FireVac® IV

FireVac® IV
Emergency Voice Evacuation System
Description
The FireVac®IV is a fully automatic combination fire alarm
and emergency voice evacuation system. When it is combined with an FCI fire alarm control, it provides automatic
and manual alarm signaling per the National Fire Alarm
Code, NFPA 72.
The FireVac®IV is ideal for installations requiring voice
evacuation of places of assembly such as churches, cafeterias, auditoriums, etc. The power output available from
the FireVac®IV is a cost effective solution to smaller voice
evacuation applications such as, assisted living facilities,
dormitories, motels, and hotels, etc.
The unit provides 50 Watts of audio power at either 25
VRMS or 70 VRMS (requires the FVIV-X70).
The FireVac®IV has eight field selectable tones built in as
well as an internal microphone for voice paging. The system also has three programmable messages. The first
and second messages may be changed via software
download and can record up to 32 seconds long. The third
message can be recorded via the system’s own internal
microphone and can record up to 49 seconds long.
®
FireVac IV
Features
•
•
•
•
•
®
The FireVac IV is fully supervised for opens, short circuits, and ground faults on the loudspeaker appliance
circuit. The system amplifier is continuously supervised. In
addition, the amplifier is protected from damage by the
short circuit disconnect feature built into the speaker circuit.
The optional FVIV-ZS provides the capacity to split the
available 50 watt power output among four separate, independently activated speaker circuits. Each speaker circuit
has its own switch for manual activation as well as an AllCall switch to turn on all four circuits at once. It mounts
inside the main FireVac®IV cabinet.
Compatible with any UL Listed fire alarm control panel.
50 watt power output.
25 or 70.7 (optional) VRMS power-limited operation.
Integral message repeater.
Eight (8) DIP-switch selectable tones.
- ANSI Cadence
- Alert Tone
- March Code
- California Code
- Steady
- Hi-Lo
- ANSI Whoop
- Continuous Whoop
• Optional FVIV-ZS provides four Style Y or Z (Class A or
B) speaker circuits.
•
•
•
•
Auxiliary audio input.
Form “C” trouble and alarm relay outputs.
Remote microphone module for all-call paging.
Single channel operation.
An ISO 9000-2000 Company
As a further option, the FVIV-RM Remote Microphone
station is available in its own cabinet. It can be mounted
up to 5,000 feet away and connects to the FireVac®IV
over shielded, four conductor, 18 AWG wire.
SIGNALING
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118
©2008
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
Gamewell-FCI. All rights reserved.
www.gamewell-fci.com
9020-0532 Rev. D1 page 1 of 4
System Operation
FVIV-X70
The operation of a fire alarm initiating device (i.e.
smoke detectors, manual stations, water-flow
switches, etc.) connected to the fire alarm control
panel will cause a either a reverse polarity signal or
a dry contact closure to be sent to the FireVac®IV.
If the optional FVIV-ZS is installed, the fire alarm
control panel will also provide up to four normally
open dry contact outputs that will close to activate
the appropriate speaker circuit. In response, the
FireVac®IV will:
1. Sound an alarm tone (DIP switch selectable) over the
speaker circuit(s).
2. Produce a recorded message that will play in alternation with the selected tone.
3. Override both tone and pre-recorded message and
broadcast voice commands from the local or remote
microphones.
The FireVac®IV provides two (2), separate messages that may be field configured using the optional 7780 program.
Optional Modules (FVIV-ZS)
S P1 +
S P1–
S PR1+
S PR1 –
S P2+
S P2–
S PR2 +
FROM CONTROL
TO SPLITTER
70.7 VRMS SPK
– IN
+
– OUT +
The FVIV-X70 optional module is used to
convert the standard speaker circuit voltage
output from 25 VRMS to 70 VRMS. This is useful
in situations where the speakers circuits must
run for longer distances. Note that speakers
at 70 VRMS are not power-limited and must be
separated from power-limited circuits by at
least 1/4 inch.
FVIV-RM
S PR 2–
TROUBLE
ACTIVE
1
2
1
3
4
5
2
6
7
8
3
9
10
4
11
12
13
14
15
16
ALL-CALL
17
18
19
20
21
22
23
24
S P+
S P–
S P4 +
S P4–
S PR4+
S PR4 –
S P3+
S P3–
S PR3 +
S PR 3–
An ideal solution for installations that require zoned
speaker circuit activation, the FVIV-ZS provides
four separate, individually activated speaker circuits. The FVIV-ZS features a switch for manual
activation of each speaker circuit as well as an addition switch for “All-Call” paging.
Interface with the fire alarm control panel is
achieved through normally open relays provided
by the main control panel. The FVIV-ZS responds
to closures across its input terminals to activate the
appropriate speaker circuit.
The FVIV-RM Remote Microphone Station
enhances operation of the system by providing voice paging from a remote location up to
5,000 feet away. Only four wires (shielded,
18 AWG minimum) are required between the
FireVac®IV and the FVIV-RM. The FVIV-RM
is fully supervised by the FireVac®IV. Simply
key the microphone to activate the FireVac®IV in an “ALL-Call” fashion to page over
all speakers.
The FVIV-RM comes complete with its own
cabinet with dimensions of 10 1/4” H x 10
3/8” W x 3 1/8” D (26.04 x 26.35 x 7.94 cm).
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472 - Tel: 203-484-7161 - Fax: 203-484-7118
www.gamewell.fci.com
9020-0532 Rev. D1 page 2 of 4
FVIV-RM
(in Cabinet up to 5,000 feet way)
FireVac® IV Assembly
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472 - Tel: 203-484-7161 - Fax: 203-484-7118
www.gamewell.fci.com
9020-0532 Rev. D1 page 3 of 4
Specifications
Ordering Information
Operating voltage: 120 VAC @ 60 Hz, 1.2 amp, or
230 VAC @ 50 Hz, 0.607 amp.*
Part Number
Operating
temperature:
Relative humidity:
32° to 120° F
(0° to 49° C)
10% to 85% at 86° F (30°C), noncondensing
* Specify voltage requirements when ordering.
150-00026
150-00027
151-00027
151-00028
Operating Current
FireVac IV
FVIV-ZS
Supervisory Alarm
0.140 amp.
0.490 amp.
0.045 amp.
0.250 amp.
(All circuits active)
FVIV-RM
0.030 amp.
0.030 amp.
FVIV-X70
0.010 amp.
0.065 amp.
Trouble & Alarm Relays
2.5 A @ 30 VDC
resistive
Dimensions:
Surface mount
26 1/4” H x 14 1/2” W x 4” D
(67 x 36.3 x 8.8 cm)
Flush mount
24 3/4” H x 14 1/2” W x 3 7/16” D
(63 x 36.3 x 8.7 cm)
Shipping weight
37 lbs. (16.78 kg.)
151-00023
151-00029
200-90002
Description
FireVac®IV, Emergency Voice
Evacuation System, 50
watts”Stand Alone”
FVIV-50-ZS, Emergency Voice
Evacuation System, 4-channel,
50 watt total
FVIV-RM, Remote Microphone
Station (one per system)
FVIV-X70, Line Transformer, converts 25 VRMS speaker circuit(s) to
70 VRMS
FVIV-ZS
FVIV-B450, Zone Splitter, 4
Speaker Circuits
7780, Programming Software to
download or removerecorded
messages