BNC/ TC-2095 Rack-Mount Adapter Installation Guide

INSTALLATION GUIDE
BNC/TC-2095 Rack-Mount Adapter
This installation guide describes how to install the National Instruments
BNC-2095 and the TC-2095 rack-mount adapters and use them with
SCXI-1100, SCXI-1102/B/C, and SCXI-1104/C modules. The BNC-2095
also can be used with the SCXI-1581.
The BNC-2095 adapter has 32 BNC connectors to connect field signals to
the SCXI module inputs. The TC-2095 adapter has 32 uncompensated
miniconnectors to connect the thermocouples to the SCXI module inputs.
Both the BNC-2095 and TC-2095 adapters have the following features:
•
A 96-pin connector to connect to the SCXI module using an SH96-96
shielded cable or an R9696 ribbon cable
•
Rack-mount construction for use with 19-in. racks
•
A shielded, metal enclosure to minimize noise
The TC-2095 also features isothermal construction to minimize the
temperature gradients across the thermocouple junctions and a
high-accuracy thermistor for cold-junction temperature sensing.
The BNC-2095 and the TC-2095 have pull-up resistors connected between
CH+ and +5 VDC and ground-referencing resistors connected between
CH– and chassis ground through switches located on the rear of the adapter.
The bias resistor is a ground-referencing pull-down resistor for referencing
floating signals; the pull-up resistor is used for open thermocouple
detection. The pull-up resistors enable open thermocouple detection by
detecting saturation in the SCXI module amplifier output and
ground-referenced floating signals.
Conventions
The following conventions are used in this guide:
♦
The ♦ symbol indicates that the text following it applies only to a specific
product, a specific operating system, or a specific software version.
<>
Angle brackets that contain numbers separated by an ellipsis represent a
range of values associated with a bit or signal name—for example,
DBIO<3..0>. Angle brackets also can denote a variable in a channel
name—for example, ACH<i>.
»
The » symbol leads you through nested menu items and dialog box options
to a final action. The sequence File»Page Setup»Options directs you to
pull down the File menu, select the Page Setup item, and select Options
from the last dialog box.
This icon denotes a note, which alerts you to important information.
This icon denotes a caution, which advises you of precautions to take to
avoid injury, data loss, or a system crash. When this symbol is marked on
the product, refer to the Read Me First: Safety and Radio-Frequency
Interference document, shipped with the product, for precautions to take.
When symbol is marked on a product it denotes a warning advising you to
take precautions to avoid electrical shock.
When symbol is marked on a product it denotes a component that may be
hot. Touching this component may result in bodily injury.
bold
Bold text denotes items that you must select or click in the software, such
as menu items and dialog box options. Bold text also denotes parameter
names and hardware labels.
italic
Italic text denotes variables, emphasis, a cross reference, or an introduction
to a key concept. This font also denotes text that is a placeholder for a word
or value that you must supply.
monospace
Text in this font denotes text or characters that you should enter from the
keyboard, sections of code, programming examples, and syntax examples.
This font is also used for the proper names of disk drives, paths, directories,
programs, subprograms, subroutines, device names, functions, operations,
variables, filenames and extensions, and code excerpts.
BNC/TC-2095 Rack-Mount Adapter Installation Guide
2
ni.com
What You Need To Get Started
To install and use the BNC/TC-2095, you need the following items:
❑ One of the following:
–
BNC-2095 rack-mount adapter with BNC connectors
–
TC-2095 rack-mount adapter with thermocouple miniconnectors
❑ BNC/TC-2095 Rack-Mount Adapter Installation Guide
❑ Read Me First: Safety and Radio-Frequency Interference
❑ Four 10 MΩ resistor networks
❑ SCXI chassis and documentation
❑ One of the following SCXI modules and its documentation:
–
SCXI-1100
–
SCXI-1102/B/C
–
SCXI-1104/C
–
SCXI-1581
❑ One of the following cable assemblies:
–
SH96-96 cable assembly (recommended)
–
R9696 cable assembly
❑ TBX cable adapter (included in cable assembly kit)
❑ Number 1 Phillips screwdriver
❑ 1/8 in. flathead screwdriver
❑ Long-nose pliers
Connecting Signals
Caution Refer to the Read Me First: Safety and Radio-Frequency Interference document
before removing equipment covers or connecting/disconnecting any signal wires.
This section describes how to connect field signals to the adapter and how
to connect the adapter to the SCXI module.
© National Instruments Corporation
3
BNC/TC-2095 Rack-Mount Adapter Installation Guide
Connecting Field Signals
♦
BNC-2095
The BNC-2095 has 32 BNC connectors, one for each channel of a
SCXI module. Each BNC connector is labeled with the corresponding
channel number. The center pin of the BNC connector is the CH+, and
the outer shield is the CH– of each channel. The CH– is isolated from
the chassis ground, so you can use it for ground-referenced differential
signals. To ensure CH– is isolated from chassis ground, do not use bias
resistors.
Caution Do not force the BNC connector on the BNC-2095. If you have difficulty making
the connection, completely remove the connector and try again.
Connect the BNC connector of the cable to the BNC connector of the
BNC-2095 by aligning and inserting the connector and turning the
cable connector clockwise.
♦
TC-2095
The TC-2095 has 32 universal thermocouple miniconnectors that you
can use to connect a thermocouple to each channel of the SCXI
module. Each connector is labeled with the corresponding channel
number. The miniconnector indicates the positive and negative
terminals.
Caution Do not force the miniconnector into the socket. If you have difficulty inserting the
miniconnector, check that the polarity is correct.
Connect the thermocouple wire to the TC-2095 by inserting the
miniconnector into the socket. Each miniconnector consists of two
spades of different widths. The differing widths guarantee correct
polarity if both connectors are correctly wired.
Both contacts of the thermocouple miniconnector are made of copper.
This could cause offset errors in T-, R-, and S-type thermocouple
measurements because each of these types of thermocouples has
one copper contact. Only one contact forms a cold junction with
T, R, and S-type thermocouples.
BNC/TC-2095 Rack-Mount Adapter Installation Guide
4
ni.com
Configuring Open-Thermocouple/Signal Detection and Signal
Ground-Referencing
Refer to Table 1 to configure the BNC/TC-2095 for operating with
open-thermocouple or signal detection, and for properly
ground-referencing the signals.
Table 1. Configuring Open-Thermocouple/Signal Detection and Signal Ground-Referencing
Switch Settings
0
ON
1
GND REF
PULL-UP
GND REF
PULL-UP
GND REF
PULL-UP
GND REF
PULL-UP
Signal Type
Floating signal or
thermocouple
Yes
O 1 2 3 4 5 6 7 8
N
2
OFF
CH
3
Detects
Open
Thermocouple
Comments
BNC-2095—Use this
setting for detecting
floating signals or open
signal leads. When
detecting open signal
leads, the positive input is
pulled to +5 VDC if the
measured signal is
<5 VDC. Only use this
setting or configuration
with signals between
±5 VDC.
TC-2095—Use this setting
to detect open
thermocouples and when
the thermocouple is
floating.
ON
5
2
1
0
GND REF
PULL-UP
GND REF
PULL-UP
GND REF
PULL-UP
GND REF
PULL-UP
O 1 2 3 4 5 6 7 8
N
3
OFF
© National Instruments Corporation
CH
Ground-referenced
signal or
thermocouple
No
BNC-2095 or
TC-2095—Use this setting
when the signal or
thermocouple is
ground-referenced and
you want to disable
open-thermocouple
detection.
BNC/TC-2095 Rack-Mount Adapter Installation Guide
Table 1. Configuring Open-Thermocouple/Signal Detection and Signal Ground-Referencing (Continued)
Switch Settings
1
0
GND REF
PULL-UP
GND REF
PULL-UP
GND REF
PULL-UP
GND REF
PULL-UP
O 1 2 3 4 5 6 7 8
N
2
OFF
CH
3
Floating
thermocouple or
signal
No
BNC-2095 or
TC-2095—Use this setting
when the signal or
thermocouple is floating
and you want to disable
open-thermocouple
detection.
Ground-referenced
thermocouple or
signal
Yes
ON
0
Comments
ON
1
GND REF
PULL-UP
GND REF
PULL-UP
GND REF
PULL-UP
GND REF
PULL-UP
Signal Type
BNC-2095—Use this
setting for detecting
ground-referenced signals
or open signal leads.
When detecting open
signal leads, the positive
input is pulled to +5 VDC
if the measured signal is
<5 VDC. Only use this
setting or configuration
with signals between
±5 VDC.
O 1 2 3 4 5 6 7 8
N
2
OFF
CH
3
Detects
Open
Thermocouple
TC-2095—Use this setting
to detect open
thermocouples for
ground-referenced
thermocouples.
Caution Connecting an external ground-referenced signal with the 10 Ω resistor network
in place can cause permanent damage to the resistor network and the traces on the
BNC/TC-2095 printed circuit board. NI is not liable for any damage or injuries resulting
from improper signal connections. Refer to the Temperature Sensor Output and Accuracy
section for more information.
Connecting the BNC/TC-2095 to the SCXI Module
Complete the following steps to mount the SH96-96 cable assembly and
connect the BNC/TC-2095 to the SCXI module. Refer to Figures 1 and 2
as needed.
BNC/TC-2095 Rack-Mount Adapter Installation Guide
6
ni.com
Refer to the Connecting Signals section before connecting the signals. If signal
wires are connected to the terminal block, dangerous voltages can exist even when the
equipment is powered off.
Caution
1.
Power off the SCXI chassis.
2.
Power off the computer that contains the E Series data acquisition
(DAQ) device, or disconnect the computer from the SCXI chassis.
3.
Connect the TBX cable adapter to the SCXI module, and secure the
adapter by tightening both thumbscrews.
4.
Connect either end of the SH96-96 cable to the TBX cable adapter and
SCXI module, and secure the cable by tightening both backshell
mounting screws.
4
5
4
3
2
1
ADDRESS
3
1
2
5
1
3
1
2
Backshell Mounting Screws
SH96-96 Cable
3
4
Thumbscrews
SCXI Chassis
5
TBX Cable Adapter
Figure 1. Connecting the SH96-96 Cable to the SCXI Module
5.
© National Instruments Corporation
Mount the BNC/TC-2095 onto a 19-in. rack or place it on a workbench
near the SCXI chassis. If you do not rack-mount the BNC/TC-2095,
attach the four adhesive rubber feet included in the kit to the bottom of
the adapter to keep it stationary.
7
BNC/TC-2095 Rack-Mount Adapter Installation Guide
Note To minimize the temperature gradient inside the TC-2095 and maintain its
isothermal properties for accurate cold-junction compensation, keep the adapter from
extreme temperature differentials.
6.
Connect the other end of the 96-pin cable to the BNC/TC-2095 96-pin
connector and screw down the backshell.
Caution The cable connectors of the cables are keyed. Do not force the connection. If you
encounter difficulty, verify that the keying of the cable connectors is correct.
1
1
1
1
1
2 3
4
5
6 7
8
2 3
4
5
6 7
8
2 3
4
5
6 7
8
2 3
4
5
6 7
8
O
N
O
N
O
N
5
4
3
2
1
1
1
1
1
2 3
4
5
6 7
8
2 3
4
5
6 7
8
2 3
4
5
6 7
8
2 3
4
5
6 7
ADDRESS
O
N
8
O
N
O
N
O
N
O
N
2
1
BNC/TC-2095
2
2
96-Pin Backshell
3
3
SCXI Chassis
Figure 2. BNC/TC-2095 Connected to SCXI Module
Configuring the BNC/TC-2095
To access jumpers W1 and W2 and the resistor networks, refer to Figure 3
as you complete the following steps:
1.
Remove the nine cover screws that secure the BNC/TC-2095 cover.
2.
Remove the cover.
3.
Set jumpers W1 and W2 as needed. For more information about setting
the jumpers, refer to the Configuring the Shield Ground Jumper and
Configuring the Cold-Junction Sensor (TC-2095 Only) sections.
4.
Replace the cover and secure it with the cover screws.
BNC/TC-2095 Rack-Mount Adapter Installation Guide
8
ni.com
1
2
13
4
6
3
5
7
9
12
1) Cover
2) Cover Screws (9)
3) RP1
4) RP5
5) RP2
11
8
10
6) RP5
7) W1
8) W2
9) RP3
10) RP7
11) RP4
12) RP8
13) Switches
Figure 3. BNC-2095 Parts Locator Diagram
Configuring the Shield Ground Jumper
Jumper W2 connects the metal case and shield to the analog ground of the
SCXI module directly or through a 100 Ω resistor. The factory-default
setting is through the 100 Ω resistor. Refer to Table 2 for configuration
options for jumper W2.
© National Instruments Corporation
9
BNC/TC-2095 Rack-Mount Adapter Installation Guide
Table 2. BNC/TC-2095 Shield Ground Jumper Configuration
Jumper W2 Configuration
4
0Ω
3
100 Ω
2
OPEN
1
W2
4
0Ω
3
100 Ω
2
OPEN
Description
When to Use a Setting
100 Ω (factory-default)—
Connects the
BNC/TC-2095 housing
to SCXI chassis ground
through a 100 Ω resistor,
while minimizing any
potential ground loop
current.
Use this setting when you are using
the SH96-96 cable, and if one of the
following is true:
0 Ω—Connects the
BNC/TC-2095 housing to
SCXI chassis ground.
Use this setting only if the
factory-default setting is inadequate
for noise rejection, you are using the
R9696 cable, and if one of the
following is true:
• You have not rack-mounted the
BNC/TC-2095.
• You have rack-mounted the
BNC/TC-2095, but are unsure
whether the rack and the
BNC/TC-2095 are grounded.
1
• You have not rack-mounted the
BNC/TC-2095.
W2
• You have rack-mounted the
BNC/TC-2095 and are sure that
the rack and the BNC/TC-2095
are not grounded.
4
0Ω
3
100 Ω
2
OPEN
Open—Disconnects the
BNC/TC-2095 metal
housing from SCXI
chassis ground.
Use this setting only if all of the
following are true:
• Factory-default setting was
inadequate for noise rejection.
1
• You are using either the SH96-96
cable or the R9696 cable.
W2
• You have rack-mounted the
BNC/TC-2095.
• You are sure that the rack and the
BNC/TC-2095 are grounded.
BNC/TC-2095 Rack-Mount Adapter Installation Guide
10
ni.com
Configuring the Cold-Junction Sensor (TC-2095 Only)
The TC-2095 jumper W1 is set by factory-default to multiplexed
temperature sensor (MTEMP) mode. This setting multiplexes the
cold-junction sensor for SCXI modules operating in multiplexed mode.
Refer to Figure 3 for the location of jumper W1.
Do not change the factory-default position of jumper W1.
Table 3 shows the jumper W1 settings.
Table 3. Jumper W1 Settings for the TC-2095
Jumper W1 Position
DTEMP
Description
W1
MTEMP (CJTEMP)
mode—Factory-default setting.
Do not change the jumper
position.
MTEMP
Temperature Sensor Output and Accuracy
The TC-2095 temperature sensor voltage output varies from 1.91 to
0.58 VDC over the 0 to 55 °C temperature range. Table 4 shows the
temperature sensor output accuracy.
Table 4. Temperature Sensor Voltage Output Accuracy
Temperature Range
Voltage Output Accuracy1
0 to 15 °C
±1.0 °C
15 to 35 °C
±0.65 °C
< 35 to 55 °C
±1.0 °C
1 Includes the combined effects of the temperature sensor accuracy and the temperature
difference between the temperature sensor and any screw terminal. The terminal sensor
accuracy includes tolerances in all component values, the effects caused by temperature
and loading, and self-heating.
To select and read the temperature sensor, refer to the driver software
documentation for programming information.
© National Instruments Corporation
11
BNC/TC-2095 Rack-Mount Adapter Installation Guide
Alternatively, you can follow these steps to convert the cold-junction sensor
voltage to the cold-junction temperature.
1.
Calculate the resistance of the thermistor in Ω.
V TEMPOUT
R T = 5,000  ---------------------------------------
 2.5 – V TEMPOUT 
VTEMPOUT = output voltage of the temperature sensor
VTEMPOUT varies from 1.91 VDC (at 0 °C) to 0.58 VDC (at 55 °C). For the best
resolution, use the maximum gain for this signal range on the analog input channel of the
E Series DAQ device.
Note
The SCXI-1100 does not have a filter on the VTEMPOUT signal. Therefore, use an average of
a large number of samples to obtain an accurate measurement. For example, sample for
one second and average. Noisy environments require more samples for greater accuracy.
The SCXI-1102/B/C has a 2 Hz filter on the VTEMPOUT signal input channel.
2.
Calculate the cold-junction temperature in Kelvin.
1
T K = ------------------------------------------------------------a + b ( ln R T ) + c ( ln R T )
3
a = 1.295361 × 10–3
b = 2.343159 × 10–4
c = 1.018703 × 10–7
RT = resistance of the thermistor
3.
Convert the temperature to Celsius and Fahrenheit.
T ( °C ) = T K – 273.15
TK = temperature in Kelvin
[ T ( °C ) ]9
T ( °F ) = ----------------------- + 32
5
where T(°F) and T(°C) are the temperature readings in degrees
Fahrenheit and Celsius, respectively.
BNC/TC-2095 Rack-Mount Adapter Installation Guide
12
ni.com
Temperature Sensor Circuit Diagram
The circuit diagram in Figure 4 is optional information that you can use if
you want more details about the TC-2095 temperature sensor.
+5 V
4.7 kΩ
1%
2.5 V
LM 4040
2.5 V
0.1%
2
5 kΩ
0.1%
W1
MTEMP
0.1 µF
–t°
+ 1 10 µF
5 kΩ
at 25 °C 2 16 V
1
2
DTEMP
0.1 µF
Figure 4. Temperature Sensor Circuit Diagram
Configuring the Resistor Networks
When using an SCXI-1102/B/C, you can use the package of 10 MΩ resistor
networks included in the BNC/TC-2095 kit. You can install these resistor
networks as RP1, RP2, RP3, and RP4. Refer to Figure 3 for the locations
of RP<1...8>. If you use this configuration and you have the
ground-referencing switch powered on, the thermocouples or signals with
low-impedance sources (less than 100 Ω) either float without affecting the
measurement or are ground-referenced.
Figure 5 shows how the pull-up and ground-referencing resistors are
connected to the CH± inputs of the SCXI module.
© National Instruments Corporation
13
BNC/TC-2095 Rack-Mount Adapter Installation Guide
5V
Rpull-up
(RP5, RP6, RP7, RP8)
Pull-Up Switch
CH+
SCXI Module or VXI-SC Submodule
CH–
CH+
Screw Terminals
CH–
Ground Referencing
Switch
Rground referencing
(RP1, RP2, RP3, RP4)
(in sockets)
Figure 5. Resistor Connections
Table 5 shows which resistors are associated with each group of channels.
Table 5. Channel Input Signals and Resistor Network
Channel
Pull-Up Resistor
Network
Ground-Referencing
Resistor Network
<0...7>
RP8
RP4
<8...15>
RP7
RP3
<16...23>
RP6
RP2
<24...31>
RP5
RP1
SCXI-1102/B/C Module
You can replace the 10 Ω ground-referencing resistor networks
(factory-default configuration) in the BNC/TC-2095 with the 10 MΩ
resistor networks supplied in the kit. The 10 MΩ resistor networks allow
the signal to be ground-referenced or floating. Channels with open
thermocouples saturate at all sample rates.
Use long-nose pliers to remove or replace the resistor networks in the
sockets. Be careful not to damage the network package. Make sure pin 1
of each network is in the correct socket. Refer to Figures 6 and 7 as needed.
BNC/TC-2095 Rack-Mount Adapter Installation Guide
14
ni.com
10x-1-100
Mfr. code
10x-1-106
Mfr. code
Pin 1
Pin 1
a. 10 Ω Resistor Network
b. 10 MΩ Resistor Network
Figure 6. Resistor Networks
RP1
Pin 1
Figure 7. Pin 1 Location on BNC/TC-2095 for Ground-Referencing Resistor Socket
Each resistor network is labeled with descriptive numbers on the left front
side, and pin 1 is located directly beneath the darkened symbol within these
numbers. The 10 Ω resistor network is labeled 10x-1-100 (10 × 100 Ω); the
10 MΩ resistor network is labeled 10x-1-106 (10 × 106 Ω). Figure 6 shows
examples of these resistors.
SCXI-1100 Module
For the open thermocouple channel to saturate without disturbing the
measurements on any other channel, use an interchannel delay of 200 µs
or greater at a gain of 100 or higher, which corresponds to a sample rate
of 5 kHz.
After installing the 10 Ω bias resistors, you can accurately measure at the
maximum sampling rate of the module. The open thermocouple channel
may not saturate if the interchannel delay is less than 200 µs or if the
sample rate is more than 5 kHz at a gain of 100 or higher.
If you want fast open thermocouple detection and you have short
thermocouple leads, or if high accuracy is not important, you can replace
the pull-up resistors with a lower value resistor network. For example,
you can replace the pull-up resistor with a 1 MΩ, 10-pin bused
configuration resistor network (not included) and have a sample rate of
20 kHz, with an interchannel delay of 50 µs typical. With a 1 MΩ bias
resistor network, the current leakage would be 5 µA (5 VDC ÷ 1 MΩ),
which can result in a larger offset error because of thermocouple lead
resistance.
Use long-nose pliers to remove or replace the resistor networks in the
sockets. Be careful not to damage the network package. Make sure that
pin 1 of each network is in the correct socket.
© National Instruments Corporation
15
BNC/TC-2095 Rack-Mount Adapter Installation Guide
Errors Due to Open-Thermocouple Detection Circuitry
Open-thermocouple detection circuitry can cause two types of
measurement errors. These errors are the results of common-mode voltage
at the input of the SCXI module and current leakage into the signal leads.
Common-Mode Voltage at the Input of the
SCXI Module
With 10 MΩ pull-up and bias resistors, a common-mode voltage of
2.5 VDC develops if the thermocouple is floating. At a gain of 100, the
common-mode rejection of the SCXI-1102/B/C module is sufficiently high
that the resulting offset error is negligible.
If the application demands extremely high accuracy, you can eliminate this
offset error by calibrating the system with both the pull-up and
ground-referencing resistor switches ON. You also can turn off the pull-up
resistor switch, which eliminates the open-thermocouple detection feature,
or use the 10 Ω ground-referencing resistor networks, which brings the
common-mode voltage down to nearly 0 VDC.
Current Leakage
The open-thermocouple detection circuitry results in a small current
leakage into the thermocouple. With the 10 MΩ bias and pull-up resistor
networks, the current leakage results in a negligible error. With the
10 Ω bias resistor, the 10 MΩ pull-up resistor connected to 5 VDC causes
a current leakage of approximately 0.5 µA (5 VDC/10 MΩ) to flow into the
unbroken thermocouple.
If the thermocouple is lengthy, a voltage drop develops in the thermocouple
because of lead resistance. For example, if you have a 24 AWG J-type
thermocouple that is 20 feet long, a voltage drop of approximately 8 µV
can develop in the thermocouple, which corresponds to an error of 0.18 °C
according to the following equation:
Voltage drop value = (0.145 Ω/ft + 0.658 Ω/ft) × 20 ft × 0.5 µA
If the application demands high accuracy, you can eliminate the voltage
drop inaccuracy error by turning off the appropriate pull-up resistor
network or by calibrating the system offset. For the location of these
switches, refer to Figure 3.
BNC/TC-2095 Rack-Mount Adapter Installation Guide
16
ni.com
Specifications
All specifications are typical at 25 °C, unless otherwise specified.
Electrical
Cold-junction sensor (TC-2095 Only)
Accuracy1 ........................................ 0.65° from 15 to 35 °C
1.0° from 0 to 15 °C
and 35 to 55 °C
Repeatability ................................... 0.35° from 15 to 35 °C
Output ............................................. 1.91 (at 0 °C) to 0.58 VDC
(at 55 °C)
Open-thermocouple detection
Pull-up resistor ................................ 10 MΩ
Ground-referencing resistor ............ 10 Ω default or 10 MΩ
Physical
Dimensions ..................................... 48.3 cm by 4.4 cm by 19.0 cm
(19.0 in. by 1.7 in. by 7.7 in.)
Maximum Working Voltage
Maximum working voltage
(signal + common mode) ....................... Each input should remain
within ±10 VDC of chassis
ground
Environmental
Operating temperature............................ 0 to 50 °C
Storage temperature ............................... –20 to 70 °C
Humidity ................................................ 10 to 90% RH, noncondensing
Maximum altitude .................................. 2,000 m
Pollution Degree (indoor use only) ........ 2
1
Includes the combined effects of the temperature sensor accuracy and the temperature difference between the temperature
sensor and any screw terminal. The temperature sensor accuracy includes tolerances in all component values, the effect caused
by temperature and loading, and self-heating.
© National Instruments Corporation
17
BNC/TC-2095 Rack-Mount Adapter Installation Guide
Safety
This product is designed to meet the requirements of the following
standards of safety for electrical equipment for measurement, control,
and laboratory use:
•
IEC 61010-1, EN 61010-1
•
UL 3111-1, UL 61010B-01
•
CAN/CSA C22.2 No. 1010.1
Note For UL and other safety certifications, refer to the product label, or visit
ni.com/hardref.nsf, search by model number or product line, and click the
appropriate link in the Certification column.
Electromagnetic Compatibility
Emissions................................................EN 55011 Class A at 10 m
FCC Part 15A above 1 GHz
Immunity ................................................EN 61326:1997+A2:2001,
Table 1
EMC/EMI ...............................................CE, C-Tick, and FCC Part 15
(Class A) Compliant
Note
For EMC compliance, you must operate this device with shielded cabling.
CE Compliance
This product meets the essential requirements of applicable European
directives, as amended for CE marking, as follows:
Low-Voltage Directive (safety)..............73/23/EEC
Electromagnetic Compatibility
Directive (EMC) .....................................89/336/EEC
Refer to the Declaration of Conformity (DoC) for this product for any additional
regulatory compliance information. To obtain the DoC for this product, visit
ni.com/hardref.nsf, search by model number or product line, and click the
appropriate link in the Certification column.
Note
BNC/TC-2095 Rack-Mount Adapter Installation Guide
18
ni.com
National Instruments™, NI™, ni.com™, and SCXI™ are trademarks of National Instruments
Corporation. Product and company names mentioned herein are trademarks or trade names of their
respective companies. For patents covering National Instruments products, refer to the appropriate
location: Help»Patents in your software, the patents.txt file on your CD, or ni.com/patents.
© 1999–2003 National Instruments Corp. All rights reserved.
*321731B-01*
321731B-01
Oct03