GOA9xx04C 1 - Green Power Solutions

Green Power Solutions srl
Phone: +39-011-988 2251
Fax: +39-011-988 1358
Web: www.gpsemi.it
e-mail: [email protected]
Via Venezia 34D - 10088 Volpiano (TO), Italy
GOA9xx04C
THREE PHASE AC-SWITCH
Fuse protection
Blown fuse indicators with microswitch
Over temperature switches
Fan loss detection circuit
Snubber for SCR's protections
Compact design
LINE VOLTAGE UP TO 500V
RMS OUTPUT CURRENT 450A
GOA94004C GOA95004C
Line to line voltage
Characteristic
IRMS
RMS output current
VINS (rms)
Insulation voltage
Conditions
400
500
Value
Value
450 A
450 A
3000 V
3000 V
3 V
3 V
THYRISTOR TRIGGERING CHARACTERISTICS
VGT
Gate trigger voltage
Tj = 25 °C, V D = 5 V
IGT
Gate trigger current
Tj = 25 °C, V D = 5 V
300 mA
300 mA
dV/dt
Critical rate of rise off-state voltage
Tj= 125 °C
1000 V/us
1000 V/us
VRRM
Blocking Voltage
Tj = 125 °C
1200 V
1600 V
690 V
690 V
630 A
630 A
94 W
94 W
FUSE TYPE SIBA 2062432.630
VNF
Rated voltage
INF
Rated current
PVF
Power loss
At rated current
I²t
Total I2t
At 660V
300 kA2s
300 kA2s
MECHANICAL AND THERMAL CHARACTERISTICS
Width
400 mm
450 mm
Depth
340 mm
340.5 mm
Height
500 mm
500 mm
Mass
30 Kg
30 Kg
Ta max
Max amb. op. Temp.
40 °C
40 °C
Tstg
Storage temperature
-40/ +60 °C
Document GOA9xx04CT002
-40/ +60 °C
THREE PHASE AC-SWITCH
GOA9xx04C
The part numbering system is reported at the beginning of the Open Assembly section.
Customisations are available on request. Please contact factory.
In the interest of product improvement Green Power Solutions reserves the right to change any specification given in this data sheet
without notice.
Document GOA9xx04CT002
THREE PHASE AC-SWITCH
GOA9xx04C
FAN BOARD
PE
V3
U3-V3: MAIN SUPPLY
PE: GROUND CONNECTION (GND)
31-32: FAN BOARD CONTACT (CLOSED WHEN FAN RUNNING)
1
2
U3
FAN CAPACITOR
1
32
2
31
FAN CAPACITOR
BROWN
BLACK
BLUE
GREEN/YELLOW
FAN 2
BLUE
GREEN/YELLOW
BROWN
BLACK
AC
AC
NO
COM
NC
FAN 1
Cooling:
Fan type:
Number of fans:
Voltage:
Current:
Frequency:
Noise:
single phase axial
2
230 V
0.4 A
50/60 Hz
62 dBA
In the interest of product improvement Green Power Solutions reserves the right to change any specification given in this data sheet
without notice.
Document GOA9xx04CT002