MOD400R Test Module - SmartHome

INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
MOD400R Test Module
Figure 1:
General Description
The MOD400R Test Module is a tool testing the relative
sensitivity of 100, 200, 300, 400, and 500 Series smoke
detectors only. It CANNOT be used on 800 Series detectors.
It consists of a test module and interface cord for connecting the module to the detector being tested.
This battery powered module is equipped with two colorcoded banana jacks for the connection of any analog or digital DC voltmeter having a sensitivity of 10 kΩ/V or greater.
As an added convenience, two adhesive-backed Velcro®
strips are also supplied for attaching the module to the
meter being used during testing.
Test module function is under the control of a 3-position
and a 2-position slide switch on the side of the unit.
Various combinations of positions of these two switches
enable the module to test conventional and analog ionization and photoelectronic smoke detectors as well as checking the battery. In addition, the 3-position switch, SW1, has
a center-OFF position for turning off the module. Therefore,
conserve battery life by always setting this switch to OFF
when the module is not in use.
A78-2075-00
CAUTION
Failure to insert and retract this plug in the direction shown
may result in damage to the pins. Handle with care. Inspect
pins regularly for damage to ensure proper operation.
MOD400R Setup
1. Connect a voltmeter having a sensitivty of 10 kΩ/V or
greater to the banana jacks on the side of the
MOD400R. Be sure to connect the positive test lead to
the red jack and the negative lead to the black.
2. Connect the interface cord to the RJ-11 telephone jack on
the bottom edge of the module.
3. Test the MOD400R battery as described in BATTERY
TESTING.
the detector. This corresponds to the NOMINAL SENS.
(sensitivity) on the label.
If the voltmeter displays a voltage outside the
MOD400(R) RANGE, it indicates that the detector
requires cleaning or repair.
6. Disconnect the MOD400R from the detector and set SW1
to OFF.
Smoke Detector Testing
Conventional Ion
1. Prepare the MOD400R for testing by performing the procedure in MOD400R SETUP.
2. Set the voltmeter to measure at least 3 VDC.
3. Make sure that power is applied to the detector to be
tested.
4. Set SW1 to its A position and the 2-position switch, SW2,
to CONV.
5. See Figure 1. Insert the test plug into the test module
socket on the detector.
The voltmeter should display a voltage that falls in the
MOD400(R) RANGE printed on the label on the back of
M400-02-01
Conventional Photoelectronic Detectors
1. Prepare the MOD400R for testing by performing the procedure in MOD400R SETUP.
2. Set the voltmeter to measure at least 3 VDC.
3. Make sure that power is applied to the detector to be
tested.
4. Set SW1 to its B position and the 2-position switch, SW2,
to CONV.
5. See Figure 1. Insert the test plug into the test module
socket on the detector.
The voltmeter should display a voltage that falls in the
MOD400(R) RANGE printed on the label on the back of
1
I56-511-02
Battery Testing
The MOD400R operates from a single 9 volt alkaline battery whose life expectancy is approximately one year.
However, it should be tested before each use of the
MOD400R to ensure accurate sensitivity measurements.
the detector. This corresponds to the NOMINAL SENS.
(sensitivity) on the label.
If the voltmeter displays a voltage outside the
MOD400(R) RANGE, it indicates that the detector
requires cleaning or repair.
6. Disconnect the MOD400R from the detector and set SW1
to OFF.
To test the battery:
1. Make sure that the MOD400R is NOT connected to any
detector or sensor.
2. Set a voltmeter having a sensitivity of at least 10 kΩ/V
to measure 9 VDC.
3. Connect the meter to the banana jacks on the side of the
MOD400R. Be sure to connect the positive lead to the
red jack and the negative lead to the black.
4. Set SW1 to its A position and read the meter. It should
indicate at least 5.5 VDC. If it does not, replace the 9 volt
alkaline battery.
Intelligent Sensors
NOTE: The MOD400R can be used to test the sensitivity of
only those sensors connected to control panels that
do NOT use drift compensation.
1. Prepare the MOD400R for testing by performing the procedure in MOD400R SETUP.
2. Set the voltmeter to measure at least 3 VDC.
3. Make sure that power is applied to the sensor to be tested.
4. Set SW1 to its B position and the 2-position switch, SW2
to INT.
5. See Figure 1. Insert the test plug into the test module
socket on the detector.
The voltmeter should display a voltage that falls in the
MOD400(R) RANGE printed on the label on the back of
the sensor. This corresponds to the NOMINAL SENS.
(sensitivity) on the label.
If the voltmeter displays a voltage outside the
MOD400(R) RANGE, it indicates that the sensor
requires cleaning or repair.
6. Disconnect the MOD400R from the detector and set SW1
to OFF.
WARNING
The Limitations of the MOD400R
The MOD400R is designed to “... assure that each smoke detector is within
its listed and marked sensitivity range ...” per NFPA 72. The MOD400R
CANNOT, however, initiate a detector/sensor alarm. Therefore, the
MOD400R meets only part of NFPA 72 testing standards.
reading is within the specified range. These fluctuations are to be expected.
The MOD400R and its associated smoke detectors/sensors contain electronic parts and, though they are designed to last over 10 years, any of these
components can fail at any time. Therefore, it is recommended to test your
smoke detectors/sensors per NFPA 72 at least semiannually. Regular cleaning and testing of your fire detection system will measurably reduce your
product liability risks and minimize nuisance alarms.
Slight fluctuations in readings may be experienced on any device at any
given time and do not indicate a defect or sensitivity shift, provided the
Three-Year Limited Warranty
System Sensor warrants its enclosed MOD400R to be free from defects in
materials and workmanship under normal use and service for a period of
three years from date of manufacture. System Sensor makes no other
express warranty for this MOD400R. No agent, representative, dealer, or
employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this
Warranty shall be limited to the repair or replacement of any part of the
MOD400R which is found to be defective in materials or workmanship
under normal use and service during the three year period commencing
with the date of manufacture. After phoning System Sensor’s toll free
number 800-SENSOR2 (736-7672) for a Return Authorization number,
send defective units postage prepaid to: System Sensor, Repair
M400-02-01
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174.
Please include a note describing the malfunction and suspected cause of
failure. The Company shall not be obligated to repair or replace units
which are found to be defective because of damage, unreasonable use,
modifications, or alterations occurring after the date of manufacture. In no
case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence
or fault. Some states do not allow the exclusion or limitation of incidental
or consequential damages, so the above limitation or exclusion may not
apply to you. This Warranty gives you specific legal rights, and you may
also have other rights which vary from state to state.
2
I56-511-02
© System Sensor 1996