diesel generator set mtu 18v2000 ds1250

DIESEL GENERATOR SET
MTU 18V2000 DS1250
1000 kWe /60 Hz /Prime
380 - 4160V
Reference MTU 18V2000 DS1250 (1250 kWe) for Standby Rating Technical Data
SYSTEM RATINGS
Prime
Voltage (L-L)
Phase
PF
Hz
kW
kVA
Amps
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
380V**
3
0.8
60
1000
1250
1899
480V**
3
0.8
60
1000
1250
1504
600V**
3
0.8
60
1000
1250
1203
4160V
3
0.8
60
1000
1250
173
1870
742RSL4048
105 °C/40 °C
4 BAR WYE
2590
741RSL4045
105 °C/40 °C
4 BAR WYE
2590
741RSS4284
105 °C/40 °C
4 BAR WYE
2600
742FSM4364
105 °C/40 °C
6 LEAD WYE
* Consult the factory for alternate configuration.
** UL 2200 Offered
CERTIFICATIONS AND STANDARDS
// Emissions – Fuel consumption optimized
// Generator set is designed and manufactured
in facilities certified to standards ISO 9001:2008 and
ISO 14001:2004
// UL 2200 / CSA – Optional
// Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for Transient Response
- Verified product design, quality and performance integrity
- All engine systems are prototype and factory tested
// Power Rating
- Accepts Rated Load in One Step Per NFPA 110
- Permissible average power output during 24 hours of
operation is approved up to 75%.
2
/ // /
MTU 18V2000 DS1250 (1000 kWe) - Prime
STANDARD FEATURES*
MTU Onsite Energy is a single source supplier
Global Product Support
2 Year Standard Warranty
18V 2000 Diesel Engine
- 40.2 Liter Displacement
- Common Rail Fuel Injection
- 4-Cycle
// Engine-generator Resilient Mounted
// Complete Range of Accessories
// // // // Generator
- Brushless, Rotating Field Generator
- 2/3 Pitch Windings
- PMG (Permanent Magnet Generator) supply to regulator
- 300% Short Circuit Capability
// Digital Control Panel(s)
- UL Recognized, CSA Certified, NFPA 110
- Complete System Metering
- LCD Display
// Cooling System
- Integral Set-Mounted
- Engine Driven Fan
// STANDARD EQUIPMENT*
// Engine
Air Cleaners
Oil Pump
Oil Drain Extension & S/O Valve
Full Flow Oil Filter
Closed Crankcase Ventilation
Jacket Water Pump
Thermostat
Blower Fan & Fan Drive
Radiator - Unit Mounted
Electric Starting Motor - 24V
Governor – Electronic Isochronous
Base - Formed Steel
SAE Flywheel & Bell Housing
Charging Alternator - 24V
Battery Rack & Cables
Flexible Fuel Connectors
Flexible Exhaust Connection
// Generator
NEMA MG1, IEEE and ANSI standards compliance for temperature rise
and motor starting
Sustained short circuit current of up to 300% of the rated current for
up to 10 seconds
Self-Ventilated
Superior Voltage Waveform
Digital, Solid State, Volts-per-Hertz Regulator
No Load to Full Load Regulation
Brushless Alternator with Brushless Pilot Exciter
4 Pole, Rotating Field
105 °C Maximum Prime Temperature Rise
1 Bearing, Sealed
Flexible Coupling
Full Amortisseur Windings
125% Rotor Balancing
3-Phase Voltage Sensing
±0.25% Voltage Regulation
100% of Rated Load - One Step
5% Maximum Total Harmonic Distortion
// Digital Control Panel(s)
Digital Metering
Engine Parameters
Generator Protection Functions
Engine Protection
CANBus ECU Communications
Windows®-Based Software
Multilingual Capability
Remote Communications to RDP-110 Remote Annunciator
Programmable Input and Output Contacts
UL Recognized, CSA Certified
Event Recording
IP 54 Front Panel Rating with Integrated Gasket
NFPA110 Compatible
* Represents standard product only. Consult Factory/MTU Onsite Energy Distributor for additional configurations.
3
/ // /
MTU 18V2000 DS1250 (1000 kWe) - Prime
APPLICATION DATA
// Engine
Manufacturer
Model
Type
Arrangement
Displacement: L (in3)
Bore: cm (in)
Stroke: cm (in)
Compression Ratio
Rated RPM
Engine Governor
Maximum Power: kWm (bhp)
Speed Regulation
Air Cleaner
// // MTU
18V 2000 B76
4-Cycle
18-V
40.2 (2,448)
13.5 (5.3)
15.6 (6.15)
17.5
1,800
Electronic Isochronous (ADEC)
1,097 (1,471)
±0.25%
Dry
At 100% of Power Rating: L/hr (gal/hr)
At 75% of Power Rating: L/hr (gal/hr)
At 50% of Power Rating: L/hr (gal/hr)
// 254 (67)
192 (51)
133 (35)
Cooling - Radiator System
Ambient Capacity of Radiator: °C (°F)
Maximum Restriction of Cooling Air, Intake,
and Discharge Side of Rad.: kPa (in. H20)
Water Pump Capacity: L/min (gpm)
Heat Rejection to Coolant: kW (BTUM)
Heat Rejection to After Cooler: kW (BTUM)
Heat Radiated to Ambient: kW (BTUM)
Fan Power: kW (hp)
50 (122)
0.13 (0.5)
950 (251)
430 (24,454)
285 (16,208)
107 (6,079)
33.5 (44.9)
Liquid Capacity (Lubrication)
Total Oil System: L (gal)
Engine Jacket Water Capacity: L (gal)
System Coolant Capacity: L (gal)
// Fuel Consumption
122 (32.2)
73 (19.3)
185 (48.9)
Electrical
Electric Volts DC
Cold Cranking Amps Under -17.8 °C (0 °F)
24
2,800
// Air Requirements
Aspirating: *m3/min (SCFM)
Air Flow Required for Rad.
Cooled Unit: *m3/min (SCFM)
Remote Cooled Applications;
Air Flow Required for Dissipation
of Radiated Gen-set Heat for a
Max of 25 °F Rise: *m3/min (SCFM)
96.6 (3,411)
1,512 (53,396)
390 (13,710)
* Air density = 1.184 kg/m3 (0.0739 lbm/ft3)
// Fuel System
Fuel Supply Connection Size
Fuel Return Connection Size
Maximum Fuel Lift: m (ft)
Recommended Fuel
Total Fuel Flow: L/hr (gal/hr)
#12 JIC 37° Female
1” NPT Adapter Provided
#12 JIC 37° Female
1” NPT Adapter Provided
5 (16)
Diesel #2
1,380 (365)
// Exhaust System
Gas Temp. (Stack): °C (°F)
Gas Volume at Stack
Temp: m3/min (CFM)
Maximum Allowable
Back Pressure: kPa (in. H20)
420 (788)
222 (7,840)
5 (20)
4
/ // /
MTU 18V2000 DS1250 (1000 kWe) - Prime
WEIGHTS AND DIMENSIONS
Drawing above for illustration purposes only, based on standard open power 480 volt generator set. Lengths may vary with other voltages. Do not use for installation design. See website
for unit specific template drawings.
System
Open Power Unit (OPU)
Dimensions (L x W x H)
5,036 x 2,275 x 2,454 mm (198.3 x 89.6 x 96.6 in)
Weight (dry/less tank)
9,525 kg (21,000 lb)
SOUND DATA
Unit Type
Level 0: Open Power Unit dB(A)
Prime Full Load
90.2
Sound data is provided at 7 m (23 ft). Generator set tested in accordance with ISO 8528-10 and with infinite exhaust.
EMISSIONS DATA
NOx + NMHC
C/F
CO
C/F
RATING DEFINITIONS AND CONDITIONS
PM
C/F
All units are in g/hp-hr and at 100% load.
Emission levels of the engine may vary as a function of ambient
temperature, barometric pressure, humidity, fuel type and
quality, installation parameters, measuring instrumentation,
etc. The data provided are laboratory results from one
engine representing this rating. The data was obtained
under controlled environmental conditions with calibrated
instrumentation traceable to the United States National Bureau
of Standards and in compliance with US EPA regulations found
within 40 CFR Part 89. The weighted cycle value (not shown)
from each engine is guaranteed to be below the US EPA
Standards at the US EPA defined conditions.
C/F = Consult Factory/MTU Onsite Energy Distributor
N/A = Not Available
MTU Onsite Energy
A Rolls-Royce Power Systems Brand
www.mtuonsiteenergy.com
Prime power ratings apply to installations where utility power
is unavailable or unreliable. At varying load, the number of
generator set operating hours is unlimited. A 10% overload
capacity is available for one hour in twelve. Ratings are in
accordance with ISO 8528-1, ISO 3046-1, BS 5514, and
AS 2789. Average load factor: ≤ 75%.
// Deration Factor:
Altitude: Consult your local MTU Onsite Energy Power
Generation Distributor for altitude derations.
Temperature: Consult your local MTU Onsite Energy Power
Generation Distributor for temperature derations.
// © MTU Onsite Energy. Subject to alteration due to technological advances. OE 23 948 (77 3E) 2014-10
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set.