AZ Series Flying Lead Current Transformers Very high output voltage & Linearity in small size Integral flying for ease of installation Large center-hole allows 6.3mm tabs Dielectric withstand voltage 4KVrms Operating temperature range -40 to +85ºC All materials UL94-V0 3 Compliance RoHS Electrical Specifications @ 20°C AZ-0500 AZ-0750 AZ-1000 Operating Frequency in Hz 50/60 50/60 50/60 Maximum Primary current in Amps 25 40 50 Lead Outs Turns Ratio Nominal 500:1 750:1 1000:1 DC Resistance in Ω Nominal 18 35 72 Flex UL1569 AWG24, 300V Rating,250±5mm long out of trafo with 5mm tinned ends Rated Burden Resistance in Ω 33 33 33 Mechanical Drawing Input current vs Output voltage 21.5 AZ-0500 3.000 Ø7.0 2.500 5±1 tinned Output Volts 2.000 Ø19.0 250±5mm 1.500 33 Ohms 1.000 0.500 0.000 0 10 20 30 40 Input Amps 11.5 Input current vs Output voltage Input current vs Output voltage AZ-1000 3.000 2.500 2.500 2.000 2.000 1.500 Output Volts Output Volts AZ-0750 3.000 33 Ohms 1.000 1.500 33 Ohms 1.000 0.500 0.500 0.000 0.000 0 10 20 30 Input Amps 40 50 60 0 10 20 30 40 50 60 70 80 Input Amps Germany: Int.+49 89 - 841 00-0 • Ireland: Int.+35 374 - 954 8666 • Czech Rep: Int.+420 37 - 744 9303 • India: Int.+91 427 - 244 1325 http://www.talema-nuvotem.com Initial Release Nov-11