DELTA DIN RAIL Jan 2014_Australia cata.qxd

AC/DC DIN RAIL MOUNTABLE
Delta DRP048V240W1BA
48V 240W - CLIQ 11 DIN RAIL POWER SUPPLY
FEATURES
•
•
•
•
•
•
•
Universal AC input voltage without power de-rating
High efficiency > 90.0% @ 230Vac
Power Boost of 150% for 5 seconds
Full corrosion resistant Aluminium chassis
Conforms to harmonic current IEC/EN 61000-3-2, Class A
Extreme low temperature cold start at -40°C
Conformal coating on PCBA to protect against chemical
and dust pollutants
• Hazardous Locations approval to ATEX and Class I, Div 2
SPECIFICATIONS
INPUT
Input Voltage Range
MECHANICAL
85-264Vac (DC input range 120-375Vdc)
Input Frequency
47-63Hz
< 2.50A @ 115Vac,
Input Current
< 1.30A @ 230Vac
> 90.0% @ 115Vac,
Efficiency 1) at 100% Load
> 92.0% @ 230Vac
Max Inrush Current
< 35A @ 115Vac & 230Vac
> 0.96 @ 115Vac,
Power Factor
> 0.90 @ 230Vac
Leakage Current
< 1mA @ 240Vac
OUTPUT
Output Voltage
Case Cover
Aluminium
Dimensions (L x W x D)
121 x 85 x 124.1 mm
Unit Weight
0.96 kg
Cooling System
Input / Output Wire
Convection
Pluggable Connector 3 Pins (Rated
300V/15A)
Pluggable Connector 4 Pins (Rated
300V/15A)
AWG 20-12
MTBF 2)
> 500,000 hrs
Input Terminal
Output Terminal
ENVIRONMENTAL
48V
Output Voltage Range
48-56V
Operating Temperature
-25°C to +80°C
Output Current
5.00A
Storage Temperature
-25°C to +85°C
Output Power
240W
Power De-rating
> 50°C (2.5% / °C)
Line Regulation
< 0.5% typ. (@ 85-264Vac input, 100% load)
Operating Humidity
< 95% RH (Non-Condensing)
Load Regulation
< 1% typ. (@ 85-264Vac input, 0-100% load)
Operating Altitude
2,500m
PARD (20MHz)
< 200mVpp
NOTES:
Hold-up Time
> 20ms @ 115Vac & 230Vac
1) Efficiency: O/P 100% load, Ta: 25°C at Vertical Mounting Orientation
2) MTBF as per Telcordia SR-332 (Confidential level: 90%, I/P: 115Vac,
O/P: 100% load) at Vertical Mounting Orientation
3) All parameters are specified at 25°C ambient unless otherwise noted
MECHANICAL DRAWINGS
12
Powering Progress – www.powerbox.com.au
Doc. No. PBC9-Delta Rev.G 3-2-14