature. It is recommended that you monitor the LTCDIFF temperature for a period of time to determine the normal operating differential for the transformer. A good rule of thumb is to set the LTCDIFF pickup temperature from 3 to 7 degrees higher than the observed operating differential. The sensitivity of this setting can be improved through the use of the LTC pickup timer (LTCPUTMR) setting. The recommended setting for the LTCPUTMR is between 360 to 480 minutes ( 6 to 8 hours ) to ignore the affects of daylight heating on a lightly loaded transformer. The LTCPUTMR can be set up to 999 minutes ( 16 hours 39 minutes ). To use this feature you must first make sure one of the two probes has been named LTCDIFF. Next, program the LTCDIFF PU (pickup) and LTCDIFF DO (drop out) temperatures. As mentioned earlier, it is a recommended that the LTCDIFF temperature be monitored to determine the transformer’s normal operating point. Finally, the LTCPUTMR can be set once the transformers normal operating condition is determined. Setting the LTCPUTMR to zero permits the LTCDIFF set point to pickup as soon as the LTCDIFF PU temperature is reached. Setting the LTCPUTMR to some time other than zero will delay the pickup of the LTCDIFF set point as long as the LTCDIFF temperature is equal to or above the LTCDIFF PU temperature. NOTE: The LTCPUTMR will not change while in progress. New settings will take effect after the set point drops out or if the LTCDIFF temperature were to drop below the LTCDIFF PU temperature while the timer is in progress. Once you have established the pickup and drop out settings you are ready to assign the LTC set point to a specific output. This set point will not pickup an output until you assign it to OUT1, OUT2, OUT3, or OUT4. 41 V4.42, December 16, 2007 NOTE: 1. In single probe versions, the LTCDIFF pickup and dropout settings display “N/A”. 2. Be careful to check that the LTCDIFF pickup and dropout set points are never set to greater than 20 or less than –20. Erroneous operation of the LTCDIFF pickup or dropout will result if these set points are set beyond the stated range. 4.6.1.1 Setting LTCDIFF Set Point Programming LTCDIFF set points from the front panel, press the or arrow buttons until the setting 030 is displayed: PRGM SETTING 030 LTCDIFFPU= 05C Press the YES button. Use the or arrow buttons to scroll through the digits. Use the or buttons to scroll between the digits. Each digit moved that is displayed will flash. Digits not displayed will not flash. The first digit is dedicated to display a minus (-) sign. Press YES after you have entered all digits. After setting the pickup temperature, press the arrow button once: Use the procedure described above to change the drop out setting. PRGM SETTING 031 LTCDIFFDO= 00C For programming from a PC just type the desired temperature on the “Enter:” line as follows: Enter:25/3 This will program LTCDIFF pickup to 3C. Enter:26/-3 This will program LTCDIFF drop out to -3C. 42 V4.42, December 16, 2007 4.6.1.2 Setting LTCDIFF Pickup Timer Programming LTCDIFF pick up timer from the front panel, press the or arrow buttons until the setting 032 is displayed: PRGM SETTING 032 LTCPUTMR=480MIN Press the YES button. The first digit will flash. Use the or arrow buttons to scroll through the digits 0 – 9. Use the or buttons to scroll between the digits. Each digit moved to will flash. Press YES after you have entered all digits. For programming from a PC just type the LTC pickup timer value on the “Enter:” line as follows: Enter:27/480 This will program the LTCDIFF pickup timer to 480 minutes. 4.6.2 LTCDIFF Rate of Rise Monitoring Temperature LTCDIFF RISE LTCDIFF RATE Time LTCDIFF LTCDIFF RofR Figure 4.4 illustrates the LTCDIFF rate of rise method. Figure 4.4: LTCDIFF Rate of Rise Method The LTCDIFF Rate of Rise method uses two parameters: LTCDIFF RISE and LTCDIFF RATE. This function is disabled if either of these parameters are set to zero. This method operates by comparing the measured rise between a start and 43 V4.42, December 16, 2007 stop period defined by parameter LTCDIFF RATE with the programmed parameter LTCDIFF RISE. If the measured rise is greater than or equal to the LTCDIFF RISE an internal set point LTCDIFF R-R is picked up. The recommended range for setting LTCDIFF Rise is 5 to 20 C LTCDIFF Rate can be set from 1 to 255 minutes. NOTE: The rate of rise feature will remain picked up unless the unit is powered down to reset it. If this has picked up, there is an extremely serious problem in the tap changer and immediate attention is required. 4.6.2.1 Setting LTCDIFF Rise Programming LTCDIFF Rise from the front panel, press the or arrow buttons until the setting 102 is displayed: PRGM SETTING 102 LTCDIFFRISE=15 C Press the YES button. The first digit will flash. Use the or arrow buttons to scroll through the digits 0 – 9. Use the or buttons to scroll between the digits. Each digit moved to will flash. Press YES after you have entered all digits. For programming from a PC just type the LTCDIFF Rise value on the “Enter:” line as follows: Enter:104/15 This will program LTCDIFF Rise to 15C 4.6.2.2 Setting LTCDIFF Rate Programming LTCDIFF Rate from the front panel, press the or arrow buttons until the setting 103 is displayed: PRGM SETTING 103 LTCDIFFRISE=15 m Press the YES button. The first digit will flash. Use the or arrow buttons to scroll through the digits 0 – 9. Use the or buttons to scroll between the digits. Each digit moved to will flash. Press YES after you have entered all digits. For programming from a PC just type the LTCDIFF Rate value on the “Enter:” line as follows: Enter:105/15 This will program the LTCDIFF RATE to 15 minutes. 44 V4.42, December 16, 2007 4.7 Load Pickup Set Points Load current is measured with an external split core Aux CT supplied with models equipped with this feature. The Aux CT is not intended for direct exposure to the elements and should be installed within a NEMA 4 enclosure. Units equipped with this feature have two load set points. Apply these set points to activate cooling earlier based on a sudden increase in load current due to normal switching operations. Each set point has a load pickup timer settable from 0 to 255 seconds. The timer operates to block inadvertent load set point pickup due to fault conditions or inrush. Each load set point has it’s own pickup and drop out current setting. Each setting is adjustable from 0 to 9.9 Amps in 0.1 Amp increments. These settings are based on the primary current measured by the split core CT. Figure 4.4 illustrates the operation of the Load Pickup Set Points. LOAD Load Pick Up Current Load Drop Out Current Time Timer Resets Load Pickup Timer Load Pickup Set Point Figure 4.5: Load Pickup Set Point Operation The first case shows that the load current remains above the pickup set point for the full duration of the load pickup timer. In this case the load pickup set point will be picked up. The second case shows a transient load or external fault wherein 45 V4.42, December 16, 2007 the load current drops below the pickup point soon after the timer starts. This causes the timer to reset and the load pickup set point remains dropped out. NOTE: When load current is present, it is important to set the load dropout set point before the load pickup set point. If load pickup set point is set first, the load set point may be already picked up when this setting is made and will not drop out. The load set points can also be used to generate an alarm should the controller command cooling and the cooling system is drawing too little or too much current. For example, if the pickup current is set lower than the drop out temperature, the set point operates as an under load detector. Conversely, setting the pickup point higher than the dropout point allows the set point to operate as an overload detector. Setting one set point for under load and the other as overload permits detection of the cooling system’s load current “sweet spot”. NOTE: The calculated winding temperature feature will not function correctly when monitoring the cooling system’s load current. 4.7.1 Setting Load Pickup Set Point These settings are used to start a stage of cooling based on a sudden increase in load current. Two set points LSP1 and LSP2 are available to start up to two stages of cooling. As with temperature set points, load set points can be configured to operate in under current mode. To operate in under current the drop out current must be greater than the pick up current. Programming load set points from the front panel, press the or arrow buttons until the setting 033 is displayed: PRGM SETTING 033 LOADPUSP1= 4.0 Press the YES button. The first digit will flash. Use the or arrow buttons to scroll through the digits. Use the or buttons to scroll between the digits. Each digit moved to will flash. Press YES after you have entered all digits. After setting the pickup current, press the arrow button once: Use the procedure described above to change the drop out setting. PRGM SETTING 034 LOADDOSP1= 3.3 46 V4.42, December 16, 2007 The second load set point, LSP2, can be changed by pressing the arrow button and following the above procedure. For programming from a PC just type the desired load current set point value on the “Enter:” line as follows: Enter:28/4.0 This will program LSP1 pickup to 4.0A. Enter:29/3.3 This will program LSP1 drop out to 3.3A. NOTE: Load pickup and drop out set points are the CT busing secondary current and must always be entered with a decimal point and trailing 1/10’s digit. For 3 amps you must enter 3.0. For .5 amps you must enter 0.5. 4.7.2 Setting Load Pickup Timer Programming Load Pickup Timer from the front panel, press the or arrow buttons until the setting 037 is displayed: PRGM SETTING 037 LSP1PUTMR=120sec Press the YES button. The first digit will flash. Use the or arrow buttons to scroll through the digits 0 – 9. Use the or buttons to scroll between the digits. Each digit moved to will flash. Press YES after you have entered all digits. The LSP2 Pickup Timer, can be changed by pressing the arrow button and following the above procedure. For programming from a PC just type the load set point pickup timer value on the “Enter:” line as follows: Enter:32/120 This will program the Load pickup timer to 120 seconds. 47 V4.42, December 16, 2007 4.8 Optically Isolated Input Settings The TTC-1000 may be optionally equipped with two optically isolated inputs. Each input contains a limiting resistor that allows these inputs to recognize a wide range of input voltage of 38 to 160 VDC as being picked up. Inputs are scanned every 32 milliseconds. Contact chatter is debounced by requiring the input be stable for two scans before the new state is recognized. Inputs may be assigned to any output using the programmable logic. Each of the digital inputs can be set either as level active, LEVEL MODE or positive edge active, PULSE MODE. For LEVEL MODE, the recognized state of IN1 or IN2 follows the voltage applied to the input. There is a built-in 64 millisecond debounce time on all low to high voltage transitions. There is no debounce delay on high to low transitions. For PULSE, the recognized state of the input toggles every low to high voltage transition. High to Low transitions will not change the recognized state of IN1 or IN2 in PULSE mode. There are separate settings of LEVEL or PULSE for IN1 and IN2. Figure 4.5 illustrates the operation of inputs set to LEVEL and Figure 4.6 illustrates the operation inputs set to PULSE. Signal Applied to Input n Debounce Timer INn Figure 4.6: Input Set for LEVEL 48 V4.42, December 16, 2007 Signal Applied to Input n Debounce Timer INn Figure 4.7: Input Set for PULSE Programming from the front panel, press the arrow button until the setting 039 is displayed: PRGM SETTING 039 IN1=LEVEL Press the YES button. The first character will flash. Use the or arrow buttons to scroll between LEVEL and PULSE. Press YES when you have made the correct selection. The second input, IN2, can be changed to LEVEL or PULSE MODE by pressing the arrow button and following the above procedure. For programming from a PC just type the input detection, IN1 or IN2 CNTRL, mode on the “Enter:” line as follows: Enter:34/1 This will program the IN1 CNTRL to PULSE MODE. Type 0 for LEVEL MODE. 49 V4.42, December 16, 2007 4.9 Programmable Logic Settings The TTC-1000 utilizes a simple scheme to control the four relay outputs. Each output can be configured to be picked up or dropped out by assigning any of the available operands to a specific output. Table 4.1 illustrates the available operands. Type Quantity Description Temperature Set Points (Probe 1: SP11, SP12, SP13, SP14; Probe 2: SP21, SP22, SP23, SP24) 4 for Single Probe, 8 for Dual Probe LTC DIFF Set Point or’ed with LTCDIFF R-R (Not available in single probe ver.) 1 Uses two methods: LTCDIFF compared to a set point or LTCDIFF Rate of Rise. Winding Set Points: WSP1, WSP2, WSP3, WSP4 4 Each has its own pickup and dropout temperatures settable from 0 to 180 º C. Load Set Points: LSP1, LSP2 2 Each has its own pickup and dropout currents settable from 0.0 to 9.9 Amps Outputs (OUT1,OUT2,OUT3,OUT4) 4 Outputs can be assigned to either itself or any other output. TIME (TIME1, TIME2, TIME3) 3 Settable pickup and dropout times. Each settable from 00:00 to 23:59 INPUT (IN1, IN2) 2 From optically isolated inputs, if equipped. Each has its own pickup and dropout temperatures settable from 0 to 160 º C. Table 4.1: Operands An operand can only be assigned to a specific output and cannot be assigned to another output as long as it is assigned. For example, SP11 cannot be assigned to OUT2 and OUT3; it can only be assigned to either OUT2 or OUT3. IN1 or IN2 may be assigned like any other operand. Any of the temperature set points or outputs can be inverted when assigned. For example inverting SP11 will cause SP11 to be recognized as true whenever it is de-asserted. Also, these specific operands can be either AND’ed () or OR’ed (+) to a specific output. In evaluating a specific output, the TTC-1000 groups all of the OR’ed terms together and all of the AND’ed terms together. As an example by assigning SP11 + and SP21 + to OUT3 will result in the following Boolean expression for OUT3: OUT3 = SP11 + SP21 Assigning SP11 to OUT3 and SP21 and SP12 + to OUT3 will result in the following Boolean expression: OUT3 = SP12 SP11SP21 50 V4.42, December 16, 2007 Note, the OR operator plays no roll in the evaluation of the above expression. The TIME operands cannot be inverted and can only be OR’ed to the other terms assigned to the same output. As an example, if TIME2 is assigned to OUT3 in addition to the operands SP1, SP2 and OUT1 as shown above, the Boolean expression will be evaluated as: OUT3 = (TIME2 + SP12) SP11SP21 TIME set points are evaluated as true at any time the real time clock date is within the specified pickup or drop out range of these set points. NOTE: Do not use the inversion operator on individual set points when remote control through DNP3.0 and fail-safe cooling control is desired. The INVERT setting must be used on each output requiring fail-safe cooling control when remote cooling control through DNP3.0 is required. The use of the inversion operator on a set point will not be recognized by the remote control functions resulting in the cooling to be de-energized. There are additional settings available that enhance the flexibility of the programmable logic. These functions include: Output Timers for delaying pickup of the output relays. Output Inversion that permits overall inversion of logic equations controlling outputs. This is particularly useful for fail safe operation. NOTE: Fail safe operation is strongly recommended. Fail safe operation ensures that the cooling system picks up whenever the TTC-1000 becomes de-energized or encounters a failure. Fail safe requires the output relay controlling the cooling stage to drop out instead of picking up. This requires that each of the individual terms operating an output to drop out and be AND’ed to every term or each term is OR’ed and the overall output invert used to drop out the relay. Please remember to connect the contactor coil to the normally closed contact of the TTC-1000’s output relay. 4.9.1 Assigning Liquid Temperature Set Points Liquid temperature set points must be assigned to a specific output to start a stage of cooling, generate high temperature alarms, and generate high temperature trips. For more complicated applications, these set points can be assigned to block a stage of cooling. NOTE: DO NOT ASSIGN SP21, SP22, SP23, and SP24 IF ASSIGNING THE LTCDIFF SET POINT. 51 V4.42, December 16, 2007 To assign a liquid set point (SP11, SP12, SP13, SP14, SP21, SP22, SP23, SP24) to an output from the front panel, press the or arrow buttons until the setting 045 is displayed: PRGM SETTING 045 SP11 TO OUT0 Press the YES button. The first character is the inversion operator. Use the or arrow buttons to scroll between the inversion operator, !, and a blank space. While the inversion operator is displayed, the ! character will flash. PRGM SETTING 045 ! SP11 TO OUT0 Use the or buttons to scroll to the AND/OR logic operator. The operator will flash. Use the or arrow buttons to scroll between the and + operators. PRGM SETTING 045 SP11 + TO OUT0 Selecting will AND SP11 with any other set point or operand controlling the same output. Use to permit or block an output from operating. Selecting + will OR SP11 with any other set point or operand controlling the same output. Use + when you have a number of operands which can command the same output: Use the or buttons to scroll to the output #. The output number will flash. Use the or arrow buttons to scroll from 0 to 4. Setting the output number to zero will have the effect of de-assigning the set point. The following illustrates the change to output 1: PRGM SETTING 045 SP11 + TO OUT1 Press YES after you have set the inversion, AND/OR and output number. The remaining set points, SP12, SP13, SP14, SP21, SP22, SP23 and SP24 can be assigned by pressing the arrow button and following the above procedure. For programming from a PC just type the SP11 assignment on the “Enter:” line as follows: 52 V4.42, December 16, 2007 Enter:48/0/1/1 This will assign SP11 Or’ed to OUT1. To assign !SP11 And’ed OUT1: Enter:48/1/0/1 Consult the setting sheets to assign the remaining temperature set points SP12 through SP24. 4.9.2 Assigning Winding Temperature Set Points Winding temperature set points must be assigned to a specific output to start a stage of cooling, generate high temperature alarms, and generate high temperature trips. To assign a winding set point (WSP1, WSP2, WSP3, WSP4) to an output from the front panel, press the or arrow buttons until the setting 054 is displayed: PRGM SETTING 054 WSP1 + TO OUT1 Press the YES button. The first character is the inversion operator. Use the or arrow buttons to scroll between the inversion operator, !, and a blank space. While the inversion operator is displayed, the ! character will flash. PRGM SETTING 054 ! WSP1 TO OUT0 Use the or buttons to scroll to the AND/OR logic operator. The operator will flash. Use the or arrow buttons to scroll between the and + operators. Selecting will AND WSP1 with any other set point or operand controlling the same output. Use to permit or block an output from operating. Selecting + will OR WSP1 with any other set point or operand controlling the same output. Use + when you have a number of operands which can command the same output: PRGM SETTING 054 WSP11 + TO OUT0 Use the or buttons to scroll to the output #. The output number will flash. Use the or arrow buttons to scroll from 0 to 4. Setting the output number to zero will have the effect of de-assigning the set point. The following illustrates the change to output 1: 53 V4.42, December 16, 2007 Press YES after you have set the inversion, AND/OR and output number. The remaining set points, WSP2, WSP3 and WSP4 can be assigned by pressing the arrow button and following the above procedure. For programming from a PC just type the WSP1 assignment on the “Enter:” line as follows: Enter:57/0/1/1 This will assign WSP1 OR’ed to OUT1. To assign !WSP1 And’ed OUT1: Enter:57/1/0/1 Consult the setting sheets to assign the remaining temperature set points WSP2 through WSP4. 4.9.3 Assigning LTCDIFF for LTC Condition Monitoring Alarm The LTCDIFF set point must be assigned to a specific output to generate an LTC condition alarm. You may dedicate a single output or group it with other high temperature alarms by Or’ing it to the output used to indicate high temperature alarms. To assign the LTCDIFF set point to an output from the front panel, press the or arrow buttons until the setting 053 is displayed: PRGM SETTING 053 LTC TO OUT0 Press the YES button. The first character is the inversion operator. Use the or arrow buttons to scroll between the inversion operator, !, and a blank space. While the inversion operator is displayed, the ! character will flash. PRGM SETTING 053 ! LTC TO OUT0 Use the or buttons to scroll to the AND/OR logic operator. The operator will flash. Use the or arrow buttons to scroll between the and + operators. Selecting will AND LTC with any other set point or operand controlling the same output. Use to permit or block an output from operating. Selecting + will OR LTC with any other set point or operand controlling the same output. Use + when you have a number of operands which can command the same output: 54 V4.42, December 16, 2007 PRGM SETTING 053 LTC TO OUT0 Use the or buttons to scroll to the output #. The output number will flash. Use the or arrow buttons to scroll from 0 to 4. Setting the output number to zero will have the affect of de-assigning the set point. The following illustrates the change to output 4: PRGM SETTING 053 LTC + TO OUT4 Press YES after you have set the inversion, AND/OR and output number. For programming from a PC just type the LTCDIFF assignment on the “Enter:” line as follows: Enter:56/0/1/4 This will assign LTCDIFF OR’ed to OUT4. To assign LTCDIFF And’ed OUT4: Enter:56/0/0/4 55 V4.42, December 16, 2007 4.9.4 Assigning Load Pickup Set Points Load pickup set points must be assigned to a specific output to start a stage of cooling based on a sudden increase in load current. To assign a load pickup set point (LSP1 and LSP2) to an output from the front panel, press the or arrow buttons until the setting 058 is displayed: PRGM SETTING 058 LSP1 TO OUT0 Press the YES button. The first character is the inversion operator. Use the or arrow buttons to scroll between the inversion operator, !, and a blank space. While the inversion operator is displayed, the ! character will flash. PRGM SETTING 058 ! LSP1 TO OUT0 Use the or buttons to scroll to the AND/OR logic operator. The operator will flash. Use the or arrow buttons to scroll between the and + operators. Selecting will AND LSP1 with any other set point or operand controlling the same output. Use to permit or block an output from operating. Selecting + will OR LSP1 with any other set point or operand controlling the same output. Use + when you have a number of operands which can command the same output: PRGM SETTING 058 LSP1 + TO OUT0 Use the or buttons to scroll to the output #. The output number will flash. Use the or arrow buttons to scroll from 0 to 4. Setting the output number to zero will have the affect of de-assigning the set point. The following illustrates the change to output 1: PRGM SETTING 058 LSP1 + TO OUT1 Press YES after you have set the inversion, AND/OR and output number. 56 V4.42, December 16, 2007 LSP2 can be assigned by pressing the arrow button and following the above procedure. For programming from a PC just type the LSP1 assignment on the “Enter:” line as follows: Enter:61/0/1/1 This will assign LSP1 OR’ed to OUT1. To assign !LSP1 And’ed OUT1: Enter:61/1/0/1 Consult the setting sheets to assign LSP2. 4.9.5 Assigning IN1 and IN2 The IN1 and IN2 can be incorporated into the programmable logic by assigning these points to a specific output. IN1 and IN2 are useful if you wish to start a stage of cooling through a switch on the control panel or even from your RTU. It can also be used to block an output relay should the need arise. One such application could be the blocking of a high temperature trip. To assign the IN1 or IN2 to an output from the front panel, press the or arrow buttons until the setting 060 is displayed: PRGM SETTING 060 IN1 TO OUT0 Press the YES button. The first character is the inversion operator. Use the or arrow buttons to scroll between the inversion operator, !, and a blank space. While the inversion operator is displayed, the ! character will flash. PRGM SETTING 060 ! IN1 TO OUT0 Use the or buttons to scroll to the AND/OR logic operator. The operator will flash. Use the or arrow buttons to scroll between the and + operators. Selecting will AND IN1 with any other set point or operand controlling the same output. Use to permit or block an output from operating. Selecting + will OR IN1 with any other set point or operand controlling the same output. Use + when you have a number of operands which can command the same output: 57 V4.42, December 16, 2007 PRGM SETTING 060 IN1 + TO OUT0 Use the or buttons to scroll to the output #. The output number will flash. Use the or arrow buttons to scroll from 0 to 4. Setting the output number to zero will have the affect of de-assigning the set point. The following illustrates the change to output 1: PRGM SETTING 060 IN1 + TO OUT1 Press YES after you have set the inversion, AND/OR and output number. IN2 can be assigned by pressing the arrow button and following the above procedure. For programming from a PC just type the IN1 assignment on the “Enter:” line as follows: Enter:67/0/1/1 This will assign IN1 OR’ed to OUT1. To assign !IN1 And’ed OUT1: Enter:67/1/0/1 Consult the setting sheets to assign IN2. 4.9.6 Assigning OUT1, OUT2, OUT3 and OUT4 The OUT1, OUT2, OUT3 and OUT4 can be incorporated into the programmable logic by assigning these points to another output. This enhances the ability of the programmable logic. It should be noted that an output should not be assigned to itself unless a latching function is desired. To assign OUT1, OUT2, OUT3 or OUT4 to an output from the front panel, press the or arrow buttons until the setting 062 is displayed: PRGM SETTING 062 OUT1 TO OUT0 Press the YES button. The first character is the inversion operator. Use the or arrow buttons to scroll between the inversion operator, !, and a blank space. While the inversion operator is displayed, the ! character will flash. 58 V4.42, December 16, 2007 PRGM SETTING 062 ! OUT1 TO OUT0 Use the or buttons to scroll to the AND/OR logic operator. The operator will flash. Use the or arrow buttons to scroll between the and + operators. Selecting will AND OUT1 with any other set point or operand controlling the same output. Use to permit or block an output from operating. Selecting + will OR OUT1 with any other set point or operand controlling the same output. Use + when you have a number of operands which can command the same output: PRGM SETTING 062 OUT1 + TO OUT0 Use the or buttons to scroll to the output #. The output number will flash. Use the or arrow buttons to scroll from 0 to 4. Setting the output number to zero will have the affect of de-assigning the set point. The following illustrates the change to output 2: PRGM SETTING 062 ! OUT1 * TO OUT2 Press YES after you have set the inversion, AND/OR and output number. OUT2, OUT3, and OUT4 can be assigned by pressing the arrow button and following the above procedure. For programming from a PC just type the OUT1 assignment on the “Enter:” line as follows: Enter:63/0/1/2 This will assign OUT1 OR’ed to OUT2. To assign !OUT1 And’ed OUT2: Enter:63/1/0/2 Consult the setting sheets to assign OUT2, OUT3 or OUT4. 4.9.7 Time Set Points The time set points allow the user additional flexibility to activate events between specific times. There are three time set points available. Time set points are useful to exercise a bank of fans periodically. For example, the user can set the device to pick up an output at 03:00 hours and drop out at 59 V4.42, December 16, 2007 04:00 hours. Time set points can be used in conjunction with the temperature set points to control an output. Therefore, when controlling a bank of fans for the purpose of exercising them daily, it is necessary to OR (+) the temperature set point to the same output as the time set point. Time set points are by default, OR’ed to any other operand assigned to the same output. A counter is provided to set the frequency at which the time set points will operate. For example, setting the counter to 7 will operate the time set points every 7th day. Time set points use a 24 hour clock. When using time set points in conjunction with temperature set points for the purpose of picking up a cooling bank in fail-safe mode, both set points should be assigned as usual. To operate in fail-safe, apply the OUT INVERT to the specific output. 4.9.7.1 Time Set Point Settings To set and assign the TSP1 (TIME1), TSP2 (TIME2), TSP3 (TIME3) to an output from the front panel, press the or arrow buttons until the setting 066 is displayed: PROGRAM TSP1 066 14:00-14:15>OUT1 The first time, 00:00 is the pickup time. The second time, 00:00 is the drop out time. OUT0 is the output the time set point is assigned to. In this case TSP1 is not assigned. PROGRAM TSP1 066 00:00-00:00>OUT0 Press the YES button. The 10’s hour digit will flash. Use the or arrow buttons to set this digit. Use the button to move to the 1’s hour digit and observe that it flashes. Again use the or arrow buttons to set this digit. Scroll to the 10’s minute digit by pressing the button and observe that it flashes. Use the or arrow buttons to set this digit. Scroll to the 1’s minute digit and observe that it flashes. Use the or arrow buttons to set this digit. Scroll once more to the output number by pressing the button. Use the or arrow buttons to set the output number from 0 to 4. The following shows TSP1 set to pickup output 1 at 14:00 and drop out output 1 after 14:15: 60 V4.42, December 16, 2007 TSP2 and TSP3 are set using the same procedure described above. For programming from a PC just type the TIME1 setting and assignment on the “Enter:” line as follows: Enter:69/09:00/09:15/2 This will assign TIME1 OR’ed to OUT2. Consult the setting sheets to assign TIME2 and TIME3. NOTE: 1. ALL 4 DIGITS OF THE TIME SET POINT PICKUP AND DROP OUT TIMES MUST BE ENTERED TO SET THE CORRECT TIME. 2. IF USING ALTERNATE, THE STOP TIME OF THE FIRST SET POINT MUST OVERLAP THE START TIME OF THE SECOND SET POINT. 4.9.7.2 Time Set Point Counter Setting The time set point counter sets the frequency which the time set points will be allowed to pick up. It is settable from 0 to 255. A setting of 0 or 1 will operate the time set points on a daily basis. Programming time set point counter from the front panel, press the or arrow buttons until the setting 099 is displayed: PRGM SETTING 099 TIME SP CNTR=000 Press the YES button. The first digit will flash. Use the or arrow buttons to scroll through the digits 0 – 9. Use the or buttons to scroll between the digits. Each digit moved to will flash. Press YES after you have entered all digits. For programming from a PC just type the time set point counter value on the “Enter:” line as follows: Enter:101/30 This will set all of the time set points programmed to pickup every 30th day. 4.9.8 Setting Output Timers Setting the output timers delays the pickup of the output by the number of seconds set. Each output has its own timer capable of being set from 0 to 255 seconds. A setting of 0 will permit the output to pickup as soon as all of the 61 V4.42, December 16, 2007 programmable logic criteria are met. The output timer is only used in conjunction with the programmable logic and has no effect in manual, remote or alarm control. Programming the time set point counter from the front panel, press the or arrow buttons until the setting 041 is displayed: PRGM SETTING 041 OUT 1PUTMR=0 00 sec Press the YES button. The first digit will flash. Use the or arrow buttons to scroll through the digits 0 – 9. Use the or buttons to scroll between the digits. Each digit moved to will flash. Press YES after you have entered all digits. For programming from a PC just type the output timer value on the “Enter:” line as follows: Enter:36/15 This will set the delay to pickup output 1 by 15 seconds. Consult the setting sheets to program the pickup timers for OUT2, OUT3, and OUT4. 4.9.9 Setting Output Invert The output invert enhances the flexibility of the programmable logic by providing an overall output inversion for an entire logic equation. This is particularly useful for fail safe operation of the controller. Fail safe operation is highly recommended as it allows your cooling system to be activated should the TTC-1000 become de-energized or a device or temperature probe alarm is detected. Fail safe operation is achieved by ensuring the output relay drops out when the necessary set points are satisfied to command a stage of cooling. In fail safe it is vital to remember to wire the contactor controlling the fan bank between the common and normally closed contact. Programming from the front panel, press the or arrow button until the setting 069 is displayed: PRGM SETTING 069 INVERT OUT1=OFF Press the YES button. The first character will flash. Use the or arrow buttons to scroll between OFF and ON. Selecting ON will invoke the overall invert function. Press YES when you have made the correct selection. 62 V4.42, December 16, 2007 INVERT OUT2, INVERT OUT3, and INVERT OUT4 can be selected by pressing the arrow button and following the above procedure. For programming from a PC just type the setting for output invert on the “Enter:” line as follows: Enter:72/1 This will set OUT1 to INVERT. Type 0 for OUT1 not INVERT. Consult the setting sheets to change INVERT OUT2, INVERT OUT3 or INVERT OUT4. 4.9.10 Application Examples Any of the operands (temperature set points, load set points, inputs, time set points, LTCDIFF set points or the outputs themselves) can be assigned to OUT1, OUT2, OUT3, or OUT4. When assigning the temperature, LTCDIFF, and output operands you have the option of inversion (!) and either logically AND’ing (*) or OR’ing (+) the operand with other assigned operands to control a specific output. For example, you can assign two temperature set points with the AND (*) operator to OUT2. When both operands are picked up at the same time, the OUT2 picks up, after a settable pickup timer has timed out. If the OUT2 pickup timer is set to zero, OUT2 will pickup in 32 milliseconds once both temperature set points are picked up. OUT2 will remain picked up until either of the two temperature set points drop out. Using the inversion operator with a temperature set point programmed for over temperature, is particularly useful when it is desirable to run the fans if the controller becomes de-energized. When using the inversion operator for this purpose, it is necessary to use the B contact of the output relay. Time set points are also operands that can be assigned to OUT1, OUT2, OUT3 or OUT4. However, time set points do not use the inversion (!) operator and are always assigned with the OR (+) operator. An INVERT setting is available for each output to allow the entire equation to be inverted. This is especially useful when using temperature and time set points together in fail-safe. 63 V4.42, December 16, 2007 NOTE: Do not use the inversion operator on individual set points when remote control through DNP3.0 and fail-safe cooling control is desired. The INVERT setting must be used on each output requiring fail-safe cooling control when remote cooling control through DNP3.0 is required. The use of the inversion operator on a set point will not be recognized by the remote control functions resulting in the cooling to be de-energized. The following are some applications examples: Commanding the cooling fans: The simplest application is using an output to control a cooling bank. First, program the Pickup and Dropout temperature set point. Second, assign the set point to an output as follows: Using the LCD: Using RS232: SPkl OUTn where kl= 11,12,13,14,21,22,23,24 and n=1,2,3,4 kk/0/0/n where k=Parameter # and n=1,2,3,4 The Boolean equation to control the same bank from two different set points is expressed as follows: OUTn = Temperature Set Pointkp1 + Temperature Set Pointk2l2 Using the LCD: SPkp1+ OUTn where kp1=11,12,13,14,21,22,23,24 and n=1,2,3,4 SPkp2+ OUTn where kp2=11,12,13,14,21,22,23,24 and n=1,2,3,4 Using RS232: kk1/0/1/n where kk1=Parameter # and n=1,2,3,4 Kk2/0/1/n where kk2=Parameter # and n=1,2,3,4 To control a bank in fail-safe, simply invert each setting as follows: Using the LCD: !SPkl OUTn where kl= 11,12,13,14,21,22,23,24 and n=1,2,3,4 Using RS232: kk/1/0/n where k=Parameter # and n=1,2,3,4 NOTE: Do not use the inversion operator on individual set points when remote control through DNP3.0 and fail-safe cooling control is desired. The INVERT setting must be used on each output requiring fail-safe cooling control when remote cooling control through DNP3.0 is required. The use of the inversion operator on a set point will not be recognized by the remote control functions resulting in the cooling to be de-energized. To control a bank using two set points in fail-safe: Using the LCD: SPkp1+ OUTn where kp1=11,12,13,14,21,22,23,24 and n=1,2,3,4 SPkp2+ OUTn where kp2=11,12,13,14,21,22,23,24 and n=1,2,3,4 Using RS232: kk1/0/1/n where kk1=Parameter # and n=1,2,3,4 Kk2/0/1/n where kk2=Parameter # and n=1,2,3,4 64 V4.42, December 16, 2007 Use the INVERT OUTn setting to cause the output relay to drop out when either temperature set point is achieved. The resulting Boolean equation is: OUTn = !(Temperature Set Pointkp1 + Temperature Set Pointkp2) Periodic exercise of cooling fans: Use a time set point with the temperature set point, controlling the cooling fans, to exercise the fans on a daily basis. This is especially useful in areas where you might be running the fans continuously during the cooler months of the year. The Boolean equation to accomplish this task is: OUTn = Time Set Pointm + Temperature Set Pointkl Therefore, the cooling fans will come on when either the over temperature condition is achieved or the time of day is in between 02:00 to 03:00 hours. To program the controller simply assign the time and temperature set points as follows: Using the LCD: 02:00 to 03:00 > OUTn SPk + OUTn Using RS232: mm/02:00/03:00/n where mm=parameter # and n=1,2,3,4 Kk/0/1/n where k=parameter # and n=1,2,3, 4 To operate the output in fail-safe, just invert the expression using the output INVERT setting. Remember to use the B contact of the output relay. Cooling Fan Alarm: This example shows how to generate an alarm when cooling is commanded but the measured current as sensed by the Aux CT is not within a specified range. The Boolean equation for this function is expressed as: OUTn1 = (Load Set Pointm1 + Load Set Pointm2) OUTn2 First you must program Load Set Pointm1 for an underload condition, that is the pickup current less than dropout, and Load Set Pointm2 for overload. Once these are programmed the two load set points must be assigned as OR to OUTn1 as follows: Using the LCD: LSPm1+ OUTn1 where m1=1,2 and n1=1,2,3,4 LSPm2+ OUTn1 where m2=1,2 and n1=1,2,3,4 Using RS232: mm1/0/1/n1 where mm1=Parameter # and n1=1,2,3,4 mm2/0/1/n1 where mm2=Parameter # and n1=1,2,3,4 Then assign the output, OUTn2, commanding cooling to OUTn1 as follows: Using the LCD: OUTn2 OUTn1 Using RS232: n1/0/0/n2 where n1=1,2,3,4 and n2=1,2,3,4 where n1=Parameter # and n2=1,2,3,4 65 V4.42, December 16, 2007 4.10 Setting Output Control With Alarm The TTC-1000 monitors two critical conditions: processor (DEVICE) and temperature (TPROBE) and allows the user to control how each output reacts when an alarm occurs. A DEVICE alarm occurs anytime the microprocessor detects a failure in any of the peripheral hardware including the non-volatile E2 memory, the real time clock, analog outputs, corruption of stored data and power supply brown out. The TPROBE alarm is generated anytime the processor is unable to obtain reliable temperature information. This failure can be due to a discontinuity in the leads connected to the temperature probe or with any of the internal circuitry associated with the analog to digital conversion process. All temperature set point evaluations are suspended until the alarm condition is cleared. The TTC-1000 allows you to program how an output will react whenever there is a DEVICE or TPROBE alarm. There are three (3) ways an output can react whenever there is a DEVICE or TPROBE alarm: 1. Unchanged (UNCHG): the output remains as it was prior to the alarm. 2. Picked Up (PCKUP): the output picks up when alarm occurs. 3. Supervised (SUPVS): the output drops out when alarm occurs. The TTC-1000 output control default is UNCHG for each output. The user should decide how they wish each output to operate whenever there is either a DEVICE or TPROBE alarm. For example if OUT1 and OUT2 control two separate banks of fans, it might be desirable to have OUT1 and OUT2 pickup as soon as a DEVICE or TPROBE alarm occur. This insures that the fans are running even though there might be a device or temperature probe failure. NOTE: It is strongly recommended to set output control to supervised (SUPVS) for all outputs controlling cooling fans in fail-safe mode. However, if OUT3 is used for a trip signal, it may be desirable to use the DEVICE or TPROBE alarm to supervise OUT3. This will insure that a trip signal is blocked whenever a DEVICE or TPROBE alarms occur. Also, if OUT4 is used for a high temperature alarm, it may be desirable for OUT4 to remain unchanged if a DEVICE or TPROBE alarm occurs. This will insure that a high temperature alarm continues to be reported. Programming from the front panel, press the or arrow button until the setting 095 is displayed: PRGM SETTING 095 OUT 1UNCHGw/ALRM 66 V4.42, December 16, 2007 Press the YES button. The first character will flash. Use the or arrow buttons to scroll between PCKUP, SUPVS or UNCHG. PRGM SETTING 095 OUT 1SUPVSw/AL RM Press YES when you have made the correct selection. For programming from a PC just type the setting for Output Control with Alarm on the “Enter:” line as follows: Enter:38/2 This will set OUT1 supervised with a Device or Temperature Probe Alarm. Type 1 to pickup OUT1 with a Device or Temperature Probe Alarm, or 0 to leave the output unchanged with a Device or Temperature Probe Alarm. Consult the setting sheets to change output control for OUT2, OUT3, and OUT4. 4.11 Alternate Fan Banks The TTC-1000 can be programmed to alternate the energization between two outputs. This feature is particularly useful when it is desirable to insure a fan bank is regularly exercised. You can choose between seven (7) alternate options: 1. Disabled (DSABL) 2. Alternate between OUT1 and OUT2 (1 – 2) 3. Alternate between OUT1 and OUT3 (1 – 3) 4. Alternate between OUT1 and OUT4 (1 – 4) 5. Alternate between OUT2 and OUT3 (2 – 3) 6. Alternate between OUT2 and OUT4 (2 – 4) 7. Alternate between OUT3 and OUT4 (3 – 4) As an example, if Alternate between OUT1 and OUT4 is selected, the first time OUT1 picks up, the output relay associated with OUT1 will pick up. If OUT4 picks up while OUT1 is picked up, the relay associated with OUT4 will pick up. Once both OUT1 and OUT4 drop out, the next time OUT1 picks up the relay associated with OUT4 will pick up. If at sometime in the future OUT4 picks up when OUT1 is already picked up, the relay associated with OUT1 will pick up. The cycle repeats when both OUT1 and OUT4 have dropped out. 67 V4.42, December 16, 2007 Programming from the front panel, press the or arrow button until the setting 073 is displayed: PRGM SETTING 073 ALTERNATE DSABL Press the YES button. The first character will flash. Use the or arrow buttons to scroll between 1 – 2, 1 – 3, 1 – 4, 2 –3, 2 – 4, 3 – 4, or DSABL: PRGM SETTING 073 ALTERNATE 1 - 2 Press YES when you have made the correct selection. For programming from a PC just type the setting for ALTERNATE on the “Enter:” line as follows: Enter:83/1 This will set ALTERNATE=1-2. Type 2 to ALTERNATE=1-3, 3 to ALTERNATE=1-4, 4 to ALTERNATE=2-3, 5 to ALTERNATE=2-4, or 6 to ALTERNATE=3-4. Type 0 to disable alternate. 4.12 Auto and Manual Control The TTC-1000 supports direct manual control of any output relay directly from the front panel. When commanded ON, the relay picks up and commanded OFF the relay drops out. Manual control is important for two reasons. First, it gives the user a simple method to test the connections to the output relays when commissioning the unit. Second, it gives the user the ability to manually override both automatic or remote control should the operator desires to command cooling on a continuous basis. It can also be used to prevent an output from picking up. Manual mode can be exerted by communicating through the RS-232 interface, but it is impossible to control the output relay using this method. This setting should only be used when it is desired to block remote control of a specific output relay. Also, the TTC-1000 will leave the output relay whatever state it happened to be at the time manual control is exerted through the RS-232 interface. The TTC-1000 will cause the Device Alarm contacts to pick up when an output is put into the manual mode. In addition the ALARM LED on the front panel will illuminate. The user can block this alarm by using the manual mode alarm disable setting shown in Section 4.13. 68 V4.42, December 16, 2007 Once in Manual Mode any output relay will be de-energized if power is removed upon re-energization. The output remains in Manual Mode and cannot be reenergized without physically going to the device and turning the output on in the manual mode. Setting from the front panel, press the or arrow button until the setting 104 is displayed: PRGM SETTING 104 OUT1CTRL=AUTO Press the YES button. The first character will flash. Use the or arrow buttons to scroll between MAN OFF, MAN ON or AUTO. PRGM SETTING 104 OUT 1CT RL=MAN ON Press YES when you have made the correct selection. In this example, OUT1 will be picked up. Setting outputs from AUTO to MANUAL from a PC will only allow the output to be dropped out. It is not possible to pickup an output when setting from a PC. To change from AUTO to MANUAL using a PC just type the setting for auto or manual on the “Enter:” line as follows: Enter:37/1 This will set OUT1 to MANUAL OFF. Type 0 to return OUT1 to AUTO. Consult the setting sheets to change AUTO to MANUAL for OUT2, OUT3, and OUT4. 4.13 Setting Control of Unit Alarm The single form B relay is utilized to provide a dry contact closure for alarm conditions. While the unit is energized, the alarm relay is energized. This allows the unit to provide an alarm should the device lose DC power or becomes deenergized. The TTC-1000 monitors five conditions: Processor (DEVICE), Temperature (TPROBE), Manual Mode (MANUAL), Winding (WNDCKT), DNP3.0 Communications (CPROC). The TTC-1000 allows the user to enable or disable all of the alarm conditions, except the DNP3.0 Communications (CPROC), through programming. 69 V4.42, December 16, 2007 4.13.1 Device Alarm Setting A DEVICE alarm occurs anytime the microprocessor detects a failure in any of the peripheral hardware including the non-volatile E2 memory, the real time clock, analog outputs or corruption of stored data. Setting from the front panel, press the or arrow button until the setting 091 is displayed: PRGM SETTING 091 DEVICEALRM=ENABL Press the YES button. The first character will flash. Use the or arrow buttons to scroll between ENABL (enable) and DSABL (disable). PRGM SETTING 091 DEVICEALRM=DSABL Press YES when you have made the correct selection. Selecting DSABL will block the device alarm relay and the front panel alarm LED from illuminating. However, the front panel will display the device alarm if present. For programming from a PC just type the setting for device alarm enable on the “Enter:” line as follows: Enter:98/1 This will disable the device alarm. Type 0 to enable the device alarm. 4.13.2 Temperature Probe Alarm Setting The TPROBE alarm is generated anytime the processor is unable to complete an A/D conversion. This can be due to a discontinuity in the leads connected to the temperature probe or with any of the internal circuitry associated with the analog to digital conversion process. All temperature set point evaluations are suspended until the alarm condition is cleared. Setting from the front panel, press the or arrow button until the setting 092 is displayed: PRGM SETTING 092 TPROBEALRM=ENABL Press the YES button. The first character will flash. Use the or arrow buttons to scroll between ENABL (enable) and DSABL (disable). 70 V4.42, December 16, 2007 Press YES when you have made the correct selection. Selecting DSABL will block the device alarm relay and the front panel alarm LED from illuminating. However, the front panel will display the alarm if present. PRGM SETTING 092 TPROBEALRM=DSABL For programming from a PC just type the setting for temperature probe alarm enable on the “Enter:” line as follows: Enter:99/1 This will disable the temperature probe alarm. Type 0 to enable the alarm. 4.13.3 Manual Mode Alarm Setting The MANUAL alarm occurs anytime any of the four outputs is programmed from Auto Mode to Manual Mode, independent of whether the output is picked up or dropped out. The Manual Mode alarm is for reporting only and does not supervise any of the control functions. Setting from the front panel, press the or arrow button until the setting 093 is displayed: PRGM SETTING 093 MANALRM=ENABL Press the YES button. The first character will flash. Use the or arrow buttons to scroll between ENABL (enable) and DSABL (disable). Press YES when you have made the correct selection. Selecting DSABL will block the device alarm relay and the front panel alarm LED from illuminating. However, the front panel will display the alarm if present. For programming from a PC just type the setting for manual mode alarm enable on the “Enter:” line as follows: Enter:100/1 This will disable the manual mode alarm. Type 0 to enable the alarm. 4.13.4 Winding Circuit Alarm Setting The WNDCKT alarm occurs anytime the TOP OIL temperature exceeds 63 ºC for two hours in units that are equipped to measure load current. These are models 71 V4.42, December 16, 2007 –XX3X or –XX4X. This alarm is for reporting only and does not supervise any of the control functions. Setting from the front panel, press the or arrow button until the setting 094 is displayed: PRGM SETTING 094 WNDCKTALRM=ENABL Press the YES button. The first character will flash. Use the or arrow buttons to scroll between ENABL (enable) and DSABL (disable). PRGM SETTING 094 WNDCKTALRM=DSABL Press YES when you have made the correct selection. Selecting DSABL will block the device alarm relay and the front panel alarm LED from illuminating. However, the front panel will display the alarm if present. For programming from a PC just type the setting for the winding circuit alarm enable on the “Enter:” line as follows: Enter:97/1 This will disable the winding circuit probe alarm. Type 0 to enable the alarm. 4.14 Setting Date and Time The TTC-1000 utilizes a real time clock to maintain date and time. This device has two functions. It supplies precise 32 millisecond time ticks for the Real Time Interrupt and it keeps track of the time, date and day of the week. Also, the time, date, and day are maintained even while the unit is unpowered for 5 days at 85ºC. The TTC-1000 powers the RTC through the use of large value that eliminates the need for battery backup and is designed to operate over the entire temperature range. Time and date are used to evaluate the TIME set points and data logging. 72 V4.42, December 16, 2007 4.14.1 Setting Time and Date Via the Front Panel Setting from the front panel, press the or arrow button until the setting 087 is displayed: PRGM SETTING 087 TIME=00:05 Press the YES button. The 10’s hour digit will flash. Use the or arrow buttons to set this digit. Use the button to move to the 1’s hour digit and observe that it flashes. Again use the or arrow buttons to set this digit. Scroll to the 10’s minute digit by pressing the button and observe that it flashes. Use the or arrow buttons to set this digit. Scroll to the 1’s minute digit and observe that it flashes. Use the or arrow buttons to set this digit. Press the YES button after entering the time. Press the arrow button to set the month: Press the YES button. The 10’s month digit will flash. Use the or arrow PRGM SETTING 088 MONTH=00 buttons to set this digit. Use the button to move to the 1’s month digit and observe that it flashes. Again use the or arrow buttons to set this digit. Press the YES button after entering the month. Press the arrow button to set the day of the month: PRGM SETTING 089 DAY=00 Press the YES button. The 10’s day digit will flash. Use the or arrow buttons to set this digit. Use the button to move to the 1’s day digit and observe that it flashes. Again use the or arrow buttons to set this digit. Press the YES button after entering the day. Press the arrow button to set the year: PRGM SETTING 090 YEAR=00 73 V4.42, December 16, 2007 Press the YES button. The 10’s year digit will flash. Use the or arrow buttons to set this digit. Use the button to move to the 1’s year digit and observe that it flashes. Again use the or arrow buttons to set this digit. Press the YES button after entering the year. 4.14.2 Setting Time and Date Via the PC For setting time from a PC just type the current time on the “Enter:” line as follows: Enter:95/08:05 This will set the time to 8:05AM. The time entered must be a 4 digit international time. For setting the date from a PC just type the current date on the “Enter” line as follows: Enter:96/07/28/03 This will set the date to July 28, 2003. The date must be entered with a total 6 digits. A date entered of 5/3/03 will not register correctly. The correct entry for May 3, 2003 is: Enter:96/05/03/03 4.15 Setting Password A four digit password can be entered to restrict access to programming settings, downloading of setting files, and downloading of firmware upgrades. The super user password of 0905 is permanently recorded and cannot be changed. Programming from the front panel, press the or arrow buttons until the setting 108 is displayed: PRGM SETTING 108 PASSWORD=0000 Press the YES button. The first digit will flash. Use the or arrow buttons to scroll through the digits 0 – 9. Use the or buttons to scroll between the digits. Each digit moved to will flash. Press YES after you have entered all four digits. For programming from a PC just type the new password on the “Enter:” line as follows: 74 V4.42, December 16, 2007 Enter:106/2767 It is important to remember to enter the password as a four digit number. Failure to enter a four digit number will result in an incorrect password. 4.16 Setting Unit ID A six character unit identifier can be programmed. The unit ID is stored as a setting but also appears on the Status menu over the RS-232 interface. Programming from the front panel, press the or arrow buttons until the setting 100 is displayed: PRGM SETTING 100 UNIT ID=TX2767 Press the YES button. The first digit will flash. Use the or arrow buttons to scroll through the digits 0 – 9. Use the or buttons to scroll between the digits. Each digit moved to will flash. Press YES after you have entered all four digits. For programming from a PC just type the Unit ID on the “Enter:” line as follows: Enter:102/TX2767 75 V4.42, December 16, 2007 5 TELEMETRY OPTIONS This section will discuss the various telemetry options available, their use and any relevant settings. The TTC-1000 can be optionally equipped with either current loop outputs and a RS-485 DNP3.0 communications interface. All TTC1000’s come equipped with a 9 pin DB-9 connector for RS-232 ASCII communications. Temperature information can be retrieved through the RS-232 interface. 5.1 Analog Outputs The TTC-1000 is available with two analog outputs configured as current loops. The source for each analog output can be selected from probe 1 (P1), probe 2 (P2), or calculated winding temperature. The analog output is designed to operate with a series resistance of 9,500 Ohms when set to 0 to 1 mA or 450 Ohms when set to 4 to 20 mA. The third analog output is configured to supply 0 to 1 mA and cannot be switched to operate in the range of 4-20 mA. The analog outputs are connected to terminal block TB2 on all panel mount units. NEMA units with serial letter suffix ‘B’ contain TB4 for connections to the analog outputs. All other NEMA units utilize TB2. The terminal marked + is the current source output. The connection marked – is the current transmitter’s return and is tied directly to the chassis ground. NOTE: Connect to the analog outputs through shielded cable. Connect the drain wire of the shield to one of the ground stud on the rear of the TTC1000 or inside the NEMA 4 enclosure. Twisted pair cable is recommended. The analog outputs A1 and A2 can be programmed for 0 to 1 mA or 4 to 20 mA. Both analog outputs are identically programmed. The scaling of the analog output varies depending on what is being measured. The following table illustrates the scaling dependent on range and the quantity measured and whether negative temperature scaling is enabled: Probe Min @ -35 Min @ 0 Max P1 or P2 0 mA @ -35 ºC 0 mA @ 0 ºC 1 mA @ 160 ºC CALC. WINDING 0 mA @ -35 ºC 0 mA @ 0 ºC 1 mA @ 180 ºC LTCDIFF Not Applicable 0 mA @ -20 ºC 1 mA @ +20 ºC P1 or P2 4 mA @ -35 ºC 4 mA @ 0 ºC 20 mA @ 160 ºC CALC. WINDING 4 mA @ -35 ºC 4 mA @ 0 ºC 20 mA @ 180 ºC LTCDIFF Not Applicable 4 mA @ -20 ºC 20 mA @ +20 ºC 0 to 1 mA Range: 4 to 20 mA Range: 76 V4.42, December 16, 2007 Upon initialization, the DAC is set to zero, if 0 to 1 mA or offset to drive 4 mA, if set for 4 to 20 mA. During the initialization process, the processor looks to see if the DAC is installed. If installed, the DAC will be updated every 16 seconds when new temperature data is available. Should the user select a new range, the output will not change range until new temperature data is available. The relationship of the analog output differs depending on what the probe is measuring. For top oil, winding, and ambient temperatures the relationship between output current and temperature is as follows: Range 0 to 1mA with normal scaling: For measurements from P1 or P2: Current = Temperature/160 For calculated winding temperature:Current = Temperature/180 Range 4 to 20mA with normal scaling: For measurements from P1 or P2: Current = 0.1 x Temperature +4 For calculated winding temperature:Current = 0.089 x Temperature + 4 Range 0 to 1mA with negative scaling: For measurements from P1 or P2: Current = Temperature/195 For calculated winding temperature:Current = Temperature/215 Range 4 to 20mA with negative scaling: For measurements from P1 or P2: Current = 0.08205 x Temperature +6.872 For calculated winding temperature: Current = 0.07442 x Temperature + 6.605 For LTCDIFF the relationship is as follows: Range 0 to 1mA: Current Temperature 40 0.5 Range 4 to 20mA: Current 0.4 Temperature 12 5.1.1 Setting the Analog Output Range The analog output range for both A1 and A2 can be switched from 0 – 1 mA to 4 – 20 mA. The range of the third analog output is fixed at 0 – 1 mA and cannot be changed. To change this setting, enter PROGRAM mode from the front panel as discussed in Section 4.1. To set the analog output range from the front panel, press the or arrow button until the setting 076 is displayed: 77 V4.42, December 16, 2007 PRGM SETTING 076 ANALGOUT=0to1mA Press the YES button. The first character will flash. Use the or arrow buttons to scroll between 0to1mA and 4to20mA. PRGM SETTING 076 ANALGOUT=4to20mA Press YES when you have made the correct selection. For programming from a PC, enter PROGRAM through the main menu as discussed in Section 4.2. Once in PROGRAM, type the setting for the ANALGOUT range on the “Enter:” line as follows: Enter:84/1 This will change the analog output range from 0 – 1 mA to 4 – 20 mA. Type 0 to change to 0 – 1 mA. 5.1.2 Setting the Analog Source The source of data for the analog input can either be liquid probe P1, liquid probe P2, or calculated winding temperature. The TTC-1000 automatically scales the data to be reported. To change this setting, enter PROGRAM mode from the front panel as discussed in Section 4.1. To set the analog source from the front panel, press the or arrow button until the setting 077 is displayed: PRGM SETTING 077 A1SOURCE>P1 Press the YES button. The first character will flash. Use the or arrow buttons to scroll between P1, P2 and WINDING. PRGM SETTING 077 A1SOURCE>WINDING Press YES when you have made the correct selection. A2 source can be selected by pressing the arrow button and following the above procedure. The setting for A3 source will appear if installed. 78 V4.42, December 16, 2007 For programming from a PC, enter PROGRAM through the main menu as discussed in Section 4.2. Once in PROGRAM, type the setting for the A1 SOURCE on the “Enter:” line as follows: Enter:85/2 This will change the source for analog output A1 to WINDING. Type 0 to change the source to P1 or 1 to change the source to P2. 5.1.3 Enabling Negative Scaling The default scaling of analog outputs for all but LTCDIFF is from zero degrees. However, if operating in cold climates, it may be necessary to scale the analog outputs from –35 ºC for all temperatures except LTCDIFF. To change this setting, enter PROGRAM mode from the front panel as discussed in Section 4.1. To set the analog source from the front panel, press the or arrow button until the setting 101 is displayed: PRGM SETTING 101 NEG ANALGOUT=NO Press the YES button. The first character will flash. Use the or arrow buttons to scroll between YES and NO. Press YES when you have made the correct selection. For programming from a PC, enter PROGRAM through the main menu as discussed in Section 4.2. Once in PROGRAM, type the setting for the NEG ANALGOUT SCALING on the “Enter:” line as follows: Enter:103/1 This will change the scaling from normal to negative. Type 0 to change back to normal scaling. 5.2 DNP3.0 Units equipped with the optional DNP3.0 communications interface contain a plug-in Communications Processor module. The module contains a separate microprocessor to handle all overhead functions associated with the DNP3.0 protocol without affecting operation of the transformer cooling control and monitoring. The module contains either a half duplex, full duplex isolated RS-485, multi-mode fiber optic asynchronous communications interface capable of 79 V4.42, December 16, 2007 supporting multi-drop topologies. RS-485 interfaces differ from RS-232 in that RS-485 uses a differential receiver and transmitter pair. This permits RS-485 links to send and receive data over much greater distances as long as some simple rules are followed. See Sections 3.7.3 and 3.7.4 for connections and jumper settings. After making the proper connections to the TTC-1000, there are only two settings that need to be made: Node Address and Baud Rate. Node Addresses can be any number from 0 to 65535. Please consult the DNP3.0 reference materials as some higher order addresses are reserved for broadcast messages. Baud Rates can be set to either 1200, 2400, 9600 or 19200. It is recommended that both Node Address and Baud Rate settings be made before attempting to communicate, however these settings can be changed “on-the-fly” without powering down the TTC-1000. The TTC-1000 implements DNP3.0 Level 1 communications. This includes Class 0 polls (Object 60 Variation 1) of analog and binary output points. The TTC-1000 supports Object 1 Variation 2 binary outputs. Binary outputs include all temperature and load set points along with the state of each output relay. Because Variation 2 is supported, the TTC-1000 communicates whether or not an output relay is under manual control by exerting the “forced” status bit for these points only. The “forced” status bit is located in bit 4 of each binary output octet transmitted to the Master. For Analog Outputs, the TTC-1000 supports Object 30 Variation 4. These are 16 bit signed analog quantities without status. Included in the Analog Output points are all temperatures equipped plus load data if available. Also, the TTC-1000 uses two points to identify whether or not the probe is measuring Top Oil, Heated Well, LTC Differential or Ambient temperature. This is particularly useful for dual probe units. It is noted that Object 1 Variation 2 and Object 30 Variation 4 points cannot be read individually and can only be read by a Class 0 poll. In addition, the TTC-1000 supports the remote control of the four output relays. The TTC-1000 supports both direct control (Object 10 Variation 0) and Select Before Operate control (Object 12 Variation 1). The TTC-1000 permits the user to command an output relay to pickup. It cannot be used to dropout an output relay. If the Binary Input point is turned off, it merely returns the device to local automatic control. Once the unit accepts the remote control command, the “remote forced” bit will become a logic “1”. The “remote forced” bit will remain a logic “1” until that point is dropped out by the DNP Master. Remote control can be blocked through the use of the REMOTE BLK setting. Enabling this setting will prevent all output points from picking up through remote control. Also, enabling the REMOTE BLK setting after an output has been commanded to remotely pickup but before remote control is returned to local control, will cause all output points to revert back to local automatic control. The “remote forced” bit will remain logic “1” until the point is returned back to local 80 V4.42, December 16, 2007 automatic control. Remote control will be immediately re-enabled once the REMOTE BLK setting is disabled. In addition, local manual control overrides remote control. The user should observe the status of the “local forced” bit in the appropriate Binary Output point, as noted above, before attempting to exert control as the TTC-1000 will remember that the bit has been exerted even though the TTC-1000 is in Manual Mode. Once an output is released from Manual Mode, the output will either return to automatic or remote control. If the point had been commanded remotely, the output will pickup as soon as the field personnel remove local manual control. This could result in an undesired operation of the specific output relay. User’s of remote control should always remember to turn off a Binary Input once they have turned it on to insure a return to local automatic control. This is why Users should observe the “local forced” and “remote forced” bits. To maintain compatibility with Fail-Safe operation of the cooling system, remote commanding of cooling operates in conjunction with the INVERT setting for each output. For example, if the INVERT bit is set for OUT1, then the OUT1 relay will drop out. This is an important point to remember when setting the programmable logic as Fail-Safe cooling will not be observed under remote control if the user implements Fail-Safe cooling by assigning a set point using the inversion operator. Finally, the user should not expect instantaneous report of updated temperature and status from the TTC-1000. The use of a separate Communications Processor does not guarantee instantaneous reporting of data. The philosophy of implementation is that the top priority of the Main microprocessor is for control and monitoring and the Communications Processor is to receive potentially highspeed request messages from the DNP Master and to respond to these requests without delay. While higher polling rates are possible, it is highly recommended that the polling rate be between 1,000 to 10,000 milliseconds, but should be no faster than 500 milliseconds. Please refer to the DNP3.0 Profile Document in Section 14 for additional details and specific definitions of all points supported. 81 V4.42, December 16, 2007 5.2.1 Setting BAUD Rate The BAUD rate of the RS-485 interface can be changed in steps of 1200, 2400, 9600, or 19200. To change this setting, enter PROGRAM mode from the front panel as discussed in Section 4.1. To set the BAUD RATE from the front panel, press the or arrow button until the setting 079 is displayed: PRGM SETTING 079 BAUD RATE= 1200 Press the YES button. The first character will flash. Use the or arrow buttons to scroll between 1200, 2400, 9600 and 19200. PRGM SETTING 079 BAUD RATE= 9600 Press YES when you have made the correct selection. For programming from a PC, enter PROGRAM through the main menu as discussed in Section 4.2. Once in PROGRAM, type the setting for the BAUD RATE on the “Enter:” line as follows: Enter:87/2 This will change the BAUD RATE to 9600. Type 0 to change the BAUD RATE to 1200, 1 to change to 2400, or 3 to change to 19200. 5.2.2 Setting NODE Address A unique node address of 0 to 65535 can be entered. Please refer to your DNP3.0 Technical Reference documents as certain node addresses are reserved. To change this setting, enter PROGRAM mode from the front panel as discussed in Section 4.1. To set the node address from the front panel, press the or arrow button until the setting 080 is displayed: PRGM SETTING 080 NODE ADDR=00000 Press the YES button. The first digit will flash. Use the or arrow buttons to scroll through the digits 0 – 9. Use the or buttons to scroll between the 82 V4.42, December 16, 2007 digits. Each digit moved to will flash. Press YES after you have entered all four digits. For programming from a PC, enter PROGRAM through the main menu as discussed in Section 4.2. Once in PROGRAM, type the setting for the node address on the “Enter:” line as follows: Enter:88/7 This will set the node address to 7. 5.2.3 Setting Remote Blocking Remote block is useful if it is necessary to block remote control of any of the output relays. This is only necessary if Objects 10 and 12 have been implemented to permit Supervisory and Control to command cooling remotely. To change this setting, enter PROGRAM mode from the front panel as discussed in Section 4.1. To set the node address from the front panel, press the or arrow button until the setting 081 is displayed: PRGM SETTING 081 REMOTE BLK=DSABL Press the YES button. The first character will flash. Use the or arrow buttons to scroll between DSABL (disable) and ENABL (enable). PRGM SETTING 081 REMOTE BLK =ENABL Press YES when you have made the correct selection. Selecting ENABL will block the remote control of the output relays. For programming from a PC, enter PROGRAM through the main menu as discussed in Section 4.2. Once in PROGRAM, type the setting for remote block on the “Enter:” line as follows: Enter:89/1 This will enable remote block. Type 0 to disable remote block. 5.3 Telemetry Via RS232 Asynchronous data communications is implemented through the front panel mounted DB-9 connector at a fixed data rate of 9600 bits per second, 8 bits of 83 V4.42, December 16, 2007 data, no parity, and one stop bit. We have verified operation of the interface with Procomm Plus, HyperTerminal and Windows Terminal 3.1. It is recommended that the terminal emulation be set for either ANSI or TTY. The pin out of this port is designed to use a 9 pin female to 9 pin male null modem cable. The TTC-1000 permits remote reporting of temperature or resetting of the time of day by sending a forward slash ‘/’ followed by either the characters T (temperature) or R (reset) followed by an ASCII carriage return character (13 Hex). Sending the string: /T causes the TTC-1000 to reply with the ambient temperature. The temperature reported will be in the units (Celsius or Fahrenheit) that the TTC-1000 was programmed to display temperature. Units are not transmitted. It is noted that the command /T is echoed back to the host computer along with the measured temperature without a carriage return character. For example, if the TTC-1000 is measuring an ambient temperature of 68 ºF, the exact format of the reply for a single probe unit is: 68 For dual probe versions, the reply is: 68/93 Where the first temperature is probe #1 and the second is probe #2. Sending the string /S causes the TTC-1000 to report the status of the output relays (OUT1, OUT2, OUT3 and OUT4) and alarm type (DEVICE, TPROBE, and WDGCKT) as a series of ASCII character ‘0’ for off and ASCII character ‘1’ for on. The string reported is as follows: OUT1/OUT2/OUT3/OUT4/ALRM_DEVICE/ALRM_TPROBE/ALRM_WNDCKT A typical response to the /S command is: 1/0/0/0/0/0/0 This string indicates that OUT1 is picked up and OUT2, OUT3, OUT4, ALRM_TPROBE, ALRM_TPROBE, and ALRM_WNDCKT are dropped out. Sending the string /R causes the TTC-1000 to reset the real time clock to 00:00:00 hours. The date is not changed. It is noted that the characters /R are echoed back to the host computer. 84 V4.42, December 16, 2007 6 VIEW TEMPERATURES The temperature & time display will be the first display you see upon power up. Date, time, and temperature are updated when fresh data is available. The display will continuously scroll through a set sequence. The sequence will depend on the number of liquid temperature probe channels and if the unit is equipped to measure calculated winding temperature. Automatic scrolling can be interrupted at any time by pressing the YES button. Once automatic scrolling is stopped, pressing the or arrow buttons will permit manual scrolling to the various displays. To resume automatic scrolling, press the NO button. NOTE: The unit will return to the automatic scrolling from any menu after one minute of inactivity. Activity is defined as any button being pressed. 6.1 Single Probe For single probe units, model number –XX1X the display sequence will appear as follows: 07/29/03 13:15 P1 TOP OIL 45C TOP OIL MIN= 35C @ 03:15 07/29/03 TOP OIL MAX= 65C @ 17:42 07/18/03 RST MIN/MAX PUSH YES TO RST The name set for P1 will appear on the display as shown above. 85 V4.42, December 16, 2007 6.2 Dual Probe For dual probe units, model number –XX2X the display sequence will appear as follows: 07/29/03 13:15 P1 TOP OIL 45C 07/29/03 13:15 P2 WINDING 58C TOP OIL MIN= 35C @ 03:15 07/29/03 TOP OIL MAX= 65C @ 17:42 07/18/03 WINDING MIN= 43C @ 03:15 07/29/03 WINDING MAX= 83C @ 17:42 07/18/03 RST MIN/MAX PUSH YES TO RST The name set for P1 and P2 will appear on the display as shown above. 86 V4.42, December 16, 2007 6.3 Single Probe With Calculated Winding For single probe units with calculated winding temperature, model number – XX3X the display sequence will appear as follows: 07/29/03 13:15 P1 TOP OIL 45C 07/29/03 13:15 WINDING 58C 07/29/03 13:15 LOAD 453 A TOP OIL MIN= 35C @ 03:15 07/29/03 TOP OIL MAX= 65C @ 17:42 07/18/03 WINDING MIN= 43C @ 03:15 07/29/03 WINDING MAX= 83C @ 17:42 07/18/03 RST MIN/MAX PUSH YES TO RST The name set for P1 will appear on the display as shown above. 87 V4.42, December 16, 2007 6.4 Dual Probe With Calculated Winding For dual probe units with calculated winding temperature, model number –XX4X the display sequence will appear as follows: 07/29/03 13:15 P1 TOP OIL 45C 07/29/03 13:15 P2 LTCDIFF - 03C 07/29/03 13:15 LOAD 453 A 07/29/03 13:15 WINDING 58C TOP OIL MIN= 35C @ 03:15 07/29/03 TOP OIL MAX= 65C @ 17:42 07/18/03 LTCDIFF MAX= 02C @ 17:42 07/18/03 LTCDIFF MIN= -08 C @ 03:15 07/29/03 WINDING MIN= 43C @ 03:15 07/29/03 WINDING MAX= 83C @ 17:42 07/18/03 RST MIN/MAX PUSH YES TO RST The name set for P1 and P2 will appear on the display as shown above. 88 V4.42, December 16, 2007 6.5 Reset Min/Max The minimum and maximum registers may be reset by pressing the YES button when the display is showing: RST MIN/MAX PUSH YES TO RST To confirm that the min/max values are reset, the display will read: MIN/MAX IS RST New data will be recorded as soon as the data is ready. 89 V4.42, December 16, 2007 7 VIEW SETTINGS View allows display of settings without entering PROGRAM. Settings may be viewed from the front panel or via a PC. 7.1 View Settings Via Front Panel To view settings from the front panel, first press the or arrow buttons until the VIEW Settings screen is displayed: VIEW SETTINGS PUSH YES TO VIEW Pressing the YES button will allow you to scroll through each parameter by using the or arrow buttons. By pressing NO you will bounce back to the above display. 7.2 View Settings Via PC To view settings via a PC, first press the Enter key to display the Main Menu. When the user presses 1 followed by the Enter key, the user will see the following display: VIEW 01 SP11 PICKUP=00 øC 02 SP11 DRPOUT=00 øC 03 SP12 PICKUP=00 øC 04 SP12 DRPOUT=00 øC 05 SP13 PICKUP=00 øC 06 SP13 DRPOUT=00 øC 07 SP14 PICKUP=00 øC 08 SP14 DRPOUT=00 øC 09 SP21 PICKUP=00 øC 10 SP21 DRPOUT=00 øC 11 SP22 PICKUP=00 øC 12 SP22 DRPOUT=00 øC 13 SP23 PICKUP=00 øC 14 SP23 DRPOUT=00 øC 15 SP24 PICKUP=00 øC 16 SP24 DRPOUT=00 øC 17 WSP1 PICKUP=00 øC 18 WSP1 DRPOUT=00 øC 19 WSP2 PICKUP=00 øC 20 WSP2 DRPOUT=00 øC 21 WSP3 PICKUP=00 øC 22 WSP3 DRPOUT=00 øC 23 WSP4 PICKUP=00 øC 24 WSP4 DRPOUT=00 øC 25 LTCDIFF PICKUP=00 øC 26 LTCDIFF DRPOUT=00 øC 27 LTCDIFF PICKUPTMR=00 28 LSP1 PICKUP=0.0 A 29 LSP1 DRPOUT=0.0 A MIN 90 V4.42, December 16, 2007 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 LSP2 PICKUP=0.0 A LSP2 DRPOUT=0.0 A LOAD PICKUP TMR1 =00 sec LOAD PICKUP TMR2 =00 sec IN1 CTRL=LEVEL (0) IN2 CTRL=LEVEL (0) OUT1 PICKUP TMR=00 sec OUT1 AUTO (0) OUT1 UNCHG (0) w/ALRM OUT2 PICKUP TMR=00 sec OUT2 AUTO (0) OUT2 PCKUP (1) w/ALRM OUT3 PICKUP TMR=00 sec OUT3 AUTO (0) OUT3 PCKUP (1) w/ALRM OUT4 PICKUP TMR=00 sec OUT4 AUTO (0) OUT4 PCKUP (1) w/ALRM SP11 Not Assigned SP12 Not Assigned SP13 Not Assigned SP14 Not Assigned SP21 Not Assigned SP22 Not Assigned SP23 Not Assigned SP24 Not Assigned LTC Not Assigned WSP1 Not Assigned WSP2 Not Assigned WSP3 Not Assigned WSP4 Not Assigned LSP1 Not Assigned LSP2 Not Assigned OUT1 Not Assigned OUT2 Not Assigned OUT3 Not Assigned OUT4 Not Assigned IN1 Not Assigned IN2 Not Assigned TIME1 00:00 TO 00:00 Not Assigned TIME2 00:00 TO 00:00 Not Assigned TIME3 00:00 TO 00:00 Not Assigned OUT1 =INVERT (1) OUT2 =Not INVERT (0) OUT3 =Not INVERT (0) OUT4 =Not INVERT (0) CT RATIO=00 RATED LOAD=00 A WINDING RISE @ RATED LOAD=00 øC WINDING TC=00 MIN COOLING TYPE=Not DIRECTED FOA (0) TPROBE1 NAME=TOP OIL (0) TPROBE2 NAME=LTCDIFF (3) ALTERNATE=DSABL (0) ANALGOUT=N/A A1 SOURCE=P1 (0) A2 SOURCE=P1 (0) BAUD RATE= 1200 (0) 91 V4.42, December 16, 2007 88 NODE ADDR=00 89 REMOTE BLK=DSABL (0) 90 TIMEBASE=00 sec 91 INCLUDE P1 IN LOG=NO (0) 92 INCLUDE P2 IN LOG=NO (0) 93 INCLUDE WINDING IN LOG=NO (0) 94 INCLUDE LOAD IN LOG=NO (0) 95 TIME=17:05 96 DATE=07/29/03 97 WNDCKT ALRM ENABLED (0) 98 DEVICE ALRM ENABLED (0) 99 TEMPERATURE ALRM ENABLED (0) 100 MANUAL ALRM ENABLED (0) 101 TIME SP CNTR=00 102 UNIT ID= 103 NEG ANALGOUT SCALING=NO (0) 104 LTCDIFF RISE=00 øC 105 LTCDIFF RATE=00 MIN After transmitting the data to the host computer, the TTC-1000 automatically logs off. The user must press the Enter key to re-display the Main Menu. NOTE: In single probe units, TEMP PROBE2 NAME=N/A. 92 V4.42, December 16, 2007 8 STATUS STATUS allows you to take a snapshot of the recognized state of any output, temperature set points, LOAD, LTCDIFF set points, time set points and optically isolated inputs. In the case of outputs, this will be the state of the programmable logic. This may not be the state of the output relay as it may be controlled either manually or remotely. 8.1 View Status Via Front Panel To view settings from the front panel, first press the or arrow buttons until the VIEW Status screen is displayed: VIEW STATUS PUSH YES TO VIEW To view the status of each operand you must first press YES. After pressing YES you can use the or arrow buttons to scroll between the operands. Pressing NO at any time will bounce you out of the display of status. 8.2 View Status Via PC To view settings via a PC, first press the Enter key to display the Main Menu. When the user presses 3 followed by the Enter key, the user will see the following display: STATUS TIME=23:04 DATE=05/26/05 UNIT ID=TX2767 TEMPERATURE TOP OIL/LTCDIFF/WINDING 23/00/23 øC LOAD=00 A TOP OIL MIN=23 øC @ 16 07/29/03 TOP OIL MAX=23 øC @ 16:49 07/29/03 LTCDIFF MIN=00 øC @ 16:49 07/29/03 LTCDIFF MAX=00 øC @ 16:49 07/29/03 WINDING MIN=23 øC @ 16:49 07/29/03 WINDING MAX=23 øC @ 16:49 07/29/03 SP11=PICKED UP SP12=PICKED UP SP13=PICKED UP SP14=PICKED UP SP21=PICKED UP SP22=PICKED UP SP23=PICKED UP SP24=PICKED UP LTC=PICKED UP WSP1=PICKED UP WSP2=PICKED UP WSP3=PICKED UP WSP4=PICKED UP LSP1=PICKED UP LSP2=PICKED UP 93 V4.42, December 16, 2007 IN1=DRP'D OUT IN2=DRP'D OUT OUT1=PICKED UP OUT2=DRP'D OUT OUT3=DRP'D OUT OUT4=DRP'D OUT TIME1=DRP'D OUT TIME2=DRP'D OUT TIME3=DRP'D OUT LTCR-R=DRP’D OUT You must press the Enter key on your keyboard to display the Main Menu. 94 V4.42, December 16, 2007 9 SETTING FILES Uploading and downloading of setting files can only be accomplished through connection from a PC directly connected to the TTC-1000. To save a setting file on your PC use Upload Setting file. To transfer a previously stored setting file from your PC to the TTC-1000, use Download Setting file. 9.1 Upload Setting Files Upload settings transfers the binary settings to a designated file in a PC connected through the RS232 communications port. The TTC-1000 uses the XMODEM protocol which is supported by HyperTerminal, HyperAccess, as well as other terminal emulation programs. Checksum error checking is employed. 9.1.1 Upload Settings Using HyperTerminal HyperTerminal as supplied in Windows XP does not work properly when scrolling back to view settings and is not recommended. The following instructions apply to both versions. In these instructions, HyperTerminal will stand for both versions, XP and Private Edition. The procedure to upload a setting file is as follows: 1. Press Enter to display the TTC-1000 Main Menu. 2. Press 4 and then press Enter: 3. Click on Transfer on the HyperTerminal toolbar, a drop down menu will appear – a. Click on Receive File and a dialog box will open b. Select Xmodem from the Use Receiving Protocol option c. Click on the Browse button and another dialog box will open where the directory can be selected to place the file. d. Click on Receive 4. Another dialog box will open for entering the file name the file is to be saved as. a. Enter the file name and click on OK The three letter suffix will not automatically be added. It is a good practice to add an ending such as .BIN or .DAT to indicate it is not a text file. . 5. Another dialog box will open that shows the file transfer progress a. HyperTerminal will try twice with CRC error detection to transfer the file. The third attempt will be using Checksum, the method the TTC1000 uses. b. The retry box will briefly show 3 and then the box will disappear. This means the file has been saved. c. If the number of retries exceeds 3, cancel and start over. At this point the transfer will not take place. Recheck your settings. 95 V4.42, December 16, 2007 d. If the main TTC-1000 menu returns to the HyperTerminal window, the transfer has timed out and the procedure must be restarted. 6. Even if the HyperTerminal transfer times out, continue with the procedure up until the transfer progress dialog box appears. This will save your settings as far as protocol and directory so that it will not need to be reentered, thus speeding up the process and avoiding another timeout. NOTE: Upload can be terminated by pressing the Esc key on your PC prior to starting the file transfer. 9.1.2 Upload Settings Using HyperAccess The procedure to upload a setting file is as follows: 1. Press Enter to display the TTC-1000 Main Menu. 2. Press 4 and then press Enter: 3. Click on Transfer on the HyperAccess toolbar, a drop down menu will appear – a. Click on Receive File and a dialog box will open b. Click on the Browse button and another dialog box will open where the directory can be selected to place the file. c. Select Xmodem from the Transfer Protocol option i. Click on the Settings button ii. A dialog box will open where you can select the Error Checking mode iii. Select Checksum (This setting can be left in Auto, but the program will try twice with CRC until it tries Checksum) d. Click on Receive 4. Another dialog box will open for entering the file name the file is to be saved as. a. Enter the file name and click on OK. The three letter suffix will not automatically be added. It is a good practice to add an ending such as .BIN or .DAT to indicate it is not a text file. 5. Another dialog box will open that shows the file transfer progress. If the main TTC-1000 menu returns to the HyperAccess window, the transfer has timed out and the procedure must be restarted. 6. Even if the HyperAccess transfer times out, continue with the procedure up until the transfer progress dialog box appears. This will save your settings as far as protocol and directory so that it will not need to be reentered, thus speeding up the process and avoiding another timeout. 96 V4.42, December 16, 2007 9.2 Download Setting Files Download settings transfers the binary setting file on your PC to the TTC-1000 connected through the RS232 communications port. The TTC-1000 uses the XMODEM protocol which is supported by HyperTerminal and HyperAccess as well as other terminal emulation programs. Checksum error checking is employed. NOTE: Be careful that the file sent is NOT a text file and is a valid settings file. Transferring a text version of a settings file into the TTC-1000 will cause the settings to be overwritten by text characters causing unpredictable behavior. To recover from this situation, download a known good settings file to overwrite the text. The master password 0905 will need to be used to regain access. Should this not work, please contact us for assistance. NOTE: Download may be terminated prior to the transfer by pressing any key on the keyboard NOTE: The TTC-1000 will suspend all measurements and calculations once downloading is selected. The outputs will also be blocked during this time. The TTC-1000 transfers the new settings to a buffer register and will transfer the settings to E2 memory only after the checksum test is passed. 9.2.1 Download Settings Using HyperTerminal The procedure to download a setting file is as follows: 1. Press Enter to display the TTC-1000 Main Menu 2. Type 5 followed by / followed by the 4 digit password: a. Note that at any time the internal data in the unit is to be changed, the password will need to be entered. 3. Click on Transfer on the HyperTerminal toolbar a. A drop down menu will appear b. Click on the Send File option 4. A dialog box will open to select the location and name of the file to be transferred. a. Make sure Xmodem is selected in the Protocol window b. Click on Browse to select the directory and then the file to be sent. c. The Send button will now be selectable, click on it. 5. A dialog box will appear to track the transfer progress. 6. The dialog box will disappear and a note will appear in the terminal window that the transfer was successful. 97 V4.42, December 16, 2007 9.2.2 Download Settings Using HyperAccess The procedure to download a setting file is as follows: 7. Press Enter to display the TTC-1000 Main Menu 8. Type 5 followed by / followed by the 4 digit password: a. Note that at any time the internal data in the unit is to be changed, the password will need to be entered. 9. Click on Transfer on the HyperAccess toolbar a. A drop down menu will appear b. Click on the Send File option 10. A dialog box will open to select the location and name of the file to be transferred. a. Click on Browse to select the directory and then the file to be sent. b. Make sure Xmodem is selected in the Protocol window c. Click on the Settings button to make sure the error checking is set to Checksum d. Click on the Send button. 11. A dialog box will appear to track the transfer progress. 12. The dialog box will disappear and a note will appear in the terminal window that the transfer was successful. NOTE: The TTC-1000 will suspend all measurements and calculations once downloading is selected. The outputs will also be blocked during this time. The TTC-1000 transfers the new settings to a buffer register and will transfer the settings to E2 memory only after the checksum test is passed. 98 V4.42, December 16, 2007 10 DATA LOGGING Data logging permits storage of time stamped temperature and load data. The user has the ability to change the time base used for time stamping from 1 to 9999 seconds. Setting the time base to zero erases the log and prevents records from being recorded. The user can select which points to record. Points which can be recorded include probe P1’s temperature, P2’s temperature, calculated winding temperature, and load. Once the log is full, the oldest records are over written with the newest records. Since the records are stored in non-volatile memory, records are never lost even in the event of a power interruption. 10.1 Data Storage There are 32,512 bytes available for storage of data records. A byte is defined as an 8 bit quantity. Each record is time stamped at an interval defined as the Time Base. A data record is defined as a set of data points. Data points can include probe P1’s temperature, P2’s temperature, calculated winding temperature, and load. All temperatures are stored as a single byte. Load is stored as a two byte quantity. There are two additional bytes per record to assist the firmware in storing and retrieving the data log. A record can be anywhere from 3 bytes to 7 bytes in length. The following table summarizes the available data points and the maximum number of records that can be stored: Points Recorded Bytes/Record Max Records P1, or P2, or Calculated Winding 3 10,837 Any two temperatures 4 8,128 Any one temperature and Load 5 6,502 P1 and P2 and Calculated Winding 6 5,418 Any two temperatures and Load 6 5,418 All three temperatures and Load 7 4,644 Table 10. 1: Maximum Records After selecting the data points to log, it is simple to figure out the length of time data can be recorded. For example if 30 minutes time stamping is required, Time Base=1800, and all four points (P1, P2, Winding & Load) are required, the maximum time that data can be recorded in days is equal to 4,644 divided by 48 records per day or 96 days. This can be extended to up to 1254 days if only one temperature is recorded every 9999 seconds or ~2.75 hours. Practically speaking, a temperature and load will be logged every hour or 3600 seconds. In this case the log will hold 270 days of data. There is one limitation, in the event that power is interrupted, the time stamp is stored as a data record. Time stamp records consume a total of 8 bytes. This is a 99 V4.42, December 16, 2007 non-factor if power is never interrupted, but if the device is AC powered, it could reduce the number of records by a small amount. 10.2 Data Points Data recorded can be selected for logging. For P1 or P2, the data recorded takes the name chosen for the specific temperature probe. If P1 or P2 is chosen as LTCDIFF, the data recorded is the differential between the LTC tank temperature and the Top Oil probe. All other temperature points are recorded as the absolute value of the measured temperature. The load current reported is the average or demand logged for the period between samples. If a Time Base of 15 minutes is selected, the load current is the average value over 15 minutes. For Time Base settings less than 16 seconds, the load current reported will be the actual load current. 10.3 Setting the Time Base Time Base can be entered from 0 to 9999 seconds. Setting the Time Base to zero will reset the log and no records will be logged. Changing the Time Base will erase the log and commence recording with the new Time Base. To change this setting, enter PROGRAM mode from the front panel as discussed in Section 4.1. To set the time base from the front panel, press the or arrow button until the setting 082 is displayed: PRGM SETTING 082 TIMEBASE=0000sec Press the YES button. The first digit will flash. Use the or arrow buttons to scroll through the digits 0 – 9. Use the or buttons to scroll between the digits. Each digit moved to will flash. Press YES after you have entered all four digits. For programming from a PC, enter PROGRAM through the main menu as discussed in Section 4.2. Once in PROGRAM, type the setting for the time base on the “Enter:” line as follows: Enter:90/3600 This will set the Time Base to 3600 seconds. 10.4 Selecting Data Points Any or all of the data points can be selected for logging. Change the number of points or the points recorded will erase the log. If no points are selected the log will be erased and no data logged. There are four points that can be added to the 100 V4.42, December 16, 2007 log: P1, P2, Calculated Winding, and Load. The heading names for probes P1 and P2.in the data log will be as displayed on the front panel. 10.4.1 Add or Delete P1 From Log To change this setting, enter PROGRAM mode from the front panel as discussed in Section 4.1. To set the P1 RECORD from the front panel, press the or arrow button until the setting 083 is displayed: PRGM SETTING 083 P1 RECORD =NO Press the YES button. The first character will flash. Use the or arrow buttons to scroll between YES and NO. For programming from a PC, enter PROGRAM through the main menu as discussed in Section 4.2. Once in PROGRAM, type the setting for P1 RECORD on the “Enter:” line as follows: Enter:91/1 This will add P1 to the log. Type 0 to remove from the log. 10.4.2 Add or Delete P2 From Log To change this setting, enter PROGRAM mode from the front panel as discussed in Section 4.1. To set the P2 RECORD from the front panel, press the or arrow button until the setting 084 is displayed: PRGM SETTING 084 P2 RECORD =NO Press the YES button. The first character will flash. Use the or arrow buttons to scroll between YES and NO. For programming from a PC, enter PROGRAM through the main menu as discussed in Section 4.2. Once in PROGRAM, type the setting for P2 RECORD on the “Enter:” line as follows: Enter:92/1 This will add P2 to the log. Type 0 to remove from the log. 101 V4.42, December 16, 2007 10.4.3 Add or Delete Calculated Winding From Log To change this setting, enter PROGRAM mode from the front panel as discussed in Section 4.1. To set the WNDGRECORD from the front panel, press the or arrow button until the setting 085 is displayed: PRGM SETTING 085 WNDGRECORD =NO Press the YES button. The first character will flash. Use the or arrow buttons to scroll between YES and NO. For programming from a PC, enter PROGRAM through the main menu as discussed in Section 4.2. Once in PROGRAM, type the setting for Calculated Winding Record on the “Enter:” line as follows: Enter:93/1 This will add Calculated Winding to the log. Type 0 to remove from the log. 10.4.4 Add or Delete Load From Log To change this setting, enter PROGRAM mode from the front panel as discussed in Section 4.1. To set the LOAD RECORD from the front panel, press the or arrow button until the setting 086 is displayed: PRGM SETTING 086 LOADRECORD =NO Press the YES button. The first character will flash. Use the or arrow buttons to scroll between YES and NO. For programming from a PC, enter PROGRAM through the main menu as discussed in Section 4.2. Once in PROGRAM, type the setting for LOAD RECORD on the “Enter:” line as follows: Enter:94/1 This will add Load to the log. Type 0 to remove from the log. 102 V4.42, December 16, 2007 10.5 Viewing the Data Log The data log can be viewed on a PC through the RS-232 interface. Downloading the data log does not erase the log. The data log is recieved as a comma delimited ASCII data. It can be captured for use in other programs as shown in the next section. To view the log via a PC, open the terminal emulation program with the settings used to access the main TTC-1000 menu. First press the Enter key to display the Main Menu: Advanced Power Technologies, LLC; (C) 2001-2005 Transformer Temperature Controller V5.3XX Select: 1. VIEW 2. PROGRAM (2/XXXX) 3. STATUS 4. UPLOAD SETTINGS 5. DOWNLOAD SETTINGS (5/XXXX) 6. DOWNLOAD DATA LOG 7. DOWNLOAD SOFTWARE PATCH, DATA LOG WILL BE ERASED (7/XXXX) 8. LOG OFF Enter Code: Enter menu option 6 and press Enter, the data log will be sent to the PC. If no data is logged the data reported through the terminal emulation program will show: NO DATA END OF REPORT. STOP TEXT CAPTURE & PRESS 'Enter' Should the log contain data, the terminal emulation program will show: DATE,TIME,TOP OIL,WINDING,LOAD 07/31/03,08:46:03,49 ,49 ,930 07/31/03,08:36:03,49 ,49 ,931 07/31/03,08:26:03,49 ,49 ,932 07/31/03,08:16:03,49 ,49 ,934 07/31/03,08:06:03,49 ,49 ,937 07/31/03,07:56:03,49 ,49 ,940 END OF REPORT. STOP TEXT CAPTURE & PRESS 'Enter' The first line is the header for the data reported. The last character is a carriage return (CR) character, hex 013, and line feed (LF), hex 011. Each subsequent line is the comma delimited data followed by a CR and LF characters. 103 V4.42, December 16, 2007 10.6 Saving the Data Log as a Text File Using HyperTerminal To capture the text using HyperTerminal, do the following: 1. Press 6 but DO NOT press Enter yet. 2. From the toolbar, select Transfer 3. Select Capture Text from the drop down menu, a dialog box will open 4. From the dialog box, browse to the location the file is to be saved and provide a file name. The program will automatically add .TXT to the end of the name. 5. Click on Save and the Capture Text dialog box will re-appear. 6. Click on Start 7. Press Enter, the data will now scroll through the screen and be recorded with the file name supplied. 10.7 Import Data Log as a Comma Delimited Text File Using HyperAccess To capture the text using HyperAccess, do the following: 1. Press 6 but DO NOT press Enter yet. 2. From the toolbar, select File 3. Select Capture to File from the drop down menu, and then select Start from the next menu 4. A dialog box will open 5. From the dialog box, browse to the location the file is to be saved and provide a file name. The program will automatically add .TXT to the end of the name. 6. Click on Start 7. Press Enter, the data will now scroll through the screen and be recorded with the file name supplied. 8. Once the data has stopped scrolling, again select File from the toolbar and then Capture to File from the drop down menu. 9. Select Stop from the next menu, the file is now saved and closed. 104 V4.42, December 16, 2007 10.8 Import to Excel The text file captured can be imported into excel for plotting and sorting. It is a good idea to open the text file in Notepad to delete any extra characters before trying to import the file into excel. 1. Open Excel. Click on File and click on Open: 105 V4.42, December 16, 2007 2. Go to the Path where the text file is stored and select Files of Type: Text Files, Double Click the file name and Click Open: 3. Click the Delimited button and click Next: 106 V4.42, December 16, 2007 4. Check the Comma box in Delimiters. Make sure all other boxes are unchecked: 5. Click the General button in the Column data format and click Finish: 107 V4.42, December 16, 2007 6. After closing the import wizard, the text data will display: The data is now ready for graphing. 108 V4.42, December 16, 2007 11 DOWNLOAD PROGRAM UPDATES The TTC-1000 firmware contains a boot loader that allows the user to download new firmware. Downloading firmware will erase the data log. Firmware can be downloaded to a PC through the RS-232 interface. Firmware patches must be obtained from Advanced Power Technologies and are only available for units with TTMV4.XX firmware. To download firmware via a PC, open your terminal emulation program.. It is recommended that the terminal emulation be set for either ANSI or TTY. The pin out of this port is designed to use a 9 pin female to 9 pin male null modem cable. You will need to configure your terminal emulation program before you get started. First press the Enter key to display the Main Menu: Advanced Power Technologies, LLC; (C) 2001-2003 Transformer Temperature Controller V4.3XX Select: 1. VIEW 2. PROGRAM (2/XXXX) 3. STATUS 4. UPLOAD SETTINGS 5. DOWNLOAD SETTINGS (5/XXXX) 6. DOWNLOAD DATA LOG 7. DOWNLOAD SOFTWARE PATCH, DATA LOG WILL BE ERASED (7/XXXX) 8. LOG OFF Enter Code: Type 7/ followed by the password programmed or the super user password. Press the Enter key. If the terminal emulation screen clears, you have entered an incorrect password. Otherwise the screen will display: FIRMWARE FILE TRANSFER IN PROGRESS. PRESS Any KEY TO ABORT. §§§§ Also, the front panel display will show: PLEASE WAIT LOADING FIRMWARE 109 V4.42, December 16, 2007 The user has approximately 90 seconds to find the file and start the download process. The user will see the following message on the PC if they are unable to locate the file in the allotted time: FIRMWARE FILE TRANSFER IN PROGRESS. PRESS Any KEY TO ABORT. §§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§§ DOWNLOAD Not SUCCESSFUL. PRESS 'Enter' KEY 11.1 Download Firmware Using HyperTerminal To download firmware using HyperTerminal: 1. Click Transfer on the toolbar and click Send File: 2. A dialog box will open a. Click on the Browse button and navigate to the file to be sent. b. Make sure that Xmodem is selected for the Protocol. c. Click on Send, the dialog box will close. 3. A new dialog box will open to show the file download progress. 4. Once the file is downloaded, the dialog box will close. 4. If the transfer is successful, a message will appear in the terminal window that the transfer was successful and to wait 15 seconds. During this time, the new firmware is loaded into program memory and the controller is restarted 5. Press enter after about 15 seconds to re-display the main menu.: 6. If the Main Menu does not appear, check the front panel display to see if the display is scrolling. If not de-energize the unit and re-energize. Wait 15 seconds. If the unit does not respond after 15 seconds call the factory at (866) 563-6600 for assistance. 11.2 Download Firmware HyperAccess To download firmware using HyperTerminal 1. Click Transfer on the toolbar and click Send File(s): 2. A dialog box will open a. Click on the Browse button and navigate to the file to be sent. b. Make sure that Xmodem is selected for the Protocol. c. Click on Send, the dialog box will close. 3. A new dialog box will open to show the file download progress. 4. Once the file is downloaded, the dialog box will close. 7. If the transfer is successful, a message will appear in the terminal window that the transfer was successful and to wait 15 seconds. During this time, 110 V4.42, December 16, 2007 the new firmware is loaded into program memory and the controller is restarted 8. Press enter after about 15 seconds to re-display the main menu.: 9. If the Main Menu does not appear, check the front panel display to see if the display is scrolling. If not de-energize the unit and re-energize. Wait 15 seconds. If the unit does not respond after 15 seconds call the factory at (866) 563-6600 for assistance. 111 V4.42, December 16, 2007 12 Front Panel Setting SheetsThe following worksheet is a comprehensive list of all the settings programmable through the Front Panel interface and possible settings. A blank space is provided to write-in the desired setting: Setting # 001 Setting SP11PICKUP Purpose Probe #1 pickup Setting Range or Factory Values Default -35 to 160 C 0 -35 to 160 C 0 -35 to 160 C 0 -35 to 160 C 0 -35 to 160 C 0 -35 to 160 C 0 -35 to 160 C 0 -35 to 160 C 0 -35 to 160 C 0 -35 to 160 C 0 -35 to 160 C 0 -35 to 160 C 0 -35 to 160 C 0 Program to temperature 002 SP11DRPOUT Probe #1 dropout temperature 003 SP12PICKUP Probe #1 pickup temperature 004 SP12DRPOUT Probe #1 dropout temperature 005 SP13PICKUP Probe #1 pickup temperature 006 SP13DRPOUT Probe #1 dropout temperature 007 SP14PICKUP Probe #1 pickup temperature 008 SP14DRPOUT Probe #1 dropout temperature 009 SP21PICKUP Probe #2 pickup temperature 010 SP21DRPOUT Probe #2 dropout temperature 011 SP22PICKUP Probe #2 pickup temperature 012 SP22DRPOUT Probe #2 dropout temperature 013 SP23PICKUP Probe #2 pickup temperature 112 V4.42, December 16, 2007 Setting # 014 Setting SP23DRPOUT Purpose Probe #2 dropout Setting Range or Factory Values Default -35 to 160 C 0 -35 to 160 C 0 -35 to 160 C 0 Program to temperature 015 SP24PICKUP Probe #2 pickup temperature 016 SP24DRPOUT Probe #2 dropout temperature 017 CT RATIO Sets Primary CT ratio 0 to 9999 0 018 RATED LOAD Sets rated load current 0 to 65535 Amps 0 WINDINGRISE Set hotspot rise above 0 to 99 C 0 (functional only in top oil temperature at units equipped with rated load from aux CT) manufacturer's heat run 0 to 999 minutes 0 YES, NO NO -35 to 180 C 0 -35 to 180 C 0 -35 to 180 C 0 -35 to 180 C 0 (functional only in units equipped with aux CT) 019 data 020 021 WINDINGTC Sets winding time (functional only in constant from units equipped with manufacturer's heat run aux CT) data DIRECTED FOA Sets cooling type to (functional only in direct FOA/FOW units equipped with CT) 022 WSP1PICKUP Calculated winding set point pickup temperature 023 WSP1DRPOUT Calculated winding set point dropout temperature 024 WSP2PICKUP Calculated winding set point pickup temperature 025 WSP2DRPOUT Calculated winding set point dropout temperature 113 V4.42, December 16, 2007 Setting # 026 Setting WSP3PICKUP Purpose Calculated winding set Setting Range or Factory Values Default -35 to 180 C 0 -35 to 180 C 0 -35 to 180 C 0 -35 to 180 C 0 -20 to 20 C 0 -20 to 20 C 0 0 to 999 Minutes 0 Program to point pickup temperature 027 WSP3DRPOUT Calculated winding set point dropout temperature 028 WSP4PICKUP Calculated winding set point pickup temperature 029 WSP4DRPOUT Calculated winding set point dropout temperature 030 LTCDIFF PU (Not LTC Differential pickup functional in single temperature probe units) 031 LTCDIFF DO (Not LTC Differential drop out functional in single temperature probe units) 032 033 LTCPUTMR (Not LTC Differential pickup functional in single timer supervises probe units) LTCDIFF pickup LOADPUSP1 Load pickup set point 0.0 to 9.9 Amps 0.0 Load dropout set point 0.0 to 9.9 Amps 0.0 Load pickup set point 0.0 to 9.9 Amps 0.0 Load dropout set point 0.0 to 9.9 Amps 0.0 (functional only in units equipped with aux CT) 034 LOADDOSP1 (functional only in units equipped with aux CT) 035 LOADPUSP2 (functional only in units equipped with aux CT) 036 LOADDOSP2 (functional only in units equipped with aux CT) 114 V4.42, December 16, 2007 Setting # 037 Setting Setting Range or Factory Values Default Load pickup timer 0 to 255 seconds 0 Load pickup timer 0 to 255 seconds 0 IN1=LEVEL or Allows input to handle LEVEL or PULSE LEVEL PULSE pulses LEVEL or PULSES LEVEL Delays activation of an 0 to 255 seconds (Note: 0 output a 0 setting results in a LSP1PUTMR Purpose Program to (functional only in units equipped with aux CT) 038 LSP2PUTMR (functional only in units equipped with aux CT) 039 (functional only in units equipped with optically isolated inputs) 040 IN2=LEVEL or Allows input to handle PULSE pulses (functional only in units equipped with optically isolated inputs) 041 OUT1PUTMR 32msec delay) 042 OUT2PUTMR Delays activation of an 0 to 255 seconds (Note: output a 0 setting results in a 0 32msec delay) 043 OUT3PUTMR Delays activation of an 0 to 255 seconds (Note: output a 0 setting results in a 0 32msec delay) 044 OUT4PUTMR Delays activation of an 0 to 255 seconds (Note: output a 0 0 setting results in a 32msec delay) 115 V4.42, December 16, 2007 Setting # 045 Setting Purpose (!) SP11 (*/+) TO Assigns probe #1 set OUTn point to a specific output using a defined AND or Setting Range or Factory Values Default SP11 * OUT n ! SP11 * OUT n Program to SP11 * OUT0 SP11 + OUT n OR logic operator ! SP11 + OUT n where n=1,2,3,4 046 (!) SP12 (*/+) TO Assigns probe #1 set OUTn point to a specific output using a defined AND or SP12 * OUT n ! SP12 * OUT n SP12 * OUT0 SP12 + OUT n OR logic operator ! SP12 + OUT n where n=1,2,3,4 047 (!) SP13 (*/+) TO Assigns probe #1 set OUTn point to a specific output using a defined AND or SP13 * OUT n ! SP13 * OUT n SP13 * OUT0 SP13 + OUT n OR logic operator ! SP13 + OUT n where n=1,2,3,4 048 (!) SP14 (*/+) TO Assigns probe #1 set OUTn point to a specific output using a defined AND or SP14 * OUT n ! SP14 * OUT n SP14 * OUT0 SP14 + OUT n OR logic operator ! SP14 + OUT n where n=1,2,3,4 049 (!) SP21 (*/+) TO Assigns probe #2 set OUTn point to a specific output (Not functional in single probe units) using a defined AND or SP21 * OUT n ! SP21 * OUT n SP21 * OUT0 SP21 + OUT n OR logic operator ! SP21 + OUT n where n=1,2,3,4 116 V4.42, December 16, 2007 Setting # 050 Setting Purpose (!) SP22 (*/+) TO Assigns probe #2 set OUTn point to a specific output (Not functional in single probe units) using a defined AND or Setting Range or Factory Values Default SP22 * OUT n ! SP22 * OUT n Program to SP22 * OUT0 SP22 + OUT n OR logic operator ! SP22 + OUT n where n=1,2,3,4 051 (!) SP23 (*/+) TO Assigns probe #2 set OUTn point to a specific output (Not functional in single probe units) using a defined AND or SP23 * OUT n ! SP23 * OUT n SP23 * OUT0 SP23 + OUT n OR logic operator ! SP23 + OUT n where n=1,2,3,4 052 (!) SP24 (*/+) TO Assigns probe #2 set OUTn point to a specific output (Not functional in single probe units) using a defined AND or SP24 * OUT n ! SP24 * OUT n SP24 * OUT0 SP24 + OUT n OR logic operator ! SP24 + OUT n where n=1,2,3,4 053 (!) LTC (*/+) TO Assigns the LTC OUTn differential SP to a (Not functional in single probe units) LTC * OUT n specific output using a defined AND or OR logic operator ! LTC * OUT n LTC * OUT0 LTC + OUT n ! LTC + OUT n where n=1,2,3,4 054 (!) WSP1 (*/+) TO Assigns calculated OUTn winding set points to a (functional only in units equipped with aux CT) WSP1 * OUT n specific output using a defined AND or OR logic operator ! WSP1 * OUT n WSP1 * OUT0 WSP1 + OUT n ! WSP1 + OUT n where n=1,2,3,4 117 V4.42, December 16, 2007 Setting # 055 Setting Purpose (!) WSP2 (*/+) TO Assigns calculated OUTn winding set points to a (functional only in units equipped with aux CT) Setting Range or Factory Values Default WSP2 * OUT n specific output using a defined AND or OR logic operator ! WSP2 * OUT n Program to WSP2 * OUT0 WSP2 + OUT n ! WSP2 + OUT n where n=1,2,3,4 056 (!) WSP3 (*/+) TO Assigns calculated OUTn winding set points to a (functional only in units equipped with aux CT) WSP3 * OUT n specific output using a defined AND or OR logic operator ! WSP3 * OUT n WSP3 * OUT0 WSP3 + OUT n ! WSP3 + OUT n where n=1,2,3,4 057 (!) WSP4 (*/+) TO Assigns calculated OUTn winding set points to a (functional only in units equipped with aux CT) WSP4 * OUT n specific output using a defined AND or OR logic operator ! WSP4 * OUT n WSP4 * OUT0 WSP4 + OUT n ! WSP4 + OUT n where n= 1,2,3,4 058 (!) LSP1 (*/+) TO Assigns load set points OUTn to a specific output using (functional only in units equipped with a defined AND or OR LSP1 * OUT n ! LSP1 * OUT n LSP1 * OUT0 LSP1 + OUT n logic operator ! LSP1 + OUT n aux CT) where n=1,2,3,4 059 (!) LSP2 (*/+) TO Assigns load set points OUTn to a specific output using (functional only in units equipped with a defined AND or OR LSP2 * OUT n ! LSP2 * OUT n LSP2 * OUT0 LSP2 + OUT n logic operator ! LSP2 + OUT n aux CT) where n=1,2,3,4 118 V4.42, December 16, 2007 Setting # 060 Setting Purpose (!) IN1 (*/+) TO Assigns optically OUTn isolated input to a (functional only in units equipped with optically isolated specific output using a defined AND or OR logic operator Assigns optically OUTn isolated input to a units equipped with optically isolated Default ! IN1 * OUT n IN1 * OUT0 IN1 + OUT n ! IN1 + OUT n IN2 * OUT n specific output using a defined AND or OR logic operator ! IN2 * OUT n IN2 * OUT0 IN2 + OUT n ! IN2 + OUT n inputs) 062 Values Program to where n=1,2,3,4 (!) IN2 (*/+) TO (functional only in Factory IN1 * OUT n inputs) 061 Setting Range or where n=1,2,3,4 (!) OUT1 (*/+) TO Assigns an output to a OUTn specific output using a defined AND or OR logic OUT1 * OUT n ! OUT1 * OUT n OUT1 * OUT0 OUT1 + OUT n operator ! OUT1 + OUT n where n=1,2,3,4 063 (!) OUT2 (*/+) TO Assigns an output to a OUTn specific output using a defined AND or OR logic OUT2 * OUT n ! OUT2 * OUT n OUT2 * OUT0 OUT2 + OUT n operator ! OUT2 + OUT n where n=1,2,3,4 064 (!) OUT3 (*/+) TO Assigns an output to a OUTn specific output using a defined AND or OR logic OUT3 * OUT n ! OUT3 * OUT n OUT3 * OUT0 OUT3 + OUT n operator ! OUT3 + OUT n where n=1,2,3,4 119 V4.42, December 16, 2007 Setting # 065 Setting Purpose (!) OUT4 (*/+) TO Assigns an output to a OUTn specific output using a defined AND or OR logic Setting Range or Factory Values Default OUT4 * OUT n ! OUT4 * OUT n Program to OUT4 * OUT0 OUT4 + OUT n operator ! OUT4 + OUT n where n=1,2,3,4 066 TIMESETPOINT1 00:00-00:00 > OR's a time range to a Pickup and Dropout 00:00- specific output range: 00:00 to 23:59 00:00> (Military time) OUT0 OR's a time range to a Pickup and Dropout 00:00- specific output range: 00:00 to 23:59 00:00> (Military time) OUT0 OR's a time range to a Pickup and Dropout 00:00- specific output range: 00:00 to 23:59 00:00> (Military time) OUT0 OUT0,1,2,3,4 067 TIMESETPOINT2 00:00-00:00 > OUT0,1,2,3,4 068 TIMESETPOINT3 00:00-00:00 > OUT0,1,2,3,4 069 INVERT OUT1 Master output inversion OFF, ON OFF 070 INVERT OUT2 Master output inversion OFF, ON OFF 071 INVERT OUT3 Master output inversion OFF, ON OFF 072 INVERT OUT4 Master output inversion OFF, ON OFF 073 ALTERNATE Selects an output pair to DSABL, 1-2, 1-3, 1-4, 2- DSABL alternate between to 3, exercise fans 074 P1 NAME 2-4, 3-4 Probe #1 name TOP OIL, WINDING, TOP AMBIENT, LTCDIFF, OIL BOTMOIL 075 P2 NAME Probe #2 name TOP OIL, WINDING, TOP (optional) AMBIENT, LTCDIFF, OIL BOTMOIL (only in dual probe) 076 ANALGOUT Current loop current 0to1mA or 4to20mA 0to1mA range 120 V4.42, December 16, 2007 Setting # 077 Setting A1 SOURCE Purpose Setting Range or Factory Values Default Sets source for analog P1 (probe1), P2 (probe P1 output A1 2), WINDING Program to (calculated) 078 A2 SOURCE Sets source for analog P1 (probe1), P2 P1 output A2 (probe2), WINDING (calculated) 079 080 BAUD RATE NODE ADDR Sets baud rate for RS- 1200, 2400, 9600, 1200 485 interface 19200 Sets the node address 0 – 65535 0 Blocks remote control ENABL to block remote DSBL command control or DSABL to for DNP3.0 081 REMOTE BLK allow remote control 082 TIMEBASE Sets record time for data 0 - 9999 0 log 083 P1 RECORD Sets P1 for data log YES, NO NO 084 P2 RECORD Sets P2 for data log YES, NO NO 085 WNDGRECORD Sets Calculated Winding YES, NO NO Sets LOAD for data log YES, NO NO (functional only in Temperature for data log units equipped with aux CT) 086 LOADRECORD (functional only in units equipped with aux CT) 087 TIME Sets military time HH:MM 00:00 088 MONTH Sets month 1 to 12 00 089 DAY Sets day 1 to 31 00 090 YEAR Sets Year 00 to 99 00 091 DEVICEALRM Processor alarm enable ENABL for enabled or ENABL DSABL for disabled 121 V4.42, December 16, 2007 Setting # 092 Setting TPROBEALRM Purpose Setting Range or Factory Values Default Temperature ENABL for enabled or ENABL measurement alarm DSABL for disabled Program to enable 093 094 MANALRM WNDCKTALARM Manual mode alarm ENABL for enabled or enable DSABL for disabled Winding circuitry alarm ENABL for enabled or enable 095 ENABL ENABL DSABL for disabled OUT1(Action) Allows OUT1 to default OUT1UNCHGw/ALRM OUT1 w/ALRM when a DEVICE or does not allow OUT1 to UNCHG TPROBE alarm change state when w/ALRM Action: UNCHG, alarm PCKUP,SUPV OUT1PCKUPw/ALRM causes OUT1 to pickup when alarm OUT1SUPVw/ALRM drops out OUT1 when alarm 096 OUT2 (Action) Allows OUT2 to default OUT2UNCHGw/ALRM OUT2 w/ALRM when a DEVICE or does not allow OUT2 to UNCHG TPROBE alarm change state when w/ALRM Action: UNCHG, alarm PCKUP, SUPV OUT2PCKUPw/ALRM causes OUT2 to pickup when alarm OUT2SUPVw/ALRM drops out OUT2 when alarm 122 V4.42, December 16, 2007 Setting # 097 Setting Purpose Setting Range or Factory Values Default OUT3(Action) Allows OUT3 to default OUT3UNCHGw/ALRM OUT3 w/ALRM when a DEVICE or does not allow OUT3 to UNCHG TPROBE alarm change state when w/ALRM Action: UNCHG, Program to alarm PCKUP,SUPV OUT3PCKUPw/ALRM causes OUT3 to pickup when alarm OUT3SUPVw/ALRM drops out OUT3 when alarm 098 OUT4 (Action) Allows OUT4 default OUT4UNCHGw/ALRM OUT4 w/ALRM when a DEVICE or does not allow OUT4 to UNCHG TPROBE alarm change state when w/ALRM Action: UNCHG, alarm PCKUP, SUPV OUT4PCKUPw/ALRM causes OUT4 to pickup when alarm OUT4SUPVw/ALRM drops out OUT4 when alarm 099 TIME SP CNTR Sets time counter for 0 to 255 0 A six character name for Any six alphanumeric Blank unit characters Enables scaling of YES, NO NO 5 to 40 ºC (recommended) 0 1 to 255 minutes 0 Permits manual control AUTO, MAN OFF, MAN AUTO of OUT1 ON Time Setpoints operation 100 101 UNIT ID NEG ANALGOUT analog outputs for negative temperatures 102 LTCDIFF RISE Maximum LTCDIFF rise in time period LTCDIFF RATE 103 LTCDIFF RATE Time period in which LTCDIFF is examined 104 OUT1CTRL 123 V4.42, December 16, 2007 Setting # 105 106 107 108 Setting OUT2CTRL OUT3CTRL OUT4CTRL PASSWORD Purpose Setting Range or Factory Values Default Permits manual control AUTO, MAN OFF, MAN AUTO of OUT2 ON Permits manual control AUTO, MAN OFF, MAN of OUT3 ON Permits manual control AUTO, MAN OFF, MAN of OUT4 ON Allows access to 4 digits 124 Program to AUTO AUTO 0000 V4.42, December 16, 2007 13 PC Setting Sheets The following worksheet is a comprehensive list of all the settings programmable through the RS-232 interface and possible settings. A blank space is provided to write-in the desired setting: Setting # Setting Purpose Setting Range or Values 01 SP11 PICKUP Probe #1 set point 1/nnn #1 pickup where nnn=-35 to 160 temperature 02 SP11 DRPOUT Probe#1 set point#1 dropout SP12 PICKUP Probe #1, set point #2 pickup SP12 DRPOUT Probe #1 set point #2 dropout SP13 PICKUP Probe #1, set point #3 pickup SP13 DRPOUT Probe #1 set point #3 dropout SP14 PICKUP Probe #1, set point #4 pickup SP14 DRPOUT 7/nnn where nnn=-35 to 160 temperature 08 6/nnn where nnn=-35 to 160 temperature 07 5/nnn where nnn=-35 to 160 temperature 06 4/nnn where nnn=-35 to 160 temperature 05 3/nnn where nnn=-35 to 160 temperature 04 2/nnn where nnn=-35 to 160 temperature 03 Program to Probe #1 set point #4 dropout 8/nnn where nnn=-35 to 160 temperature 125 V4.42, December 16, 2007 Setting # Setting Purpose Setting Range or Values 09 SP21 PICKUP Probe #2, set point 9/nnn #1 pickup Program to where nnn=-35 to 160 temperature DO NOT SET IF SINGLE PROBE 10 SP21 DRPOUT Probe #2 set point #1 dropout 10/nnn where nnn=-35 to 160 temperature DO NOT SET IF SINGLE PROBE 11 SP22 PICKUP Probe #2, set point #2 pickup 11/nnn where nnn=-35 to 160 temperature DO NOT SET IF SINGLE PROBE 12 SP22 DRPOUT Probe #2 set point #2 dropout 12/nnn where nnn=-35 to 160 temperature DO NOT SET IF SINGLE PROBE 13 SP23 PICKUP Probe #2, set point #3 pickup 13/nnn where nnn=-35 to 160 temperature DO NOT SET IF SINGLE PROBE 14 SP23 DRPOUT Probe #2 set point #3 dropout 14/nnn where nnn=-35 to 160 temperature DO NOT SET IF SINGLE PROBE 15 SP24 PICKUP Probe #2, set point #4 pickup 15/nnn where nnn=-35 to 160 temperature DO NOT SET IF SINGLE PROBE 16 SP24 DRPOUT Probe #2 set point #4 dropout 16/nnn where nnn=-35 to 160 temperature DO NOT SET IF SINGLE PROBE 126 V4.42, December 16, 2007 Setting # Setting Purpose Setting Range or Values 17 WSP1 PICKUP Calculated winding 17/nnn pickup temperature Program to where nnn=-35 to 180 SET ONLY IF Aux CT avail. 18 WSP1 DRPOUT Calculated winding dropout temperature 18/nnn where nnn=-35 to 180 SET ONLY IF Aux CT avail. 19 WSP2 PICKUP Calculated winding pickup temperature 19/nnn where nnn=-35 to 180 SET ONLY IF Aux CT avail. 20 WSP2 DRPOUT Calculated winding dropout temperature 20/nnn where nnn=-35 to 180 SET ONLY IF Aux CT avail. 21 WSP3 PICKUP Calculated winding pickup temperature 21/nnn where nnn=-35 to 180 SET ONLY IF Aux CT avail. 22 WSP3 DRPOUT Calculated winding dropout temperature 22/nnn where nnn=-35 to 180 SET ONLY IF Aux CT avail. 23 WSP4 PICKUP Calculated winding pickup temperature 23/nnn where nnn=-35 to 180 SET ONLY IF Aux CT avail. 24 WSP4 DRPOUT Calculated winding dropout temperature 24/nnn where nnn=-35 to 180 SET ONLY IF Aux CT avail. 25 LTCDIFF LTC Differential PICKUP pickup temperature 25/-nn or 25/nn where nn=0 to 20 DO NOT SET IF SINGLE PROBE 127 V4.42, December 16, 2007 Setting # Setting Purpose Setting Range or Values 26 LTCDIFF LTC Differential drop 26/-nn or 26/nn DRPOUT out temperature Program to where nn=0 to 20 DO NOT SET IF SINGLE PROBE 27 LTCDIFF LTC Pickup Timer in PICKUPTMR minutes 27/nnn where nnn=0 to 999 DO NOT SET IF SINGLE PROBE 28 LSP1 PICKUP Load pickup current 28/n.n where n.n=0.0 to 9.9 SET ONLY IF Aux CT avail. 29 LSP1 DRPOUT Load dropout 29/n.n current where n.n=0.0 to 9.9 SET ONLY IF Aux CT avail. 30 LSP2 PICKUP Load pickup current 30/n.n where n.n=0.0 to 9.9 SET ONLY IF Aux CT avail. 31 LSP2 DRPOUT Load dropout 31/n.n current where n.n=0.0 to 9.9 SET ONLY IF Aux CT avail. 32 LOAD PICKUP Load pickup timer TMR1 for LSP1 32/nnn where n=0 to 255 seconds SET ONLY IF Aux CT avail. 33 LOAD PICKUP Load pickup timer TMR2 for LSP2 33/nnn where n=0 to 255 seconds SET ONLY IF Aux CT avail. 34 IN1 CTRL Allows the input to handle pulses 34/0: LEVEL 34/1: PULSE SET ONLY IF Optically Isolated Inputs avail. 128 V4.42, December 16, 2007 Setting # Setting Purpose Setting Range or Values 35 IN2 CTRL Allows the input to 35/0: LEVEL handle pulses Program to 35/1: PULSE SET ONLY IF Optically Isolated Inputs avail. 36 37 OUT1 PICKUP Delays activation of 36/nnn TMR an output OUT1 Operate Output in 37/0: AUTO (uses AUTO/MANUAL AUTO or MANUAL programmable logic where n=0 to 255 seconds control 37/1: MANUAL (control through front panel) 38 OUT1 xxxxx (n) Controls Behavior 38/0: OUT1 UNCHG (0) w/ALRM of output when w/ALRM Device or Temp Alarm 38/1: OUT1 PCKUP (1) w/ALRM 38/2: OUT1 SUPVS (2) w/ALRM 39 40 OUT2 PICKUP Delays activation of 39/nnn TMR an output OUT2 Operate Output in 40/0: AUTO (uses AUTO/MANUAL AUTO or MANUAL programmable logic where n=0 to 255 seconds control 40/1: MANUAL (control through front panel) 41 OUT2 xxxxx (n) Controls Behavior 41/0: OUT2 UNCHG (0) w/ALRM of output when w/ALRM Device or Temp Alarm 41/1: OUT2 PCKUP (1) w/ALRM 41/2: OUT2 SUPVS (2) w/ALRM 42 OUT3 PICKUP Delays activation of TMR an output 42/nnn where n=0 to 255 seconds 129 V4.42, December 16, 2007 Setting # Setting Purpose Setting Range or Values 43 OUT3 Operate Output in 43/0: AUTO (uses AUTO/MANUAL AUTO or MANUAL programmable logic control Program to 43/1: MANUAL (control through front panel) 44 OUT3 xxxxx (n) Controls Behavior 44/0: OUT3 UNCHG (0) w/ALRM of output when w/ALRM Device or Temp Alarm 44/1: OUT3 PCKUP (1) w/ALRM 44/2: OUT3 SUPVS (2) w/ALRM 45 46 OUT4 PICKUP Delays activation of 45/nnn TMR an output OUT4 Operate Output in 46/0: AUTO (uses AUTO/MANUAL AUTO or MANUAL programmable logic where n=0 to 255 seconds control 46/1: MANUAL (control through front panel) 47 OUT4 xxxxx (n) Controls Behavior 47/0: OUT4 UNCHG (0) w/ALRM of output when w/ALRM Device or Temp Alarm 47/1: OUT4 PCKUP (1) w/ALRM 47/2: OUT4 SUPVS (2) w/ALRM 48 (!) SP11 (*/+) TO Programmable OUTn logic for SP11 48/0/0/0: SP11 not assigned 48/0/0/n: SP11 * to OUTn 48/1/0/n: !SP11 * to OUTn 48/0/1/n: SP11 + to OUTn 48/1/1/n: !SP11 + to OUTn where n=1,2,3,4 130 V4.42, December 16, 2007 Setting # Setting Purpose Setting Range or Values 49 (!) SP12 (*/+) TO Programmable 49/0/0/0: SP12 not assigned OUTn logic for SP12 Program to 49/0/0/n: SP12 * to OUTn 49/1/0/n: !SP12 * to OUTn 49/0/1/n: SP12 + to OUTn 49/1/1/n: !SP12 + to OUTn where n=1,2,3,4 50 (!) SP13 (*/+) Programmable logic TO OUTn for SP13 50/0/0/0: SP13 not assigned 50/0/0/n: SP13 * to OUTn 50/1/0/n: !SP13 * to OUTn 50/0/1/n: SP13 + to OUTn 50/1/1/n: !SP13 + to OUTn where n=1,2,3,4 51 (!) SP14 (*/+) Programmable logic TO OUTn for SP14 51/0/0/0: SP14 not assigned 51/0/0/n: SP14 * to OUTn 51/1/0/n: !SP14 * to OUTn 51/0/1/n: SP14 + to OUTn 51/1/1/n: !SP14 + to OUTn where n=1,2,3,4 52 (!) SP21 (*/+) Programmable logic TO OUTn for SP21 52/0/0/0: SP21 not assigned 52/0/0/n: SP21 * to OUTn DO NOT USE FOR SINGLE PROBE 52/1/0/n: !SP21 * to OUTn 52/0/1/n: SP21 + to OUTn 52/1/1/n: !SP21 + to OUTn where n=1,2,3,4 53 (!) SP22 (*/+) Programmable logic TO OUTn for SP22 53/0/0/0: SP22 not assigned 53/0/0/n: SP22 * to OUTn DO NOT USE FOR SINGLE PROBE 53/1/0/n: !SP22 * to OUTn 53/0/1/n: SP22 + to OUTn 53/1/1/n: !SP22 + to OUTn where n=1,2,3,4 131 V4.42, December 16, 2007 Setting # Setting Purpose Setting Range or Values 54 (!) SP23 (*/+) Programmable logic 54/0/0/0: SP23 not assigned TO OUTn for SP23 Program to 54/0/0/n: SP23 * to OUTn DO NOT USE FOR SINGLE PROBE 54/1/0/n: !SP23 * to OUTn 54/0/1/n: SP23 + to OUTn 54/1/1/n: !SP23 + to OUTn where n=1,2,3,4 55 (!) SP24 (*/+) Programmable logic TO OUTn for SP24 55/0/0/0: SP24 not assigned 55/0/0/n: SP24 * to OUTn DO NOT USE FOR SINGLE PROBE 55/1/0/n: !SP24 * to OUTn 55/0/1/n: SP24 + to OUTn 55/1/1/n: !SP24 + to OUTn where n=1,2,3,4 56 (!) LTCDIFF Programmable logic 56/0/0/0: LTCDIFF not (*/+) TO OUTn for LTCDIFF assigned DO NOT USE FOR 56/0/0/n: LTCDIFF * to OUTn SINGLE PROBE 56/1/0/n: !LTCDIFF * to OUTn 56/0/1/n: LTCDIFF + to OUTn 56/1/1/n: !LTCDIFF + to OUTn where n=1,2,3,4 57 (!) WSP1 (*/+) Programmable logic TO OUTn for WSP1 57/0/0/0: WSP1 not assigned 57/0/0/n: WSP1 * to OUTn SET ONLY IF Aux CT avail. 57/1/0/n: !WSP1 * to OUTn 57/0/1/n: WSP1 + to OUTn 57/1/1/n: !SP23 + to OUTn 58 (!) WSP2 (*/+) Programmable logic TO OUTn for WSP2 where n=1,2,3,4 58/0/0/0: WSP2 not assigned 58/0/0/n: WSP2 * to OUTn SET ONLY IF Aux CT avail. 58/1/0/n: !WSP2 * to OUTn 58/0/1/n: WSP2 + to OUTn 58/1/1/n: !WSP2 + to OUTn where n=1,2,3,4 132 V4.42, December 16, 2007 Setting # Setting Purpose Setting Range or Values 59 (!) WSP3 (*/+) Programmable 59/0/0/0: WSP3 not assigned TO OUTn logic for SP3 Program to 59/0/0/n: WSP3 * to OUTn SET ONLY IF Aux CT avail. 59/1/0/n: !WSP3 * to OUTn 59/0/1/n: WSP3 + to OUTn 59/1/1/n: !WSP3 + to OUTn where n=1,2,3,4 60 (!) WSP4 (*/+) Programmable TO OUTn logic for SP3 60/0/0/0: WSP4 not assigned 60/0/0/n: WSP4 * to OUTn SET ONLY IF Aux CT avail. 60/1/0/n: !WSP4 * to OUTn 60/0/1/n: WSP4 + to OUTn 60/1/1/n: !WSP4 + to OUTn where n=1,2,3,4 61 (!) LSP1 (*/+) TO Programmable OUTn logic for LSP1 SET ONLY IF Aux CT avail. 61/0/0/0: LSP1 not assigned 61/0/0/n: LSP1 * to OUTn 61/1/0/n: !LSP1 * to OUTn 61/0/1/n: LSP1 + to OUTn 61/1/1/n: !LP1 + to OUTn where n=1,2,3,4 62 (!) LSP2 (*/+) TO Programmable OUTn logic for LSP2 SET ONLY IF Aux CT avail. 62/0/0/0: LSP2 not assigned 62/0/0/n: LSP2 * to OUTn 62/1/0/n: !LSP2 * to OUTn 62/0/1/n: LSP2 + to OUTn 62/1/1/n: !LP2 + to OUTn where n=1,2,3,4 63 (!) OUT1 (*/+) Programmable TO OUTn logic for OUT1 63/0/0/0: OUT1 not assigned 63/0/0/n: OUT1 * to OUTn 63/1/0/n: !OUT1 * to OUTn 63/0/1/n: OUT1 + to OUTn 63/1/1/n: !OUT1 + to OUTn where n=1,2,3,4 133 V4.42, December 16, 2007 Setting # Setting Purpose Setting Range or Values 64 (!) OUT2 (*/+) Programmable 64/0/0/0: OUT2 not assigned TO OUTn logic for OUT2 Program to 64/0/0/n: OUT2 * to OUTn 64/1/0/n: !OUT2 * to OUTn 64/0/1/n: OUT2 + to OUTn 64/0/1/n: !OUT2 + to OUTn where n=1,2,3,4 65 (!) OUT3 (*/+) Programmable TO OUTn logic for OUT3 65/0/0/0: OUT3 not assigned 65/0/0/n: OUT3 * to OUTn 65/1/0/n: !OUT3 * to OUTn 65/0/1/n: OUT3 + to OUTn 65/1/1/n: !OUT3 + to OUTn where n=1,2,3,4 66 (!) OUT4 (*/+) Programmable TO OUTn logic for OUT4 66/0/0/0: OUT4 not assigned 66/0/0/n: OUT4 * to OUTn 66/1/0/n: !OUT4 * to OUTn 66/0/1/n: OUT4 + to OUTn 66/1/1/n: !OUT4 + to OUTn where n=1,2,3,4 67 (!) IN1 (*/+) TO Programmable OUTn logic for IN1 67/0/0/0: IN1 not assigned 67/0/0/n: IN1 * to OUTn SET ONLY IF Optically Isolated 67/1/0/n: !IN1 * to OUTn 67/0/1/n: IN1 + to OUTn Input avail. 67/1/1/n: !IN1 + to OUTn where n=1,2,3,4 68 (!) IN2 (*/+) TO Programmable OUTn logic for IN2 68/0/0/0: IN2 not assigned 68/0/0/n: IN2 * to OUTn SET ONLY IF Optically Isolated 68/1/0/n: !IN2 * to OUTn 68/0/1/n: IN2 + to OUTn Input avail. 68/1/1/n: !IN2 + to OUTn where n=1,2,3,4 134 V4.42, December 16, 2007 Setting # Setting Purpose Setting Range or Values 69 TIME1 xx:xx TO Assigns TIME1 69/xx:xx/yy:yy/n yy:yy Assigned setpoint to OUTn TO OUTn Program to where xx:xx= pickup time yy:yy=dropout time n=0,1,2,3,4 70 TIME2 xx:xx TO Assigns TIME2 yy:yy Assigned setpoint to OUTn TO OUTn 70/xx:xx/yy:yy/n where xx:xx= pickup time yy:yy=dropout time n=0,1,2,3,4 71 TIME3 xx:xx TO Assigns TIME3 yy:yy Assigned setpoint to OUTn TO OUTn 71/xx:xx/yy:yy/n where xx:xx= pickup time yy:yy=dropout time n=0,1,2,3,4 72 OUT1 INVERT Inverts OUT1 72/0: Not INVERT 72/1: INVERT 73 OUT2 INVERT Inverts OUT2 73/0: Not INVERT 73/1: INVERT 74 OUT3 INVERT Inverts OUT3 74/0: Not INVERT 74/1: INVERT 75 OUT4 INVERT Inverts OUT4 75/0: Not INVERT 75/1: INVERT 76 CT RATIO Sets ratio of 76/nnnn primary CT 77 RATED LOAD where nnnn= 0 to 6000 Sets rated load in amps based on mfg’s data 78 WINDING RISE Sets hotspot rise in @ RATED LOAD C over top oil at rated load based 77/nnnnn where nnnnn=0 to 65535 78/nn where nn=0 to 99 on mfg’s data 135 V4.42, December 16, 2007 Setting # Setting Purpose Setting Range or Values 79 WINDING TC Sets winding time 79/nnn constant in minutes based on mfg’s Program to where nnn=0 to 999 data 80 COOLING TYPE Sets cooling type 80/0: Not directed FOA/FOW 80/1: Directed FOA/FOW 81 TPROBE1 NAME Names PROBE1 81/0: TOP OIL 81/1: WINDING 81/2: AMBIENT 81/3: LTCDIFF (dual probe) 81/4: BOTMOIL 82 TPROBE2 NAME Names PROBE2 82/0: TOP OIL 82/1: WINDING 82/2: AMBIENT 82/3: LTCDIFF 82/4: BOTMOIL 83 ALTERNATE Alternate output control 83/0: DSBL 83/1: 1 – 2 83/2: 1 – 3 83/3: 1 – 4 83/4: 2 –3 83/5: 2 – 4 83/6: 3 - 4 84 ANALGOUT Sets scaling of Analog output 85 A1 SOURCE Selects data source for analog output A1 84/0: 0 to 1 mA 84/1: 4 to 20 mA 85/0: P1 (probe #1) 85/1: P2 (probe #2) 85/2: Calc winding temp. 86 A2 SOURCE Selects data source for analog output A2 86/0: P1 (probe #1) 86/1: P2 (probe #2) 86/2: Calc winding temp. 136 V4.42, December 16, 2007 Setting # Setting Purpose Setting Range or Values 87 BAUD RATE Sets baud rate for 87/0: 1200 baud RS-485 interface Program to 87/1: 2400 baud 87/2: 9600 baud 87/3: 19200 baud 88 NODE ADDR Sets the node 88/xxxxx address for DNP3.0 communications 89 REMOTE BLK Enables blocking of remote control commands through where xxxxx=0 to 65535 89/0: Disables remote block 89/1: Enables remote block DNP3.0 90 TIMEBASE Sets record time for data log 90/nnnn where nnnn=0 to 9999 91 INCLUDE P1 Sets P1 for data log IN LOG 92 INCLUDE P2 91/1: YES Sets P2 for data log IN LOG 93 91/0: NO 92/0: NO 92/1: YES INCLUDE Sets Calculated WINDING IN Winding Temp. for LOG data log 93/0: NO 93/1: YES SET ONLY IF Aux CT avail. 94 INCLUDE LOAD IN LOG Sets LOAD for data log 94/0: NO 94/1: YES SET ONLY IF Aux CT avail. 95 TIME Sets time of day 95/xx:xx where xx:xx= 00:00 to 23:59 96 DATE Sets date 96/mm/dd/yr where mm=01-12 dd=01-31 yr=00 to 99 97 WNDCKT ALRM Enables or disables winding circuit alarm 137 97/0: Enabled 97/1: Disabled V4.42, December 16, 2007 Setting # Setting Purpose Setting Range or Values 98 DEVICE ALRM Enables or disables 98/0: Enabled device alarm 99 TEMPERATUR E ALRM 100 MANUAL ALRM 98/1: Disabled Enables or disables temperature measurement alarm 99/0: Enabled Enables or disables 100/0: Enabled Manual Mode alarm 101 TIME SP CNTR Sets Time Setpoints Counter 102 UNIT ID Program to 99/1: Disabled 100/1: Disabled 101/nnn where nnn=0 to 255 A six character name for unit 102/XXXXX where X=any printable character 103 NEG Enables scaling of ANALGOUT analog outputs for SCALING negative 103/0: NO 103/1: YES temperatures 104 LTCDIFF RISE Maximum LTCDIFF rise in time period LTCDIFF RATE 105 LTCDIFF RATE Time period in which LTCDIFF is PASSWORD where nn=0 to 40 105/nnn where nnn=0 to 255 minutes examined 106 104/nn Sets password 102/xxxx where xxxx=0000 to 9999 138 V4.42, December 16, 2007 14 DNP3.0 PROFILE DOCUMENT DNP V3.00 DEVICE PROFILE DOCUMENT Vendor Name: Advanced Power Technologies, LLC Device Name: TTC-1000, Transformer Temperature Controller Highest DNP Level Supported: For Requests: Device Function: Master Level 1 Slave For Responses: Level 1 Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the complete list is described in the attached table): See attached table. Maximum Data Link Frame Size (octets): Transmitted: 70 Received 37 Maximum Application Fragment Size (octets): Maximum Data Link Re-tries: Transmitted: 51 Received: 22 Maximum Application Layer Re-tries: None Fixed at ____ None Configurable Configurable from ___ to ____ Requires Data Link Layer Confirmation: Never Always Sometimes Configurable as: Never 139 V4.42, December 16, 2007 DNP V3.00 DEVICE PROFILE DOCUMENT Requires Application Layer Confirmation: Never Always When reporting Event Data When sending multi-fragment responses Sometimes Configurable Timeouts while waiting for: Data Link Confirm: None Fixed at ____ Variable Configurable Complete Appl. Fragment: None Fixed at ____ Variable Configurable Application Confirm: None Fixed at ____ Variable Configurable Complete Appl. Response: None Fixed at ____ Variable Configurable Others:__________________________________________________ Sends/Executes Control Operations: WRITE Binary Outputs Never Always Sometimes Configurable SELECT/OPERATE Never Always Sometimes Configurable DIRECT OPERATE Never Always Sometimes Configurable DIRECT OPERATE – NO ACK Never Always Sometimes Configurable Count > 1 Never Always Sometimes Configurable Pulse On Never Always Sometimes Configurable Pulse Off Never Always Sometimes Configurable Latch On Never Always Sometimes Configurable Latch Off Never Always Sometimes Configurable Queue Never Always Sometimes Configurable Clear Queue Never Always Sometimes Configurable 140 V4.42, December 16, 2007 DNP V3.00 DEVICE PROFILE DOCUMENT Reports Binary Input Change Events when no specific variation requested: Reports time-tagged Binary Input Change Events when no specific variation requested: Never Never Only time-tagged Binary Input Change With Time Only non-time-tagged Binary Input Change With Relative Time Configurable Configurable (attach explanation) Sends Unsolicited Responses: Sends Static Data in Unsolicited Responses: Never Never Configurable When Device Restarts Only certain objects When Status Flags Change Sometimes (attach explanation) ENABLE/DISABLE UNSOLICITED Function codes supported Default Counter Object/Variation: No other options are permitted. Counters Roll Over at: No Counters Reported No Counters Reported Configurable Configurable (attach explanation) Default Object: 20 and 21 16 Bits 32 Bits Default Variation: Point-by-point list attached Other Value: _____ Point-by-point list attached Sends Multi-Fragment Responses: Yes No 141 V4.42, December 16, 2007 DNP V3.00 DEVICE PROFILE DOCUMENT Sequential File Transfer Support: Yes No Custom Status Code Strings Yes No Yes No File Events Assigned to Class Yes No Yes No File Events Send Immediately Yes No Multiple Blocks in a Fragment Yes No Append File Mode Permissions Field File Events Poll Specifically Max Number of Files Open 0 IMPLEMENTATION TABLE REQUEST OBJECT Object Variation Number Number 10 0 RESPONSE (supported) Description Binary Output Status (Variation 0 is (may generate) Function Qualifier Codes Function Qualifier Codes Codes (dec) (hex) Codes (dec) (hex) 1 (read) 3 (select) 4 (operate) 5 (direct op) 06 (no range, or all) used to request default variation) 12 1 Control Relay Output Block 17, 28 129 (response) echo of request 6 (dir. op, noack) 60 1 Class 0 Data 1 80 1 Internal Indications 2 142 (read) 06 00 (start-stop) V4.42, December 16, 2007 TTC-1000 Data Map Index # 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 DNP Object Group,Variation 01,02 01,02 01,02 01,02 01,02 01,02 01,02 01,02 01,02 01,02 01,02 01,02 01,02 01,02 01,02 01,02 01,02 01,02 01,02 01,02 01,02 01,02 01,02 01,02 01,02 01,02 01,02 01,02 Description State of Set Point SP11 (Probe 1, Set Point 1), 0-Dropped Out, 1-Picked Up State of Set Point SP12 (Probe 1, Set Point 2), 0-Dropped Out, 1-Picked Up State of Set Point SP13 (Probe 1, Set Point 3), 0-Dropped Out, 1-Picked Up State of Set Point SP14 (Probe 1, Set Point 4), 0-Dropped Out, 1-Picked Up State of Set Point SP21 (Probe 2, Set Point 1), 0-Dropped Out, 1-Picked Up State of Set Point SP22 (Probe 2, Set Point 2), 0-Dropped Out, 1-Picked Up State of Set Point SP23 (Probe 2, Set Point 3), 0-Dropped Out, 1-Picked Up State of Set Point SP24 (Probe 2, Set Point 4), 0-Dropped Out, 1-Picked Up State of Set Point WSP1 (Winding Set Point 1), 0-Dropped Out, 1-Picked Up State of Set Point WSP2 (Winding Set Point 2), 0-Dropped Out, 1-Picked Up State of Set Point WSP3 (Winding Set Point 3), 0-Dropped Out, 1-Picked Up State of Set Point WSP4 (Winding Set Point 4), 0-Dropped Out, 1-Picked Up State of Set Point LSP1 (Load Set Point 1), 0-Dropped Out, 1-Picked Up State of Set Point LSP2 (Load Set Point 2), 0-Dropped Out, 1-Picked Up State of Set Point LTCDIFF (LTC Set Point ), 0-Dropped Out, 1-Picked Up State of Output #1 (OUT1), 0-Dropped Out, 1-Picked Up State of Output #2 (OUT2), 0-Dropped Out, 1-Picked Up State of Output #3 (OUT3), 0-Dropped Out, 1-Picked Up State of Output #4 (OUT4), 0-Dropped Out, 1-Picked Up State of Set Point TIME1 (Time Set Point 1), 0-Dropped Out, 1-Picked Up State of Set Point TIME2 (Time Set Point 2), 0-Dropped Out, 1-Picked Up State of Set Point TIME3 (Time Set Point 3), 0-Dropped Out, 1-Picked Up State of Device Alarm, 0-No Alarm, 1-Alarm State of Temperature Probe Alarm, 0-No Alarm, 1-Alarm State of Remote Block, 0-Remote Block Disabled, 1-Remote Block Enabled State of Optically Isolated Input, IN1, 0-Dropped Out, 1-Picked Up State of Optically Isolated Input, IN2, 0-Dropped Out, 1-Picked Up State of Winding Circuit Alarm, 0-No Alarm, 1-Alarm 00 01 02 03 12,01 12,01 12,01 12,01 OUT1 Control, 1-remote on, 0-local control OUT2 Control, 1-remote on, 0-local control OUT3 Control, 1-remote on, 0-local control OUT4 Control, 1-remote on, 0-local control 00 01 02 03 04 05 30,04 30,04 30,04 30,04 30,04 30,04 Probe 1 Temperature Probe 2 Temperature Calculated Winding Hotspot Temperature Measured Load Current Probe 1 Name, 0-Top Oil, 1-Winding, 2-Ambient, 3-LTCDIFF, 4-BOTMOIL Probe 2 Name, 0-Top Oil, 1-Winding, 2-Ambient, 3-LTCDIFF, 4-BOTMOIL 143 V4.42, December 16, 2007