Time Delay Curves

Circuit Breaker - Time Delay Values
,
Notes:
1
2
3
4
Delay Curves 12,14, 22, 24, 32, 34, 62, 64, 72, 74, 92, 94: Breakers to hold 100% and must trip at 135% of rated current and greater within the time limit shown in this curve.
Delay Curves 10, 20, 30: Breakers to hold 100% and must trip at 150% of rated current and greater within the time limit shown in this curve.
All Curves: Curve data shown represents breaker response at ambient temperature of 77°F (25°C) with no preloading. Breakers are mounted in standard wall-mount position.
The minimum inrush pulse tolerance handling capability is 12 times the rated current on standard delays and 18 times the rated current on high inrush delays. These values are based on a 60 Hz 1/2 cycle,
8.33 ms pulse. High inrush delays should be specified for applications with high initial surge currents of short duration, such as switching power supplies, highly capacitive loads and transformer loads.
Dual Rated AC/DC
Instantaneous
Short
Short D2
Medium
Medium D4
www.carlingtech.com
1
Circuit Breaker - Time Delay Values
H, A, B, C, D, G, L, CX-SERIES TIME VALUES
PERCENT OF RATED CURRENT
Notes:
UL489 C-Series Breakers available with Delay Curves 11, 12, 14, 16, 21, 22, 24, 26, 42, 44, 46.
Delay Curves 11,12,14,16,21,22,24,26,42,44,46,52,54,56: Breakers to hold 100% and must trip at 125% of rated current and greater within the time limit shown in this curve.
Delay Curves 32,34,36: Breakers to hold 100% and must trip at 135% of rated current and greater within the time limit shown in this curve.
Delay Curves 10,20: Breakers to hold 100% and must trip at 150% of rated current and greater within the time limit shown in this curve.
All Curves: Curve data shown represents breaker response at ambient temperature of 77°F (25°C) with no preloading. Breakers are mounted in standard wall-mount position.
On 50 amp and less current ratings, the minimum inrush pulse tolerance handling capability is 12 times the rated current on standard delays and 25 times the rated current on high inrush delays. These values are based on a 60
Hz 1/2 cycle, 8.33 ms pulse. High inrush delays should be
for applications with high initial surge currents of short duration such as switching power supplies, highly capacitive loads and transformer loads.
AC
DC
TRIP TIME IN SECONDS
TRIP TIME IN SECONDS
Instantaneous
PERCENT OF RATED CURRENT
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
TRIP TIME IN SECONDS
Ultrashort
PERCENT OF RATED CURRENT
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
TRIP TIME IN SECONDS
Short
PERCENT OF RATED CURRENT
2
PERCENT OF RATED CURRENT
www.carlingtech.com
Circuit Breaker - Time Delay Values
AC
DC
TRIP TIME IN SECONDS
TRIP TIME IN SECONDS
Medium
PERCENT OF RATED CURRENT
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
TRIP TIME IN SECONDS
Long
PERCENT OF RATED CURRENT
PERCENT OF RATED CURRENT
High Inrush AC
High Inrush DC
TRIP TIME IN SECONDS
TRIP TIME IN SECONDS
Short
TRIP TIME IN SECONDS
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
PERCENT OF RATED CURRENT
Medium
TRIP TIME IN SECONDS
PERCENT OF RATED CURRENT
www.carlingtech.com
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
PERCENT OF RATED CURRENT
Long
PERCENT OF RATED CURRENT
3
Circuit Breaker - Time Delay Values
AC/DC
TRIP TIME IN SECONDS
Short
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
Medium
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
Long
PERCENT OF RATED CURRENT
4
www.carlingtech.com
Circuit Breaker - Time Delay Values
NOTES
Delay Curves 10,20,30: Breakers to hold 100% and must trip at 150% of rated current and greater wthin the time limit shown in these curves.
Delay Curves 12,14,16,22,24,26,62,64,66,72,74,76: Breakers to hold 100% and must trip at 125% of rated current and greater wthin the time limit shown in these curves.
Delay Curves 32,34,36,92,94,96: Breakers to hold 100% and must trip at 135% of rated current and greater wthin the time limit shown in these curves.
All curves: Data shown represents breaker response at ambient temperature of 77°F (25°C) with no preloading: Breakers are mounted in standard wall-mount position.
The minimum inrush pulse tolerance handling capacity on the above standard delays is 16 times rated current &20 times rated current for high inrush delays based on a 60Hz 1/2 cycle, 8.33 ms pulse.
DC
TRIP TIME IN SECONDS
AC
TRIP TIME IN SECONDS
Instantaneous
PERCENT OF RATED CURRENT
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
TRIP TIME IN SECONDS
Short
PERCENT OF RATED CURRENT
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
TRIP TIME IN SECONDS
Medium
PERCENT OF RATED CURRENT
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
TRIP TIME IN SECONDS
Long
PERCENT OF RATED CURRENT
www.carlingtech.com
PERCENT OF RATED CURRENT
5
Circuit Breaker - Time Delay Values
AC/DC
TRIP TIME IN SECONDS
Instantaneous
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
Short
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
Medium
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
Long
PERCENT OF RATED CURRENT
6
www.carlingtech.com
Circuit Breaker - Time Delay Values
11
.475 - 10.0
No Trip
14
16
22
24
26
Short - AC 22
.013 - .125
No Trip
12
10.0 - 110
110 - 1000
.700 - 12.0
10.0 - 160
50.0 - 700
No Trip
No Trip
No Trip
No Trip
No Trip
AC
.010 - .070
.008 - .032
.275 - 2.80
.140 - .850
6.00 - 40.0
60.0 - 400
.350 - 4.00
6.00 - 60.0
32.0 - 350
2.50 - 15.0
22.0 - 150
.130 - 1.30
.220 - 20.0
10.0 - 90.0
.005 - .020
.004 - .020
.030 - .190
.015 - .125
.004 - .020
.010 - .050
.008 - .038
.500 - 3.00
4.00 - 25.0
.027 - .220
.300 - 3.00
1.50 - 15.0
.180 - 1.00
1.00 - 5.50
.008 - .130
.050 - 1.30
.500 - 7.00
.010 - .280
.008 - .080
.008 - .390
.004 - .045
.005 - .060
.006 - 2.00
.006 - .020
Ultrashort - DC
.010 - 1.80
.004 - .090
.007 - .500
.020 - 3.00
DC
TRIP TIME IN SECONDS
TRIP TIME IN SECONDS
F SERIES
50/60 HZ SHORT
CURVE NO. 22
PERCENT OF RATED CURRENT
Short - DC
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
F SERIES
50/60 HZ MEDIUM
CURVE NO. 24
TRIP TIME IN SECONDS
Medium - AC 24
Medium - DC
PERCENT OF RATED CURRENT
Long - AC 26
TRIP TIME IN SECONDS
F SERIES
50/60 HZ LONG
CURVE NO. 26
TRIP TIME IN SECONDS
PERCENT OF RATED CURRENT
PERCENT OF RATED CURRENT
www.carlingtech.com
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
Long - DC
7