DIESEL GENERATOR SET MTU 4R0113 DS40

DIESEL GENERATOR SET
MTU 4R0113 DS40
40 kWe /60 Hz /Standby
208 - 600V
Reference MTU 4R0113 DS40 (40 kWe) for Prime Rating Technical Data
SYSTEM RATINGS
Standby
Voltage (L-L)
Phase
PF
Hz
kW
kVA
Amps
skVA@30%
Voltage Dip
Generator Model
Temp Rise
Connection
240V**
1
1
60
40
40
166
208V**
3
0.8
60
40
50
138
240V**
3
0.8
60
40
50
120
380V**
3
0.8
60
40
50
76
480V**
3
0.8
60
40
50
60
600V**
3
0.8
60
40
50
48
63
361CSL1601
130 °C/40 °C
129
361CSL1601
130 °C/40 °C
129
361CSL1601
130 °C/40 °C
112
361CSL1601
130 °C/40 °C
172
361CSL1601
130 °C/40 °C
92
361PSL1632
130 °C/40 °C
12 LEAD
DOUBLE DELTA
12 LEAD LOW WYE
12 LEAD HI DELTA
12 LEAD HI WYE
12 LEAD HI WYE
4 LEAD WYE
** UL 2200 Offered
CERTIFICATIONS AND STANDARDS
// Emissions – EPA Tier 3 Certified
// Generator set is designed and manufactured in
facilities certified to standards ISO 9001:2008 and
ISO 14001:2004
// UL 2200 / CSA – Optional
– UL 2200 Listed
– CSA Certified
// Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for Transient Response
- Verified product design, quality and performance integrity
- All engine systems are prototype and factory tested
// Power Rating
- Accepts Rated Load in One Step Per NFPA 110
2
/ // / MTU 4R0113 DS40 (40 kWe) - Standby
STANDARD FEATURES*
MTU Onsite Energy is a single source supplier
Global Product Support
2 Year Standard Warranty
4045TF280 Diesel Engine
- 4.5 Liter Displacement
- Mechanical Injection Pump
- 4-Cycle
// Engine-generator resilient mounted
// Complete Range of Accessories
// // // // Generator
- Brushless, Rotating Field Generator
- 2/3 Pitch Windings
- 300% Short Circuit Capability with Optional PMG
// Digital Control Panel(s)
- UL Recognized, CSA Certified, NFPA 110
- Complete System Metering
- LCD Display
// Cooling System
- Integral Set-Mounted
- Engine Driven Fan
// STANDARD EQUIPMENT*
// Engine
Air Cleaner
Oil Pump
Oil Drain Extension & S/O Valve
Full Flow Oil Filter
Fuel Filter with Water Separator
Jacket Water Pump
Thermostat
Blower Fan & Fan Drive
Radiator - Unit Mounted
Electric Starting Motor - 12V
Governor – Mechanical Droop
Base - Formed Steel
SAE Flywheel & Bell Housing
Charging Alternator - 12V
Battery Box & Cables
Flexible Fuel Connectors
Flexible Exhaust Connection
EPA Certified Engine
// Generator
NEMA MG1, IEEE and ANSI standards compliance for temperature rise
and motor starting
Self-Ventilated and Drip-Proof
Superior Voltage Waveform
Solid State, Volts-per-Hertz Regulator
±1% Voltage Regulation No Load to Full Load
Brushless Alternator with Brushless Pilot Exciter
4 Pole, Rotating Field
130 °C Maximum Standby Temperature Rise
1 Bearing, Sealed
Flexible Coupling
Full Amortisseur Windings
125% Rotor Balancing
3-Phase Voltage Sensing
100% of Rated Load - One Step
5% Maximum Total Harmonic Distortion
// Digital Control Panel(s)
Digital Metering
Engine Parameters
Generator Protection Functions
Engine Protection
Windows®-Based Software
Multilingual Capability
Remote Communications to RDP-110 Remote Annunciator
Programmable Input and Output Contacts
UL Recognized, CSA Certified, CE Approved
Event Recording
IP 54 Front Panel Rating with Integrated Gasket
NFPA110 Compatible
* Represents standard product only. Consult Factory/MTU Onsite Energy Distributor for additional configurations.
3
/ // / MTU 4R0113 DS40 (40 kWe) - Standby
APPLICATION DATA
// Engine
Manufacturer
Model
Type
Arrangement
Displacement: L (in3)
Bore: cm (in)
Stroke: cm (in)
Compression Ratio
Rated RPM
Engine Governor
Maximum Power: kWm (bhp)
Speed Regulation
Air Cleaner
// // John Deere
4045TF280
4-Cycle
4-Inline
4.5 (275)
10.6 (4.19)
12.7 (5)
19.0:1
1,800
Mechanical Droop
63 (85)
±0.5%
Dry
At 100% of Power Rating: L/hr (gal/hr)
At 75% of Power Rating: L/hr (gal/hr)
At 50% of Power Rating: L/hr (gal/hr)
// 17.4 (4.6)
13.6 (3.6)
9.5 (2.5)
Cooling - Radiator System
Ambient Capacity of Radiator: °C ( °F)
Maximum Allowable Static
Pressure on Rad. Exhaust: kPa (in. H20)
Water Pump Capacity: L/min (gpm)
Heat Rejection to Coolant: kW (BTUM)
Heat Radiated to Ambient: kW (BTUM)
Fan Power: kW (hp)
50 (122)
0.12 (0.5)
144 (38)
36 (2,049)
6.8 (384)
1.6 (2.2)
Liquid Capacity (Lubrication)
// Total Oil System: L (gal)
Engine Jacket Water Capacity: L (gal)
System Coolant Capacity: L (gal)
// Fuel Consumption
13 (3.4)
8.5 (2.3)
18.9 (5)
Electrical
Electric Volts DC
Cold Cranking Amps Under -17.8 °C (0 °F)
12
925
Air Requirements
Aspirating: *m3/min (SCFM)
Air Flow Required for Rad.
Cooled Unit: *m3/min (SCFM)
Remote Cooled Applications;
Air Flow Required for Dissipation
of Radiated Gen-set Heat for a
Max of 25 °F Rise: *m3/min (SCFM)
5.3 (187)
117 (4,088)
25 (867)
* Air density = 1.184 kg/m3 (0.0739 lbm/ft3)
// Fuel System
// Fuel Supply Connection Size
Fuel Return Connection Size
Maximum Fuel Lift: m (ft)
Recommended Fuel
Total Fuel Flow: L/hr (gal/hr)
3/8” NPT
3/8” NPT
1.8 (6)
Diesel #2
62.5 (16.5)
Exhaust System
Gas Temp. (Stack): °C (°F)
Gas Volume at Stack
Temp: m3/min (CFM)
Maximum Allowable
Back Pressure: kPa (in. H20)
Minimum Allowable
Back Pressure: kPa (in. H20)
579 (1,074)
19.2 (679)
7.5 (30)
N/A
4
/ // / MTU 4R0113 DS40 (40 kWe) - Standby
WEIGHTS AND DIMENSIONS
Drawing above for illustration purposes only, based on standard open power 480 volt generator set. Lengths may vary with other voltages. Do not use for installation design. See website
for unit specific template drawings.
System
Open Power Unit (OPU)
Dimensions (L x W x H)
1,781 x 800 x 1,321 mm (70.13 x 31.5 x 52 in)
Weight (dry/less tank)
872 kg (1,920 lb)
SOUND DATA
Unit Type
Level 0: Open Power Unit dB(A)
Standby Full Load
80.5
Sound data is provided at 7 m (23 ft). Generator set tested in accordance with ISO 8528-10 and with infinite exhaust.
EMISSIONS DATA
NOx + NMHC
3.8
CO
0.69
RATING DEFINITIONS AND CONDITIONS
PM
0.22
All units are in g/hp-hr and shown at 100% load
(not comparable to EPA weighted cycle values).
Emission levels of the engine may vary with ambient
temperature, barometric pressure, humidity, fuel type and
quality, installation parameters, measuring instrumentation, etc.
The data was obtained in compliance with US EPA regulations.
The weighted cycle value (not shown) from each engine
is guaranteed to be within the US EPA Standards. 5-mode
emission data per 40 CFR 89 or 40 CFR 1039 (as applicable) is
available upon request.
C/F = Consult Factory/MTU Onsite Energy Distributor
N/A = Not Available
MTU Onsite Energy
A Rolls-Royce Power Systems Brand
www.mtuonsiteenergy.com
Standby ratings apply to installations served by a reliable
utility source. The standby rating is applicable to varying
loads for the duration of a power outage. No overload
capability for this rating. Ratings are in accordance with
ISO 3046-1, BS 5514, and AS 2789. Average load
factor: ≤ 85%.
// Deration Factor:
Altitude: Consult your local MTU Onsite Energy Power
Generation Distributor for altitude derations.
Temperature: Consult your local MTU Onsite Energy Power
Generation Distributor for temperature derations.
// © MTU Onsite Energy. Subject to alteration due to technological advances. OE 23 458 (77 3E) 2015-07
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set.