400 Series Plug-In Thermal Detectors

400 Series Plug-In
Thermal Detectors
System Sensor 400 Series plug-in thermal detectors
meet the performance criteria designated by
Underwriters Laboratories.
Features
•Low standby current
•Two visible LEDs “blink” in standby and provide a 360° field
viewing angle
•Wide variety of mounting bases with built-in shorting spring
•Detector head plugs easily into base
•Built-in test switch
•Field sensitivity metering of detector to meet the requirements
of NFPA 72
•Built-in tamper-resistant feature
•SEMS screws for easy wiring
•Optional recessed mounting
Agency Listings
S2101
OB3AO.AY
7270-1653:104
The 5451 thermal detector meets the needs for applications
where rapid response is vital and rapid temperature increases would
only be caused by a fire emergency.
This detector contains a unique dual thermistor heat sensing circuit
that provides maximum performance and solid-state reliability. It
initiates an alarm in response to both rapid rate-of-rise conditions
(increases in excess of 15°F per minute) and fixed heat (135°F). This
enables the heat detector to communicate an alarm to the central
control panel prior to reaching its fixed set point for high rates of
rise, providing a timely response to both rapid and slow temperature
increases.
Additional key features include a recessed mounting option, a variety
of mounting bases, and a full line of optional accessories.
400 Series Plug-In Smoke Detector Specifications
Physical/Operating Specifications
Size
Weight
Operating Temperature Range
Humidity Range
Construction
Alarm Point
Smoke Detector Spacing
Standby Current
Operating Voltage/Alarm Current
Mounting Base Selection Guide
Base Model Number
3.2˝ (8.1 cm) H; 4.0˝ (10.2 cm) Dia., unflanged base; 6.2˝ (15.7 cm) Dia., flanged base
0.3 lb (136 g)
32°F to 100°F (0°C to 38°C)
10% to 93% RH non-condensing
Flame retardant Noryl® plastic
135°F (57.2°C) or 15°F/min rate-of-rise
On smooth ceilings (as defined in NFPA 72), spacing of 50 feet (2500 sq ft) may be used. Other spacing may be used
depending on ceiling height, high air movements, and other conditions or response requirements.
100 µA maximum
Mounting base dependent (see Mounting Base Selection Guide below)
Version
Loop
Type
2-wire*
B401†
UL/EN-54
*Functionality contingent on panel compatibility.
**Must be limited by control panel.
Current
Limit Resistor
No
Alarm
Contact Type
—
Nominal
Current Draw
Voltage
on Alarm (mA)
12/24 VDC††
10 to 100**
†
Flangeless base
††
Although B401 bases are capable
of operating at 12 and 24 VDC, they
cannot be used with the 5451 in 12
V applications.
Junction Box Selection Guide*
B401
Single Gang
3.5” Octagon
4” Octagon
4” Square
50 mm
60 mm
75 mm
No
No
No
No
Yes
Yes
No
*Box depth contingent on base and wire size. Refer to National Electrical Code of local applicable codes for appropriate recommendations.
Wiring
Accessories
(–)
(–)
(–)
OPTIONAL
RA400Z/
RA100Z
OPTIONAL
(+)
RA400Z/
RA100Z
(–)
(–)
2
(–)
(–)
2
3
(+)
1
4
(+)
(+)
3
EOL
RESISTOR
1
4
(+)
The MOD400R Field Sensitivity
Test Module can be used with
any standard DC voltmeter or
multimeter to check the sensitivity
range of System Sensor’s detectors
(satisfies NFPA 72 requirement for
sensitivity testing).
(+)
OPTIONAL FAULT TOLERANT WIRING
B401
Ordering Information
Part No.
5451
Accessories
RA100Z
MOD400R
EOLR-1
DUST45
M02-04-01
M02-09-00
XR5
XP-4
Description
Fixed heat detector with rate-of-rise. Alarm point at 57.2°C (135°F). Must be mounted to one of the 400 Series Bases listed in Mounting Base
Guide.
Remote annunciator for 2- or 4-wire systems, 3 to 32 V. Use with ion and photo plug-in detectors. Fits standard U.S. single-gang electrical box.
Detector sensitivity test tool. (See above.) Use with most analog or digital multimeters. Satisfies requirement of NFPA 72 for sensitivity testing.
(See above.)
End of line relay for power supervision, 12/24 VDC, 4-wire only.
Replacement protective dust cover for plug-in 400 Series.
Test magnet.
Test magnet with 32-inch telescoping handle.
Detector removal tool. Allows installation and/or removal of detector heads from base in high-ceiling installations.
Extension pole for XR5. Comes in three 5 ft. sections.
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
©2011 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com for
current product information, including the latest version of this data sheet.
A05-0205-009 • 3/11 • #2651