2112/24ATR Photoelectronic Smoke Detector with

3. Remove screen assembly, pulling straight out (please
see Figure 5).
4. Remove the sensing chamber cover.
5. Clean the sensing chamber by vacuuming or blowing
out dust and particles.
6. Replace the sensing chamber cover, aligning the arrow
on the cover top with the arrow on the printed circuit
board.
7. Replace the screen by placing the screen assembly over
the sensing chamber cover and twisting until it snaps
into place.
8. Replace the housing by aligning the three triangular
slots on the base with their counterparts on the housing. Gently press the housing until it locks in place.
Check to make sure that the thermistors are in the upright position.
9. Reinstall the detector.
10. Notify the proper authorities that the system is back in
operation.
Figure 5. Removal of cover and screen for cleaning:
REMOVABLE
HOUSING
;;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyyy
;;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyyy
;;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyyy
;;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyyy
;;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyyy
;;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyyy
;;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyyy
;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyy
;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyy
;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyy
;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyy
;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyy
;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyy
;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyy
INSTALLATION AND MAINTENANCE INSTRUCTIONS
2112/24ATR
Photoelectronic Smoke Detector with
Fixed Heat and Integral Temp-3 Sounder
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Figure 1. Wiring diagram for the 2112/24ATR detector:
REMOVABLE
SCREEN
IMPORTANT: OBSERVE POLARITY
As with all sounder models, polarity must be observed on the power connections.
POWER +
TO
DETECTORS
SENSING
CHAMBER
COVER
–
SENSING
CHAMBER
UL LISTED
COMPATIBLE
CONTROL
PANEL
BASE
A78-2565-04
NC
(OPTIONAL) COMMON
RELEASING
NO
DEVICE
+ P
+ W
– R
A ALARM
A CONTACT
NC
NC A
(OPTIONAL) COMMON
RELEASING
C U
NO
DEVICE
NO X
+ P
+ W
– R
A ALARM
A CONTACT
NC A
C U
NO X
EOL POWER
SUPERVISION
RELAY (SHOWN
ENERGIZED)
A77-716 12/24V
EOL RESISTOR
SPECIFIED BY
PANEL
MANUFACTURER
INITIATING
LOOP
OPTIONAL CLASS A WIRING
Specifications
Diameter:
Height (including mounting bracket):
Weight:
Operating Temperature Range:
Operating Humidity Range:
Latching Alarm:
Audible Signal:
Heat Sensor:
Electrical Ratings
System Voltage (nominal):
Minimum:
Maximum:
Maximum Ripple Voltage:
Standby Current:
Alarm Current:
Please refer to insert for the Limitations of Fire Alarm Systems
Three-Year Limited Warranty
System Sensor warrants its enclosed smoke detector to be free from defects in materials and workmanship under normal use and service for a
period of three years from date of manufacture. System Sensor makes no
other express warranty for this smoke detector. No agent, representative,
dealer, or employee of the Company has the authority to increase or alter
the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the repair or replacement of any part of
the smoke detector which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll
free number 800-SENSOR2 (736-7672) for a Return Authorization number,
send defective units postage prepaid to: System Sensor, Repair DepartD200-84-00
ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please
include a note describing the malfunction and suspected cause of failure.
The Company shall not be obligated to repair or replace units which are
found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case
shall the Company be liable for any consequential or incidental damages
for breach of this or any other Warranty, expressed or implied whatsoever,
even if the loss or damage is caused by the Company’s negligence or fault.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to
you. This Warranty gives you specific legal rights, and you may also have
other rights which vary from state to state.
4
I56-1240-02R
© 2001 System Sensor
Reset Voltage:
Reset Time:
Start-up Time:
EOL Relay:
Alarm Initiation and Auxiliary Relay:
Contact Ratings, Resistive Load:
Special Considerations:
5.5 inches (140 mm)
2.05 inches (52 mm)
7.5 oz. (210 g)
32° to 100° F (0° to 38° C)
10% to 93% Relative Humidity, Noncondensing
Reset by momentary power interruption
85 dBA minimum when in alarm or with supply polarity reversed
135° F Fixed Temperature Electronic Thermistor
12 or 24 VDC
10 VDC
35 VDC
30% of nom. Voltage (peak to peak)
50 µA maximum
49 mA typical, 60 mA max. at 12V
57 mA typical, 65 mA max. at 24V
0.8 VDC minimum
1.0 second maximum
30 seconds maximum (after 60 sec. reset)
A77-716B, 12/24 VDC
1A @ 30 VAC
1A @ 30 VDC
Due to the built-in temporal pattern, use these detectors only with a non-coded
power supply.
NOTICE: This manual shall be left with the owner/user of
this equipment.
Before Installing
Please thoroughly read the System Sensor manual I56-407,
Guide for Proper Use of System Smoke Detectors, which provides detailed information on detector spacing, placement,
zoning, wiring, and special applications. Copies of this
manual are available at no charge from System Sensor.
D200-84-00
A78-2336-16
IMPORTANT: This detector must be tested and maintained
following NFPA 72 requirements. The detector should be
cleaned at least once a year.
1
I56-1240-02R
Figure 2. Surface mounting of 2112/24ATR smoke
detector on 31/2-inch and 4-inch octagonal box:
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
Mounting
Each 2112/24ATR detector is supplied with a mounting
bracket that permits the detector to be mounted:
1. To a single gang box, or
2. Directly to a 3-1/2 inch or 4 inch octagonal box, or
3. To a 4 inch square electrical box by using a plaster ring.
4. Directly to the ceiling using drywall anchors, if
permitted by local codes and/or the authority having
jurisdiction.
Tamper-resistant Feature
This detector includes a tamper-resistant feature that prevents its removal from the bracket without the use of a tool.
To make the detector tamper-resistant, remove the smaller
tab by breaking it at the scribed line on the tamper resistant
tab on the detector mounting bracket (see Figure 3), then
install the detector. To remove the detector from the bracket
once it has been made tamper resistant, use a small screwdriver to depress the tamper-resistant tab, located in the
slot on the mounting bracket, and turn the detector counterclockwise.
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
A78-2563-03
General Description
Model 2112/24ATR is a 4-wire photoelectronic smoke detector that uses a state-of-the-art optical sensing chamber.
This detector also provides restorable, 135˚F fixed-temperature heat detection. The units have a heat detection
unit that is integrated with the photoelectronic sensor.
In addition, a piezoelectric horn in each detector produces
an interrupted, 85 dBA tone when the individual detector
alarms or when the supply voltage polarity is reversed.
NOTE: In order for all detectors on a loop to sound when
the panel alarms, the panel must reverse the supply voltage polarity to that loop upon alarm. For panels that do
not reverse the polarity during alarm, a reversing relay,
such as Systems Sensor’s RR-2, must be used. The RR-2
is designed to allow all the detectors in the same loop to
sound when one of the detectors goes into alarm. Some
panels may require the use of programmable outputs.
Refer to System Sensor literature for further information
on the RR-2.
Wiring Installation Guidelines
All wiring must be installed in compliance with the National Electrical Code, applicable local codes, and any special requirements of the local authority having jurisdiction.
Proper wire gauges should be used. The conductors used to
connect smoke detectors to control panels and accessory
devices should be color-coded to reduce the likelihood of
wiring errors. Improper connections can prevent a system
from responding properly in the event of a fire.
Installation of this detector is simplified by the use of a
mounting bracket and a plug-in screw terminal block that
can be prewired to the system, allowing the detector to be
easily installed or removed for cleaning. The detector’s
sensitivity can be tested in place using the MOD400R Test
Module.
The screw terminal block accepts 14 – 22 gauge wire. For
best system performance, all wiring should be installed in
separate grounded conduit. Do not mix fire system wiring
in the same conduit as any other electrical wiring. Twisted
pair may be used to provide additional protection against
electrical interference.
An LED on the detector provides a local visual indication of
the detector’s status. If power is applied to the detector and
it is functioning normally in standby within the listed sensitivity range, the status LED blinks every ten seconds. The
LED also latches on in alarm.
Smoke detectors and alarm system control panels have
specifications for allowable loop resistance. Consult the
control panel specifications for the total loop resistance allowed for the control panel being used before wiring the
detector loops.
If the LED stops blinking, the unit should be removed for
maintenance and inspection.
Wire connections are made by stripping about 1/4 inch of
insulation from the end of the feed wire, inserting the wire
into the appropriate terminal, and tightening the screw to
secure the wire in place.
Installation
WARNING
Remove power from the control unit or initiating device circuits before installing detectors.
1. Wire the plug-in screw terminal block per Figure 1 and
plug the terminal block into the detector.
2. Align the arrows on the detector with the arrows on the
mounting bracket.
3. Turn the detector clockwise in the mounting bracket until it clicks into place.
4. After all detectors have been installed, apply power to
the control unit or initiating device circuits.
5. Test the detector as described in TESTING.
6. Reset the detector at the system control panel.
7. Notify the proper authorities the system is in operation.
Both smoke and heat detection testing are recommended
for verifying system protection capability.
A detector that fails to activate with any of the above tests
should first be cleaned as outlined in MAINTENANCE. If
the detector still fails to activate, return it for repair.
CAUTION
Dust covers are an effective way to limit the entry of dust
into smoke detector sensing chambers. However, they may
not completely prevent airborne dust particles from entering the detector. Therefore, System Sensor recommends the
removal of detectors before beginning construction or other
dust producing activity. Be sure to remove dust covers from
any sensors that were left in place during construction as
part of returning the system to service.
Notify the proper authorities the system is back in
operation.
Testing
NOTE: Before testing, notify the proper authorities that
the smoke detector system is undergoing maintenance and will be temporarily out of service. Disable the zone or system undergoing maintenance
to prevent unwanted alarms.
Maintenance
NOTE: Before removing the detector, notify the proper authorities that the smoke detector system is undergoing maintenance and will be temporarily out of
service. Disable the zone or system undergoing
maintenance to prevent unwanted alarms.
NOTE: Before removing the detector cover, note the position of the thermistors. Make sure the thermistors
are not bent over when the housing is replaced.
Detectors must be tested after installation and following
periodic maintenance. Test the 2112/24ATR as follows:
A. Test Switch
1. A recessed test switch is located on the detector housing (See Figure 4).
1. Remove the detector housing by gently prying the four
housing tabs on the bottom of the base with a smallbladed screwdriver and pull the housing from the base.
Use caution to avoid damaging the thermistors.
2. Vacuum the screen carefully without removing it.
Figure 4. Top and side views showing position of test switch:
Figure 3. 2112/24ATR smoke detector mounting bracket:
TAMPER RESISTANT TAB
(CUT OFF SMALL TAB TO
ACTIVATE TAMPER-RESIST
FEATURE)
TAMPER SLOT
(DEPRESS TAB TO
REMOVE DETECTOR)
2. Press and hold the recessed test switch with a 0.18
inch maximum diameter tool such as an allen wrench
or small screwdriver.
3. The detector’s LED should light within 5 seconds.
B. Test Module (System Sensor Model No. MOD400R).
The MOD400R test module can be used with a DMM or
analog voltmeter to check the detector sensitivity as described in the test module’s manual.
C. Smoke Entry Test
Hold a smoldering punk stick or cotton wick at the side
of the detector and gently blow smoke through the detector until the unit alarms.
D. Direct Heat Method (Hair dryer of 1000-1500 watts)
Direct the heat toward either of the side thermistors.
Hold the heat source about 12 inches from the detector
in order to avoid damage to the plastic. The detector will
reset only after it has had sufficient time to cool and the
power source has been momentarily interrupted.
LED
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
ALIGNMENT
ARROWS
TEST MODULE
SOCKET
PUSH RECESSED
SWITCH WITH A
0.18″ MAX. DIAMETER TOOL
RECESSED TEST
SWITCH
A78-2564-00
A78-2333-01
D200-84-00
2
I56-1240-02R
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
D200-84-00
3
I56-1240-02R
Figure 2. Surface mounting of 2112/24ATR smoke
detector on 31/2-inch and 4-inch octagonal box:
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
Mounting
Each 2112/24ATR detector is supplied with a mounting
bracket that permits the detector to be mounted:
1. To a single gang box, or
2. Directly to a 3-1/2 inch or 4 inch octagonal box, or
3. To a 4 inch square electrical box by using a plaster ring.
4. Directly to the ceiling using drywall anchors, if
permitted by local codes and/or the authority having
jurisdiction.
Tamper-resistant Feature
This detector includes a tamper-resistant feature that prevents its removal from the bracket without the use of a tool.
To make the detector tamper-resistant, remove the smaller
tab by breaking it at the scribed line on the tamper resistant
tab on the detector mounting bracket (see Figure 3), then
install the detector. To remove the detector from the bracket
once it has been made tamper resistant, use a small screwdriver to depress the tamper-resistant tab, located in the
slot on the mounting bracket, and turn the detector counterclockwise.
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
A78-2563-03
General Description
Model 2112/24ATR is a 4-wire photoelectronic smoke detector that uses a state-of-the-art optical sensing chamber.
This detector also provides restorable, 135˚F fixed-temperature heat detection. The units have a heat detection
unit that is integrated with the photoelectronic sensor.
In addition, a piezoelectric horn in each detector produces
an interrupted, 85 dBA tone when the individual detector
alarms or when the supply voltage polarity is reversed.
NOTE: In order for all detectors on a loop to sound when
the panel alarms, the panel must reverse the supply voltage polarity to that loop upon alarm. For panels that do
not reverse the polarity during alarm, a reversing relay,
such as Systems Sensor’s RR-2, must be used. The RR-2
is designed to allow all the detectors in the same loop to
sound when one of the detectors goes into alarm. Some
panels may require the use of programmable outputs.
Refer to System Sensor literature for further information
on the RR-2.
Wiring Installation Guidelines
All wiring must be installed in compliance with the National Electrical Code, applicable local codes, and any special requirements of the local authority having jurisdiction.
Proper wire gauges should be used. The conductors used to
connect smoke detectors to control panels and accessory
devices should be color-coded to reduce the likelihood of
wiring errors. Improper connections can prevent a system
from responding properly in the event of a fire.
Installation of this detector is simplified by the use of a
mounting bracket and a plug-in screw terminal block that
can be prewired to the system, allowing the detector to be
easily installed or removed for cleaning. The detector’s
sensitivity can be tested in place using the MOD400R Test
Module.
The screw terminal block accepts 14 – 22 gauge wire. For
best system performance, all wiring should be installed in
separate grounded conduit. Do not mix fire system wiring
in the same conduit as any other electrical wiring. Twisted
pair may be used to provide additional protection against
electrical interference.
An LED on the detector provides a local visual indication of
the detector’s status. If power is applied to the detector and
it is functioning normally in standby within the listed sensitivity range, the status LED blinks every ten seconds. The
LED also latches on in alarm.
Smoke detectors and alarm system control panels have
specifications for allowable loop resistance. Consult the
control panel specifications for the total loop resistance allowed for the control panel being used before wiring the
detector loops.
If the LED stops blinking, the unit should be removed for
maintenance and inspection.
Wire connections are made by stripping about 1/4 inch of
insulation from the end of the feed wire, inserting the wire
into the appropriate terminal, and tightening the screw to
secure the wire in place.
Installation
WARNING
Remove power from the control unit or initiating device circuits before installing detectors.
1. Wire the plug-in screw terminal block per Figure 1 and
plug the terminal block into the detector.
2. Align the arrows on the detector with the arrows on the
mounting bracket.
3. Turn the detector clockwise in the mounting bracket until it clicks into place.
4. After all detectors have been installed, apply power to
the control unit or initiating device circuits.
5. Test the detector as described in TESTING.
6. Reset the detector at the system control panel.
7. Notify the proper authorities the system is in operation.
Both smoke and heat detection testing are recommended
for verifying system protection capability.
A detector that fails to activate with any of the above tests
should first be cleaned as outlined in MAINTENANCE. If
the detector still fails to activate, return it for repair.
CAUTION
Dust covers are an effective way to limit the entry of dust
into smoke detector sensing chambers. However, they may
not completely prevent airborne dust particles from entering the detector. Therefore, System Sensor recommends the
removal of detectors before beginning construction or other
dust producing activity. Be sure to remove dust covers from
any sensors that were left in place during construction as
part of returning the system to service.
Notify the proper authorities the system is back in
operation.
Testing
NOTE: Before testing, notify the proper authorities that
the smoke detector system is undergoing maintenance and will be temporarily out of service. Disable the zone or system undergoing maintenance
to prevent unwanted alarms.
Maintenance
NOTE: Before removing the detector, notify the proper authorities that the smoke detector system is undergoing maintenance and will be temporarily out of
service. Disable the zone or system undergoing
maintenance to prevent unwanted alarms.
NOTE: Before removing the detector cover, note the position of the thermistors. Make sure the thermistors
are not bent over when the housing is replaced.
Detectors must be tested after installation and following
periodic maintenance. Test the 2112/24ATR as follows:
A. Test Switch
1. A recessed test switch is located on the detector housing (See Figure 4).
1. Remove the detector housing by gently prying the four
housing tabs on the bottom of the base with a smallbladed screwdriver and pull the housing from the base.
Use caution to avoid damaging the thermistors.
2. Vacuum the screen carefully without removing it.
Figure 4. Top and side views showing position of test switch:
Figure 3. 2112/24ATR smoke detector mounting bracket:
TAMPER RESISTANT TAB
(CUT OFF SMALL TAB TO
ACTIVATE TAMPER-RESIST
FEATURE)
TAMPER SLOT
(DEPRESS TAB TO
REMOVE DETECTOR)
2. Press and hold the recessed test switch with a 0.18
inch maximum diameter tool such as an allen wrench
or small screwdriver.
3. The detector’s LED should light within 5 seconds.
B. Test Module (System Sensor Model No. MOD400R).
The MOD400R test module can be used with a DMM or
analog voltmeter to check the detector sensitivity as described in the test module’s manual.
C. Smoke Entry Test
Hold a smoldering punk stick or cotton wick at the side
of the detector and gently blow smoke through the detector until the unit alarms.
D. Direct Heat Method (Hair dryer of 1000-1500 watts)
Direct the heat toward either of the side thermistors.
Hold the heat source about 12 inches from the detector
in order to avoid damage to the plastic. The detector will
reset only after it has had sufficient time to cool and the
power source has been momentarily interrupted.
LED
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
ALIGNMENT
ARROWS
TEST MODULE
SOCKET
PUSH RECESSED
SWITCH WITH A
0.18″ MAX. DIAMETER TOOL
RECESSED TEST
SWITCH
A78-2564-00
A78-2333-01
D200-84-00
2
I56-1240-02R
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;
D200-84-00
3
I56-1240-02R
3. Remove screen assembly, pulling straight out (please
see Figure 5).
4. Remove the sensing chamber cover.
5. Clean the sensing chamber by vacuuming or blowing
out dust and particles.
6. Replace the sensing chamber cover, aligning the arrow
on the cover top with the arrow on the printed circuit
board.
7. Replace the screen by placing the screen assembly over
the sensing chamber cover and twisting until it snaps
into place.
8. Replace the housing by aligning the three triangular
slots on the base with their counterparts on the housing. Gently press the housing until it locks in place.
Check to make sure that the thermistors are in the upright position.
9. Reinstall the detector.
10. Notify the proper authorities that the system is back in
operation.
Figure 5. Removal of cover and screen for cleaning:
REMOVABLE
HOUSING
;;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyyy
;;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyyy
;;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyyy
;;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyyy
;;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyyy
;;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyyy
;;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyyy
;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyy
;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyy
;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyy
;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyy
;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyy
;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyy
;;;;;;;;;;;;;;;
yyyyyyyyyyyyyyy
INSTALLATION AND MAINTENANCE INSTRUCTIONS
2112/24ATR
Photoelectronic Smoke Detector with
Fixed Heat and Integral Temp-3 Sounder
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Figure 1. Wiring diagram for the 2112/24ATR detector:
REMOVABLE
SCREEN
IMPORTANT: OBSERVE POLARITY
As with all sounder models, polarity must be observed on the power connections.
POWER +
TO
DETECTORS
SENSING
CHAMBER
COVER
–
SENSING
CHAMBER
UL LISTED
COMPATIBLE
CONTROL
PANEL
BASE
A78-2565-04
NC
(OPTIONAL) COMMON
RELEASING
NO
DEVICE
+ P
+ W
– R
A ALARM
A CONTACT
NC
NC A
(OPTIONAL) COMMON
RELEASING
C U
NO
DEVICE
NO X
+ P
+ W
– R
A ALARM
A CONTACT
NC A
C U
NO X
EOL POWER
SUPERVISION
RELAY (SHOWN
ENERGIZED)
A77-716 12/24V
EOL RESISTOR
SPECIFIED BY
PANEL
MANUFACTURER
INITIATING
LOOP
OPTIONAL CLASS A WIRING
Specifications
Diameter:
Height (including mounting bracket):
Weight:
Operating Temperature Range:
Operating Humidity Range:
Latching Alarm:
Audible Signal:
Heat Sensor:
Electrical Ratings
System Voltage (nominal):
Minimum:
Maximum:
Maximum Ripple Voltage:
Standby Current:
Alarm Current:
Please refer to insert for the Limitations of Fire Alarm Systems
Three-Year Limited Warranty
System Sensor warrants its enclosed smoke detector to be free from defects in materials and workmanship under normal use and service for a
period of three years from date of manufacture. System Sensor makes no
other express warranty for this smoke detector. No agent, representative,
dealer, or employee of the Company has the authority to increase or alter
the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the repair or replacement of any part of
the smoke detector which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll
free number 800-SENSOR2 (736-7672) for a Return Authorization number,
send defective units postage prepaid to: System Sensor, Repair DepartD200-84-00
ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please
include a note describing the malfunction and suspected cause of failure.
The Company shall not be obligated to repair or replace units which are
found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case
shall the Company be liable for any consequential or incidental damages
for breach of this or any other Warranty, expressed or implied whatsoever,
even if the loss or damage is caused by the Company’s negligence or fault.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to
you. This Warranty gives you specific legal rights, and you may also have
other rights which vary from state to state.
4
I56-1240-02R
© 2001 System Sensor
Reset Voltage:
Reset Time:
Start-up Time:
EOL Relay:
Alarm Initiation and Auxiliary Relay:
Contact Ratings, Resistive Load:
Special Considerations:
5.5 inches (140 mm)
2.05 inches (52 mm)
7.5 oz. (210 g)
32° to 100° F (0° to 38° C)
10% to 93% Relative Humidity, Noncondensing
Reset by momentary power interruption
85 dBA minimum when in alarm or with supply polarity reversed
135° F Fixed Temperature Electronic Thermistor
12 or 24 VDC
10 VDC
35 VDC
30% of nom. Voltage (peak to peak)
50 µA maximum
49 mA typical, 60 mA max. at 12V
57 mA typical, 65 mA max. at 24V
0.8 VDC minimum
1.0 second maximum
30 seconds maximum (after 60 sec. reset)
A77-716B, 12/24 VDC
1A @ 30 VAC
1A @ 30 VDC
Due to the built-in temporal pattern, use these detectors only with a non-coded
power supply.
NOTICE: This manual shall be left with the owner/user of
this equipment.
Before Installing
Please thoroughly read the System Sensor manual I56-407,
Guide for Proper Use of System Smoke Detectors, which provides detailed information on detector spacing, placement,
zoning, wiring, and special applications. Copies of this
manual are available at no charge from System Sensor.
D200-84-00
A78-2336-16
IMPORTANT: This detector must be tested and maintained
following NFPA 72 requirements. The detector should be
cleaned at least once a year.
1
I56-1240-02R