DIESEL GENERATOR SET MTU 4R0113 DS125

DIESEL GENERATOR SET
MTU 4R0113 DS125
125 kWe /60 Hz /Standby
208 - 600V
Reference MTU 4R0113 DS125 (111 kWe) for Prime Rating Technical Data
SYSTEM RATINGS
Standby
Voltage (L-L)
Phase
PF
Hz
kW
kVA
Amps
skVA@30%
Voltage Dip
Generator Model
Temp Rise
Connection
240V**
1
1
60
125
125
520
240V**
1
1
60
125
125
520
208V**
3
0.8
60
125
156
433
240V**
3
0.8
60
125
156
375
480V**
3
0.8
60
125
156
188
600V**
3
0.8
60
125
156
150
187
431PSL6206
130 °C/40 °C
192
431PSL6224
130 °C/40 °C
323
363CSL1607
130 °C/40 °C
323
363CSL1607
130 °C/40 °C
430
363CSL1607
130 °C/40 °C
333
363PSL1658
130 °C/40 °C
12 LEAD ZIG-ZAG
4 LEAD
12 LEAD LOW WYE
12 LEAD HI DELTA
12 LEAD HI WYE
4 LEAD WYE
** UL 2200 Offered
CERTIFICATIONS AND STANDARDS
// Emissions – EPA Tier 3 Certified
// Generator set is designed and manufactured
in facilities certified to standards ISO 9001:2008 and
ISO 14001:2004
// Seismic Certification – Optional
– IBC Certification
– OSHPD Pre-Approval
// UL 2200 / CSA – Optional
– UL 2200 Listed
– CSA Certified
// Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for
Transient Response
- Verified product design, quality and performance integrity
- All engine systems are prototype and factory tested
// Power Rating
- Accepts Rated Load in One Step Per NFPA 110
2
/ // /
MTU 4R0113 DS125 (125 kWe) - Standby
STANDARD FEATURES*
MTU Onsite Energy is a single source supplier
Global Product Support
2 Year Standard Warranty
4045HF285 Diesel Engine
- 4.58 Liter Displacement
- 4-Cycle
// Engine-generator resilient mounted
// Complete Range of Accessories
// // // // Generator
- Brushless, Rotating Field Generator
- 2/3 Pitch Windings
- 300% Short Circuit Capability with Optional PMG
// Digital Control Panel(s)
- UL Recognized, CSA Certified, NFPA 110
- Complete System Metering
- LCD Display
// Cooling System
- Integral Set-Mounted
- Engine Driven Fan
// STANDARD EQUIPMENT*
// Engine
Air Cleaners
Oil Pump
Oil Drain Extension & S/O Valve
Full Flow Oil Filter
Fuel Filter with Water Separator
Jacket Water Pump
Thermostat
Blower Fan & Fan Drive
Radiator - Unit Mounted
Electric Starting Motor - 12V
Governor – Electronic Isochronous
Base - Formed Steel
SAE Flywheel & Bell Housing
Charging Alternator - 12V
Battery Box & Cables
Flexible Fuel Connectors
Flexible Exhaust Connection
EPA Certified Engine
// Generator
NEMA MG1, IEEE and ANSI standards compliance for temperature rise
and motor starting
Self-Ventilated and Drip-Proof
Superior Voltage Waveform
Solid State, Volts-per-Hertz Regulator
±1% Voltage Regulation No Load to Full Load
Brushless Alternator with Brushless Pilot Exciter
4 Pole, Rotating Field
130 °C Maximum Standby Temperature Rise
1 Bearing, Sealed
Flexible Coupling
Full Amortisseur Windings
125% Rotor Balancing
3-Phase Voltage Sensing
100% of Rated Load - One Step
5% Maximum Total Harmonic Distortion
// Digital Control Panel(s)
Digital Metering
Engine Parameters
Generator Protection Functions
Engine Protection
SAE J1939 Engine ECU Communications
Windows®-Based Software
Multilingual Capability
Remote Communications to RDP-110 Remote Annunciator
Programmable Input and Output Contacts
UL Recognized, CSA Certified, CE Approved
Event Recording
IP 54 Front Panel Rating with Integrated Gasket
NFPA110 Compatible
* Represents standard product only. Consult Factory/MTU Onsite Energy Distributor for additional configurations.
3
/ // /
MTU 4R0113 DS125 (125 kWe) - Standby
APPLICATION DATA
// Engine
Manufacturer
Model
Type
Arrangement
Displacement: L (in3)
Bore: cm (in)
Stroke: cm (in)
Compression Ratio
Rated RPM
Engine Governor
Maximum Power: kWm (bhp)
Speed Regulation
Air Cleaner
// John Deere
4045HF285
4-Cycle
4-Inline
4.5 (275)
10.6 (4.19)
12.7 (5)
19:1
1,800
JDEC
147 (197)
±0.25%
Dry
Fuel Consumption
At 100% of Power Rating: L/hr (gal/hr)
At 75% of Power Rating: L/hr (gal/hr)
At 50% of Power Rating: L/hr (gal/hr)
// 37.3 (9.9)
28.8 (7.6)
19.3 (5.1)
Cooling - Radiator System
Ambient Capacity of Radiator: °C (°F)
Maximum Allowable Static
Pressure on Rad. Exhaust: kPa (in. H20)
Water Pump Capacity: L/min (gpm)
Heat Rejection to Coolant: kW (BTUM )
Heat Rejection to Air to Air: kW (BTUM )
Heat Radiated to Ambient: kW (BTUM )
Fan Power: kW (hp)
50 (122)
0.12 (0.5)
180 (48)
72.1 (4,098)
26.5 (1,508)
19.9 (1,134)
10.6 (14.2)
Liquid Capacity (Lubrication)
Total Oil System: L (gal)
Engine Jacket Water Capacity: L (gal)
System Coolant Capacity: L (gal)
// // 13 (3.4)
8.5 (2.2)
24 (6.2)
Electrical
Electric Volts DC
Cold Cranking Amps Under -17.8 °C (0 °F)
12
925
// Air Requirements
Aspirating: *m3/min (SCFM)
Air Flow Required for Rad.
Cooled Unit: *m3/min (SCFM)
Remote Cooled Applications;
Air Flow Required for Dissipation
of Radiated Gen-set Heat for a
Max of 25 °F Rise: *m3/min (SCFM)
9.7 (341)
433 (15,303)
71 (2,520)
* Air density = 1.184 kg/m3 (0.0739 lbm/ft3)
// Fuel System
Fuel Supply Connection Size
Fuel Return Connection Size
Maximum Fuel Lift: m (ft)
Recommended Fuel
Total Fuel Flow: L/hr (gal/hr)
3/8” NPT
3/8” NPT
2 (6.7)
Diesel #2
90.1 (23.8)
// Exhaust System
Gas Temp. (Stack): °C (°F)
Gas Volume at Stack
Temp: m3/min (CFM)
Maximum Allowable
Back Pressure: kPa (in. H20)
580 (1,076)
27 (953)
7.5 (30)
4
/ // /
MTU 4R0113 DS125 (125 kWe) - Standby
WEIGHTS AND DIMENSIONS
Drawing above for illustration purposes only, based on standard open power 480 volt generator set. Lengths may vary with other voltages. Do not use for installation design.
See website for unit specific template drawings.
System
Open Power Unit (OPU)
Dimensions (L x W x H)
2,540 x 1,219 x 1,499 mm (100 x 48 x 59 in)
Weight (less tank)
971 kg (2,140 lb)
SOUND DATA
Unit Type
Level 0: Open Power Unit dB(A)
Standby Full Load
86.8
Sound data is provided at 7 m (23 ft). Generator set tested in accordance with ISO 8528-10 and with infinite exhaust.
EMISSIONS DATA
NOx + NMHC
5.02
CO
0.16
RATING DEFINITIONS AND CONDITIONS
PM
0.01
All units are in g/hp-hr and shown at 100% load
(not comparable to EPA weighted cycle values).
Emission levels of the engine may vary with ambient
temperature, barometric pressure, humidity, fuel type and
quality, installation parameters, measuring instrumentation, etc.
The data was obtained in compliance with US EPA regulations.
The weighted cycle value (not shown) from each engine
is guaranteed to be within the US EPA Standards. 5-mode
emission data per 40 CFR 89 or 40 CFR 1039 (as applicable) is
available upon request.
C/F = Consult Factory/MTU Onsite Energy Distributor
N/A = Not Availabler
MTU Onsite Energy
A Rolls-Royce Power Systems Brand
www.mtuonsiteenergy.com
Standby ratings apply to installations served by a reliable
utility source. The standby rating is applicable to varying
loads for the duration of a power outage. No overload
capability for this rating. Ratings are in accordance with
ISO 3046-1, BS 5514, and AS 2789. Average load
factor: ≤ 85%.
// Deration Factor:
Altitude: Consult your local MTU Onsite Energy Power
Generation Distributor for altitude derations.
Temperature: Consult your local MTU Onsite Energy Power
Generation Distributor for temperature derations.
// © MTU Onsite Energy. Subject to alteration due to technological advances. OE 23 463 (77 3E) 2015-07
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set.